Buildings.Fluid.SolarCollectors.Data.GlazedFlatPlate
Package with SRCC rating information for glazed flat-plate solar thermal collectors
Information
Package with records for SRCC rating information for glazed flat-plate solar thermal collector. All models in the GlazedFlatPlate package are tested according to the ASHRAE Standard 93.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
![]() |
FP - Guandong Fivestar Solar Energy Co, FS-PTY95-2.0 |
![]() |
FP - Solahart Kf |
![]() |
Default values in the TRNSYS Simulation Studio SDHW example |
![]() |
FP - Therma-Lite, HS-20 |
![]() |
FP - All inputs necessary for verification of EN12975 models |
Buildings.Fluid.SolarCollectors.Data.GlazedFlatPlate.FP_GuangdongFSPTY95
FP - Guandong Fivestar Solar Energy Co, FS-PTY95-2.0
Information
References
Ratings data taken from the
Solar Rating and Certification Corporation website. SRCC# = 2012043A.
Extends from Buildings.Fluid.SolarCollectors.Data.GenericASHRAE93 (Generic data record for ASHRAE93 solar collector models).
Contents
Type | Name | Default | Description |
---|---|---|---|
Area | A | 2 | Area [m2] |
HeatCapacity | CTyp | Buildings.Fluid.SolarCollect... | Total thermal capacity or fluid volume and 'dry' thermal capacity or mass |
HeatCapacity | C | 0 | Dry or total thermal capacity of the solar thermal collector [J/K] |
Volume | V | 1.7/1000 | Fluid volume [m3] |
Mass | mDry | 35 | Dry mass [kg] |
Real | mperA_flow_nominal | 0.02 | Nominal mass flow rate per unit area of collector [kg/(s.m2)] |
PressureDifference | dp_nominal | 235 | Nominal pressure drop [Pa] |
Angle | incAngDat[:] | Modelica.Units.Conversions.f... | Incident angle data [rad] |
Real | incAngModDat[size(incAngDat, 1)] | {1.0,0.9967,0.9862,0.9671,0.... | Incident angle modifier data [1] |
Real | y_intercept | 0.678 | y intercept (Maximum efficiency) [1] |
CoefficientOfHeatTransfer | slope | -4.426 | Slope from rating data [W/(m2.K)] |
Modelica definition
Buildings.Fluid.SolarCollectors.Data.GlazedFlatPlate.FP_SolahartKf
FP - Solahart Kf
Information
References
Ratings data taken from the
Solar Rating and Certification Corporation website. SRCC# = 2012021A.
Extends from Buildings.Fluid.SolarCollectors.Data.GenericASHRAE93 (Generic data record for ASHRAE93 solar collector models).
Contents
Type | Name | Default | Description |
---|---|---|---|
Area | A | 2.003 | Area [m2] |
HeatCapacity | CTyp | Buildings.Fluid.SolarCollect... | Total thermal capacity or fluid volume and 'dry' thermal capacity or mass |
HeatCapacity | C | 0 | Dry or total thermal capacity of the solar thermal collector [J/K] |
Volume | V | 3.8/1000 | Fluid volume [m3] |
Mass | mDry | 42 | Dry mass [kg] |
Real | mperA_flow_nominal | 0.0194 | Nominal mass flow rate per unit area of collector [kg/(s.m2)] |
PressureDifference | dp_nominal | 93.89 | Nominal pressure drop [Pa] |
Angle | incAngDat[:] | Modelica.Units.Conversions.f... | Incident angle data [rad] |
Real | incAngModDat[size(incAngDat, 1)] | {1.0,0.9979,0.9913,0.9792,0.... | Incident angle modifier data [1] |
Real | y_intercept | 0.775 | y intercept (Maximum efficiency) [1] |
CoefficientOfHeatTransfer | slope | -5.103 | Slope from rating data [W/(m2.K)] |
Modelica definition
Buildings.Fluid.SolarCollectors.Data.GlazedFlatPlate.FP_TRNSYSValidation
Default values in the TRNSYS Simulation Studio SDHW example
Information
Default values in the TRNSYS Simualtion Studio SDHW example.
No value for dp_nominal
was provided in TRNSYS, so 100
Pascal was used as a placeholder.
Extends from Buildings.Fluid.SolarCollectors.Data.GenericASHRAE93 (Generic data record for ASHRAE93 solar collector models).
Contents
Type | Name | Default | Description |
---|---|---|---|
Area | A | 5 | Area [m2] |
HeatCapacity | CTyp | Buildings.Fluid.SolarCollect... | Total thermal capacity or fluid volume and 'dry' thermal capacity or mass |
HeatCapacity | C | 0 | Dry or total thermal capacity of the solar thermal collector [J/K] |
Volume | V | 0.6/1000 | Fluid volume [m3] |
Mass | mDry | 8.6 | Dry mass [kg] |
Real | mperA_flow_nominal | 0.0111 | Nominal mass flow rate per unit area of collector [kg/(s.m2)] |
PressureDifference | dp_nominal | 100 | Nominal pressure drop [Pa] |
Angle | incAngDat[:] | Modelica.Units.Conversions.f... | Incident angle data [rad] |
Real | incAngModDat[size(incAngDat, 1)] | {1.0,0.9969,0.9872,0.9691,0.... | Incident angle modifier data [1] |
Real | y_intercept | 0.8 | y intercept (Maximum efficiency) [1] |
CoefficientOfHeatTransfer | slope | -3.6111 | Slope from rating data [W/(m2.K)] |
Modelica definition
Buildings.Fluid.SolarCollectors.Data.GlazedFlatPlate.FP_ThermaLiteHS20
FP - Therma-Lite, HS-20
Information
References
Ratings data taken from the Solar Rating and Certification Corporation website. SRCC# = 2012047A.
Extends from Buildings.Fluid.SolarCollectors.Data.GenericASHRAE93 (Generic data record for ASHRAE93 solar collector models).
Contents
Type | Name | Default | Description |
---|---|---|---|
Area | A | 1.97 | Area [m2] |
HeatCapacity | CTyp | Buildings.Fluid.SolarCollect... | Total thermal capacity or fluid volume and 'dry' thermal capacity or mass |
HeatCapacity | C | 0 | Dry or total thermal capacity of the solar thermal collector [J/K] |
Volume | V | 2.8/1000 | Fluid volume [m3] |
Mass | mDry | 26 | Dry mass [kg] |
Real | mperA_flow_nominal | 0.1777 | Nominal mass flow rate per unit area of collector [kg/(s.m2)] |
PressureDifference | dp_nominal | 242.65 | Nominal pressure drop [Pa] |
Angle | incAngDat[:] | Modelica.Units.Conversions.f... | Incident angle data [rad] |
Real | incAngModDat[size(incAngDat, 1)] | {1.0,0.9989,0.9946,0.9836,0.... | Incident angle modifier data [1] |
Real | y_intercept | 0.762 | y intercept (Maximum efficiency) [1] |
CoefficientOfHeatTransfer | slope | -3.710 | Slope from rating data [W/(m2.K)] |
Modelica definition
Buildings.Fluid.SolarCollectors.Data.GlazedFlatPlate.FP_VerificationModel
FP - All inputs necessary for verification of EN12975 models
Information
No model on the Solar Rating and Certification Corporation website tested to EN12975 standards provides all of the necessary information for modeling. This data record was created to allow verification of EN12975 base classes despite the limitations in available data.
Extends from Buildings.Fluid.SolarCollectors.Data.GenericEN12975 (Generic data record for EN12975 solar collector models).
Contents
Type | Name | Default | Description |
---|---|---|---|
Area | A | 4.302 | Area [m2] |
HeatCapacity | CTyp | Buildings.Fluid.SolarCollect... | Total thermal capacity or fluid volume and 'dry' thermal capacity or mass |
HeatCapacity | C | 0 | Dry or total thermal capacity of the solar thermal collector [J/K] |
Volume | V | 4.4/1000 | Fluid volume [m3] |
Mass | mDry | 484 | Dry mass [kg] |
Real | mperA_flow_nominal | 0.0241 | Nominal mass flow rate per unit area of collector [kg/(s.m2)] |
PressureDifference | dp_nominal | 100 | Nominal pressure drop [Pa] |
Angle | incAngDat[:] | Modelica.Units.Conversions.f... | Incident angle data [rad] |
Real | incAngModDat[size(incAngDat, 1)] | {1.0,0.9967,0.9862,0.9671,0.... | Incident angle modifier data [1] |
Real | IAMDiff | 0.133 | Incidence angle modifier for diffuse irradiance (incidence angle of 50°) [1] |
Real | eta0 | 0.720 | Optical efficiency (Maximum efficiency) [1] |
CoefficientOfHeatTransfer | a1 | 2.8312 | First order heat loss coefficient [W/(m2.K)] |
Real | a2 | 0.00119 | Second order heat loss coefficient [W/(m2.K2)] |