Buildings.Fluid.DXSystems.Heating.AirSource.Examples.PerformanceCurves
Package with several performance curves
Information
This package contains performance curves for the coil heat transfer capacity and the EIR of air source DX cooling and heating coils that are used in the examples.
The data are described in Buildings.Fluid.DXSystems.Heating.AirSource.Data.Generic.DXCoil.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
Curve_I | DX heating coil performance curve I |
Buildings.Fluid.DXSystems.Heating.AirSource.Examples.PerformanceCurves.Curve_I
DX heating coil performance curve I
Information
This record declares performance curves for the heating capacity and the EIR for use in
Buildings.Fluid.DXSystems.Heating.AirSource.Examples.SingleSpeed.
It has been obtained from the EnergyPlus 9.6 example file
PackagedTerminalHeatPump.idf
.
Extends from Buildings.Fluid.DXSystems.Heating.AirSource.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.9135970355,0.0127860478,0... | Biquadratic coefficients for heating capacity function of temperature |
Real | capFunFF[:] | {0.84,0.16,0,0} | Polynomial coefficients for heating capacity function of flow fration |
Real | EIRFunT[6] | {0.6019839404,-0.0053765594,... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.3824,-0.4336,0.0512} | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 17.78 + 273.15 | Minimum condenser inlet temperature for heating capacity function [K] |
Temperature | TConInMax | 23.33 + 273.15 | Maximum condenser inlet temperature for heating capacity function [K] |
Temperature | TEvaInMin | -30.56 + 273.15 | Minimum evaporator inlet temperature for heating capacity function [K] |
Temperature | TEvaInMax | 17.22 + 273.15 | Maximum evaporator inlet temperature for heating capacity function [K] |
Real | ffMin | 0.5 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.5 | Maximum flow fraction for which performance data are valid |