Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data
Data records for BESTEST validation
Information
This package contains data records for the BESTEST validation.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
Case600FFResults | BESTEST comparison results free-floating |
Case600Mass | BESTEST600 |
Case600Results | BESTEST comparison results |
Case900Mass | BESTEST900 |
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600FFResults
BESTEST comparison results free-floating
Information
BESTEST results for annual heating and cooling loads in free-floating mode.
Extends from Modelica.Icons.Record (Icon for records).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Temperature | TavgMax | 299.05 | Maximum average annual air temperature [K] |
Temperature | TavgMin | 297.35 | Minimum average annual air temperature [K] |
Modelica definition
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Mass
BESTEST600
Information
Thermal mass for Case600Mass.
Extends from Buildings.ThermalZones.ISO13790.Data.Generic (Generic data record for building thermal mass).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Thermal mass | |||
Real | heaC | 51289.8 | Heat capacity per unit area of the floor [J/(K.m2)] |
Real | facMas | 4.522 | Effective mass area factor [1] |
Modelica definition
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Results
BESTEST comparison results
Information
BESTEST results for annual heating and cooling loads.
Extends from Modelica.Icons.Record (Icon for records).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Energy | EHeaMax | 20552400000 | Maximum annual heating load [J] |
Energy | EHeaMin | 15465600000 | Minimum annaul heating load [J] |
Energy | ECooMax | -26200800000 | Maximum annual cooling load [J] |
Energy | ECooMin | -22093200000 | Minimum annual cooling load [J] |
Power | PHeaMax | 4354 | Maximum peak heating load [W] |
Power | PHeaMin | 3437 | Minimum peak heating load [W] |
Power | PCooMax | -6827 | Maximum peak cooling load [W] |
Power | PCooMin | -5965 | Minimum peak cooling load [W] |
Modelica definition
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case900Mass
BESTEST900
Information
Thermal mass for Case900Mass.
Extends from Buildings.ThermalZones.ISO13790.Data.Generic (Generic data record for building thermal mass).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Thermal mass | |||
Real | heaC | 249272 | Heat capacity per unit area of the floor [J/(K.m2)] |
Real | facMas | 2.7 | Effective mass area factor [1] |