Buildings.Fluid.DXSystems.Cooling.BaseClasses.Examples.PerformanceCurves
Package with sevral performance curves
Information
This package contains performance curves for the cooling capacity and the EIR of DX cooling coils that are used in the examples.
The data are described in Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.DXCoil.
Package Content
Name | Description |
---|---|
Curve_III_AirCooled | Curve_III for air source DX coils |
Curve_II_AirCooled | Curve_II for air source DX coils |
Curve_I_AirCooled | Curve_I for air source DX coils |
Curve_I_WaterCooled | Curve_I for water source DX coils |
Buildings.Fluid.DXSystems.Cooling.BaseClasses.Examples.PerformanceCurves.Curve_III_AirCooled
Curve_III for air source DX coils
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
5ZoneAutoDXVAV.idf
.
Extends from Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.476428,0.0401147000,0.000... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.47278589,1.2433415,-1.038... | Polynomial coefficients for cooling capacity function of flow fraction |
Real | EIRFunT[6] | {0.632475,-0.0121321000,0.00... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.0079484,0.34544129,-0.692... | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 297.03889 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.5 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.5 | Maximum flow fraction for which performance data are valid |
Modelica definition
Buildings.Fluid.DXSystems.Cooling.BaseClasses.Examples.PerformanceCurves.Curve_II_AirCooled
Curve_II for air source DX coils
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
DXCoilSystemAuto.idf
.
Extends from Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.766956,0.0107756,-0.00004... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.8,0.2,0,0} | Polynomial coefficients for cooling capacity function of flow fraction |
Real | EIRFunT[6] | {0.297145,0.0430933,-0.00074... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.1552,-0.1808,0.0256,0} | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 291.15 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.5 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.5 | Maximum flow fraction for which performance data are valid |
Modelica definition
Buildings.Fluid.DXSystems.Cooling.BaseClasses.Examples.PerformanceCurves.Curve_I_AirCooled
Curve_I for air source DX coils
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
AirflowNetwork_MultiZone_House.idf
.
Extends from Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.942587793,0.009543347,0.0... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.8,0.2,0,0} | Polynomial coefficients for cooling capacity function of flow fraction |
Real | EIRFunT[6] | {0.342414409,0.034885008,-0.... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.1552,-0.1808,0.0256,0} | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 291.15 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.6 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.8 | Maximum flow fraction for which performance data are valid |
Modelica definition
Buildings.Fluid.DXSystems.Cooling.BaseClasses.Examples.PerformanceCurves.Curve_I_WaterCooled
Curve_I for water source DX coils
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
5ZoneAutoDXVAV.idf
.
Extends from Buildings.Fluid.DXSystems.Cooling.WaterSource.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.476428,0.0401147000,0.000... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.47278589,1.2433415,-1.038... | Polynomial coefficients for cooling capacity function of flow fraction |
Real | EIRFunT[6] | {0.632475,-0.0121321000,0.00... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.0079484,0.34544129,-0.692... | Polynomial coefficients for EIR function of flow fration |
Real | capFunFFCon[:] | {0.47278589,1.2433415,-1.038... | Polynomial coefficients for cooling capacity function of water flow fration at condensers |
Real | EIRFunFFCon[:] | {1.0079484,0.34544129,-0.692... | Polynomial coefficients for EIR function of water flow fraction at condensers |
Minimum and maximum values | |||
Temperature | TConInMin | 297.03889 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.5 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.5 | Maximum flow fraction for which performance data are valid |
Real | ffConMin | 0.5 | Minimum water flow fraction at condensers for which performance data are valid |
Real | ffConMax | 1.5 | Maximum water flow fraction at condensers for which performance data are valid |