Buildings.Templates.Plants.HeatPumps.Components.HeatPumpGroups
Models for heat pump groups
Information
This package contains models of heat pump groups.
Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Package Content
| Name | Description | 
|---|---|
|  AirToWater | Air-to-water heat pump group | 
 Buildings.Templates.Plants.HeatPumps.Components.HeatPumpGroups.AirToWater
Buildings.Templates.Plants.HeatPumps.Components.HeatPumpGroups.AirToWater
Air-to-water heat pump group
 
Information
This model represents a group of heat pumps.
Extends from Buildings.Templates.Plants.HeatPumps.Components.Interfaces.PartialHeatPumpGroup (Interface for heat pump group).
Parameters
| Type | Name | Default | Description | 
|---|---|---|---|
| replaceable package MediumHeaWat | Water | HW medium | |
| replaceable package MediumSou | Water | Source-side medium | |
| replaceable package MediumAir | Air | Air medium | |
| HeatPumpGroup | dat | Design and operating parameters | |
| Configuration | |||
| Integer | nHp | Number of heat pumps | |
| HeatPump | typ | Buildings.Templates.Componen... | Equipment type | 
| Boolean | is_rev | Set to true for reversible heat pumps, false for heating only | |
| HeatPumpModel | typMod | Buildings.Templates.Componen... | Type of heat pump model | 
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state | 
| Assumptions | |||
| Boolean | allowFlowReversal | true | Load side flow reversal: false to simplify equations, assuming, but not enforcing, no flow reversal | 
| Boolean | allowFlowReversalSou | true | Source side flow reversal: false to simplify equations, assuming, but not enforcing, no flow reversal | 
| Boolean | have_preDroChiHeaWat | true | Set to true for CHW/HW pressure drop computed by this model, false for external computation | 
| Boolean | have_preDroSou | true | Set to true for source fluid pressure drop computed by this model, false for external computation | 
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed | 
Connectors
| Type | Name | Description | 
|---|---|---|
| replaceable package MediumSou | Source-side medium | |
| FluidPorts_b | ports_bChiHeaWat[nHp] | CHW/HW supply | 
| FluidPorts_a | ports_aChiHeaWat[nHp] | CHW/HW return | 
| FluidPorts_b | ports_bSou[nHp] | Source fluid return (from heat pumps) | 
| FluidPorts_a | ports_aSou[nHp] | Source fluid supply (to heat pumps) | 
| Bus | bus | Plant control bus | 
| Bus | busWea | Weather bus | 
Modelica definition
model AirToWater
  "Air-to-water heat pump group"
  extends Buildings.Templates.Plants.HeatPumps.Components.Interfaces.PartialHeatPumpGroup
    (
    redeclare final package MediumSou=MediumAir,
    final typ=Buildings.Templates.Components.Types.HeatPump.AirToWater,
    final typMod=Buildings.Templates.Components.Types.HeatPumpModel.EquationFit);
  Buildings.Templates.Components.HeatPumps.AirToWater hp[nHp](
    redeclare each final package MediumHeaWat=MediumHeaWat,
    redeclare each final package MediumAir=MediumAir,
    each final is_rev=is_rev,
    final dat=datHp,
    each final allowFlowReversal=allowFlowReversal,
    each final energyDynamics=energyDynamics,
    each final have_preDroChiHeaWat=have_preDroChiHeaWat,
    each final have_preDroSou=have_preDroSou)
    "Heat pump unit";
equation 
  for i in 1:nHp loop
    connect(busWea, hp[i].busWea);
  end for;
  connect(ports_aChiHeaWat, hp.port_a);
  connect(hp.port_b, ports_bChiHeaWat);
  connect(busHp, hp.bus);
  connect(ports_aSou, hp.port_aSou);
  connect(ports_bSou, hp.port_bSou);
end AirToWater;