Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data

Data records for BESTEST validation

Information

This package contains data records for the BESTEST validation.

Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).

Package Content

Name Description
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600FFResults Case600FFResults BESTEST comparison results free-floating
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Mass Case600Mass BESTEST600
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Results Case600Results BESTEST comparison results
Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case900Mass Case900Mass BESTEST900

Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600FFResults Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600FFResults

BESTEST comparison results free-floating

Information

BESTEST results for annual heating and cooling loads in free-floating mode.

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
TemperatureTavgMax299.05Maximum average annual air temperature [K]
TemperatureTavgMin297.35Minimum average annual air temperature [K]

Modelica definition

record Case600FFResults "BESTEST comparison results free-floating" extends Modelica.Icons.Record; parameter Modelica.Units.SI.Temperature TavgMax=299.05 "Maximum average annual air temperature"; parameter Modelica.Units.SI.Temperature TavgMin=297.35 "Minimum average annual air temperature"; end Case600FFResults;

Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Mass Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Mass

BESTEST600

Information

Thermal mass for Case600Mass.

Extends from Buildings.ThermalZones.ISO13790.Data.Generic (Generic data record for building thermal mass).

Parameters

TypeNameDefaultDescription
Thermal mass
RealheaC51289.8Heat capacity per unit area of the floor [J/(K.m2)]
RealfacMas4.522Effective mass area factor [1]

Modelica definition

record Case600Mass = Buildings.ThermalZones.ISO13790.Data.Generic ( heaC=51289.8, facMas=4.522) "BESTEST600";

Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Results Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case600Results

BESTEST comparison results

Information

BESTEST results for annual heating and cooling loads.

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
EnergyEHeaMax20552400000Maximum annual heating load [J]
EnergyEHeaMin15465600000Minimum annaul heating load [J]
EnergyECooMax-26200800000Maximum annual cooling load [J]
EnergyECooMin-22093200000Minimum annual cooling load [J]
PowerPHeaMax4354Maximum peak heating load [W]
PowerPHeaMin3437Minimum peak heating load [W]
PowerPCooMax-6827Maximum peak cooling load [W]
PowerPCooMin-5965Minimum peak cooling load [W]

Modelica definition

record Case600Results "BESTEST comparison results" extends Modelica.Icons.Record; parameter Modelica.Units.SI.Energy EHeaMax=20552400000 "Maximum annual heating load"; parameter Modelica.Units.SI.Energy EHeaMin=15465600000 "Minimum annaul heating load"; parameter Modelica.Units.SI.Energy ECooMax=-26200800000 "Maximum annual cooling load"; parameter Modelica.Units.SI.Energy ECooMin=-22093200000 "Minimum annual cooling load"; parameter Modelica.Units.SI.Power PHeaMax=4354 "Maximum peak heating load"; parameter Modelica.Units.SI.Power PHeaMin=3437 "Minimum peak heating load"; parameter Modelica.Units.SI.Power PCooMax=-6827 "Maximum peak cooling load"; parameter Modelica.Units.SI.Power PCooMin=-5965 "Minimum peak cooling load"; end Case600Results;

Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case900Mass Buildings.ThermalZones.ISO13790.Validation.BESTEST.Data.Case900Mass

BESTEST900

Information

Thermal mass for Case900Mass.

Extends from Buildings.ThermalZones.ISO13790.Data.Generic (Generic data record for building thermal mass).

Parameters

TypeNameDefaultDescription
Thermal mass
RealheaC249272Heat capacity per unit area of the floor [J/(K.m2)]
RealfacMas2.7Effective mass area factor [1]

Modelica definition

record Case900Mass = Buildings.ThermalZones.ISO13790.Data.Generic ( heaC=249272, facMas=2.7) "BESTEST900";