Buildings.Fluid.DXSystems.Heating.AirSource.Examples.PerformanceCurves

Package with several performance curves

Information

This package contains performance curves for the coil heat transfer capacity and the EIR of air source DX cooling and heating coils that are used in the examples.

The data are described in Buildings.Fluid.DXSystems.Heating.AirSource.Data.Generic.DXCoil.

Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).

Package Content

Name Description
Buildings.Fluid.DXSystems.Heating.AirSource.Examples.PerformanceCurves.Curve_I Curve_I DX heating coil performance curve I

Buildings.Fluid.DXSystems.Heating.AirSource.Examples.PerformanceCurves.Curve_I Buildings.Fluid.DXSystems.Heating.AirSource.Examples.PerformanceCurves.Curve_I

DX heating coil performance curve I

Information

This record declares performance curves for the heating capacity and the EIR for use in Buildings.Fluid.DXSystems.Heating.AirSource.Examples.SingleSpeed. It has been obtained from the EnergyPlus 9.6 example file PackagedTerminalHeatPump.idf.

Extends from Buildings.Fluid.DXSystems.Heating.AirSource.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.9135970355,0.0127860478,0...Biquadratic coefficients for heating capacity function of temperature
RealcapFunFF[:]{0.84,0.16,0,0}Polynomial coefficients for heating capacity function of flow fration
RealEIRFunT[6]{0.6019839404,-0.0053765594,...Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.3824,-0.4336,0.0512}Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin17.78 + 273.15Minimum condenser inlet temperature for heating capacity function [K]
TemperatureTConInMax23.33 + 273.15Maximum condenser inlet temperature for heating capacity function [K]
TemperatureTEvaInMin-30.56 + 273.15Minimum evaporator inlet temperature for heating capacity function [K]
TemperatureTEvaInMax17.22 + 273.15Maximum evaporator inlet temperature for heating capacity function [K]
RealffMin0.5Minimum flow fraction for which performance data are valid
RealffMax1.5Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_I "DX heating coil performance curve I" extends Buildings.Fluid.DXSystems.Heating.AirSource.Data.Generic.BaseClasses.PerformanceCurve ( capFunT={0.9135970355,0.0127860478,0.0000527533,-0.0005917719,0.000136017, -0.0000894155}, capFunFF={0.84,0.16,0,0}, EIRFunT={0.6019839404,-0.0053765594,0.000773762,0.0186496391,0.0002225627,-0.0008182042}, EIRFunFF={1.3824,-0.4336,0.0512}, TConInMin=17.78+273.15, TConInMax=23.33+273.15, TEvaInMin=-30.56+273.15, TEvaInMax=17.22+273.15, ffMin=0.5, ffMax=1.5); end Curve_I;