Buildings.Templates.AirHandlersFans.Validation.UserProject.Data

Package with classes for storing system parameters

Information

This package provides records for design and operating parameters that are used for validation purposes.

Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).

Package Content

Name Description
Buildings.Templates.AirHandlersFans.Validation.UserProject.Data.AllSystems AllSystems Top-level (whole building) system parameters

Buildings.Templates.AirHandlersFans.Validation.UserProject.Data.AllSystems Buildings.Templates.AirHandlersFans.Validation.UserProject.Data.AllSystems

Top-level (whole building) system parameters

Information

This class provides the set of sizing and operating parameters for the whole HVAC system. It is aimed for validation purposes only.

Extends from Buildings.Templates.Data.AllSystems (Top-level (whole building) system parameters).

Parameters

TypeNameDefaultDescription
UnitssysUniBuildings.Templates.Types.Un...Unit system
EnergyStandardstdEneBuildings.Controls.OBC.ASHRA...Energy standard
VentilationStandardstdVenBuildings.Controls.OBC.ASHRA...Ventilation standard
ASHRAEClimateZoneashCliZonBuildings.Controls.OBC.ASHRA...ASHRAE climate zone
Title24ClimateZonetit24CliZon California Title 24 climate zone
Air handlers and fans
VAVMultiZoneVAV_1VAV_1(id="VAV_1", damOut(dp_...Parameters for system VAV_1

Modelica definition

class AllSystems "Top-level (whole building) system parameters" extends Buildings.Templates.Data.AllSystems( sysUni=Buildings.Templates.Types.Units.SI, stdEne=Buildings.Controls.OBC.ASHRAE.G36.Types.EnergyStandard.ASHRAE90_1, stdVen=Buildings.Controls.OBC.ASHRAE.G36.Types.VentilationStandard.ASHRAE62_1, ashCliZon=Buildings.Controls.OBC.ASHRAE.G36.Types.ASHRAEClimateZone.Zone_3B); parameter Buildings.Templates.AirHandlersFans.Data.VAVMultiZone VAV_1( id="VAV_1", damOut(dp_nominal=15), damOutMin(dp_nominal=15), damRel(dp_nominal=15), damRet(dp_nominal=15), mOutMin_flow_nominal=0.2, fanSup(m_flow_nominal=1, dp_nominal=500), fanRel(m_flow_nominal=1, dp_nominal=200), fanRet(m_flow_nominal=1, dp_nominal=200), coiHeaPre( cap_nominal=1e4, dpAir_nominal=100, dpWat_nominal=0.5e4, dpValve_nominal=0.3e4, mWat_flow_nominal=1e4/4186/10, TAirEnt_nominal=273.15, TWatEnt_nominal=50 + 273.15), coiHeaReh( cap_nominal=1e4, dpAir_nominal=100, dpWat_nominal=0.5e4, dpValve_nominal=0.3e4, mWat_flow_nominal=1e4/4186/10, TAirEnt_nominal=273.15, TWatEnt_nominal=50 + 273.15), coiCoo( cap_nominal=1e4, dpAir_nominal=100, dpWat_nominal=3e4, dpValve_nominal=2e4, mWat_flow_nominal=1e4/4186/5, TAirEnt_nominal=30 + 273.15, TWatEnt_nominal=7 + 273.15, wAirEnt_nominal=0.012), ctl( VOutUnc_flow_nominal=0.4, VOutTot_flow_nominal=0.5, VOutAbsMin_flow_nominal=0.3, VOutMin_flow_nominal=0.4, dpDamOutMinAbs=10, dpDamOutMin_nominal=15, pAirSupSet_rel_max=500, pAirRetSet_rel_min=10, pAirRetSet_rel_max=40, yFanSup_min=0.1, yFanRel_min=0.1, yFanRet_min=0.1, dVFanRet_flow=0.1, TAirSupSet_min=12+273.15, TAirSupSet_max=18+273.15, TOutRes_min=16+273.15, TOutRes_max=21+273.15)) "Parameters for system VAV_1"; end AllSystems;