Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR
Performance data for chiller ElectricReformulatedEIR
Information
Package with performance data for chillers.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
Generic | Generic data record for chiller ElectricReformulatedEIR |
ReformEIRChiller_McQuay_WSC_471kW_5_89COP_Vanes | ReformEIRChiller McQuay WSC 471kW/5.89COP/Vanes |
ReformEIRChiller_York_YT_563kW_10_61COP_Vanes | ReformEIRChiller York YT 563kW/10.61COP/Vanes |
ReformEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes | ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes |
ReformEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes | ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes |
ReformEIRChiller_Carrier_19XR_742kW_5_42COP_VSD | ReformEIRChiller Carrier 19XR 742kW/5.42COP/VSD |
ReformEIRChiller_McQuay_WSC_816kW_6_74COP_Vanes | ReformEIRChiller McQuay WSC 816kW/6.74COP/Vanes |
ReformEIRChiller_McQuay_PEH_819kW_8_11COP_Vanes | ReformEIRChiller McQuay PEH 819kW/8.11COP/Vanes |
ReformEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes | ReformEIRChiller Carrier 19XR 823kW/6.28COP/Vanes |
ReformEIRChiller_Carrier_19XR_869kW_5_57COP_VSD | ReformEIRChiller Carrier 19XR 869kW/5.57COP/VSD |
ReformEIRChiller_Carrier_19XR_897kW_7_23COP_VSD | ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD |
ReformEIRChiller_Carrier_19XR_897kW_6_50COP_Vanes | ReformEIRChiller Carrier 19XR 897kW/6.50COP/Vanes |
ReformEIRChiller_York_YT_897kW_7_60COP_VSD | ReformEIRChiller York YT 897kW/7.60COP/VSD |
ReformEIRChiller_York_YT_897kW_6_27COP_VSD | ReformEIRChiller York YT 897kW/6.27COP/VSD |
ReformEIRChiller_Carrier_19XR_897kW_6_23COP_VSD | ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD |
ReformEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes | ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes |
ReformEIRChiller_York_YT_960kW_4_64COP_Vanes | ReformEIRChiller York YT 960kW/4.64COP/Vanes |
ReformEIRChiller_York_YT_1023kW_5_81COP_Vanes | ReformEIRChiller York YT 1023kW/5.81COP/Vanes |
ReformEIRChiller_McQuay_PEH_1030kW_8_58COP_Vanes | ReformEIRChiller McQuay PEH 1030kW/8.58COP/Vanes |
ReformEIRChiller_York_YT_1048kW_6_06COP_Vanes | ReformEIRChiller York YT 1048kW/6.06COP/Vanes |
ReformEIRChiller_York_YT_1055kW_5_96COP_Vanes | ReformEIRChiller York YT 1055kW/5.96COP/Vanes |
ReformEIRChiller_Carrier_19XR_1076kW_5_52COP_Vanes | ReformEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes |
ReformEIRChiller_Trane_CVHE_1080kW_7_39COP_Vanes | ReformEIRChiller Trane CVHE 1080kW/7.39COP/Vanes |
ReformEIRChiller_York_YT_1090kW_7_57COP_VSD | ReformEIRChiller York YT 1090kW/7.57COP/VSD |
ReformEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes | ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes |
ReformEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes | ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes |
ReformEIRChiller_York_YT_1125kW_7_92COP_VSD | ReformEIRChiller York YT 1125kW/7.92COP/VSD |
ReformEIRChiller_Trane_CVHE_1129kW_7_19COP_Vanes | ReformEIRChiller Trane CVHE 1129kW/7.19COP/Vanes |
ReformEIRChiller_Carrier_19XR_1143kW_6_57COP_VSD | ReformEIRChiller Carrier 19XR 1143kW/6.57COP/VSD |
ReformEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD | ReformEIRChiller Carrier 19XR 1157kW/5.62COP/VSD |
ReformEIRChiller_Carrier_19XR_1196kW_6_50COP_Vanes | ReformEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes |
ReformEIRChiller_Carrier_19XR_1213kW_7_78COP_Vanes | ReformEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes |
ReformEIRChiller_McQuay_PEH_1231kW_6_18COP_Vanes | ReformEIRChiller McQuay PEH 1231kW/6.18COP/Vanes |
ReformEIRChiller_Carrier_19XR_1234kW_5_39COP_VSD | ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD |
ReformEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes | ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes |
ReformEIRChiller_York_YK_1259kW_6_45COP_Vanes | ReformEIRChiller York YK 1259kW/6.45COP/Vanes |
ReformEIRChiller_York_YT_1266kW_4_39COP_Vanes | ReformEIRChiller York YT 1266kW/4.39COP/Vanes |
ReformEIRChiller_Carrier_19XR_1284kW_6_20COP_Vanes | ReformEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes |
ReformEIRChiller_Carrier_19XR_1294kW_7_61COP_Vanes | ReformEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes |
ReformEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes | ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes |
ReformEIRChiller_Carrier_19XR_1350kW_7_90COP_VSD | ReformEIRChiller Carrier 19XR 1350kW/7.90COP/VSD |
ReformEIRChiller_York_YT_1368kW_7_35COP_VSD | ReformEIRChiller York YT 1368kW/7.35COP/VSD |
ReformEIRChiller_Trane_CVHE_1372kW_7_49COP_Vanes | ReformEIRChiller Trane CVHE 1372kW/7.49COP/Vanes |
ReformEIRChiller_York_YT_1396kW_7_35COP_Vanes | ReformEIRChiller York YT 1396kW/7.35COP/Vanes |
ReformEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD | ReformEIRChiller Carrier 19XR 1403kW/7.09COP/VSD |
ReformEIRChiller_York_YT_1403kW_6_94COP_VSD | ReformEIRChiller York YT 1403kW/6.94COP/VSD |
ReformEIRChiller_Trane_CVHE_1407kW_7_14COP_VSD | ReformEIRChiller Trane CVHE 1407kW/7.14COP/VSD |
ReformEIRChiller_McQuay_PFH_1407kW_6_60COP_Vanes | ReformEIRChiller McQuay PFH 1407kW/6.60COP/Vanes |
ReformEIRChiller_Carrier_19XR_1407kW_6_04COP_VSD | ReformEIRChiller Carrier 19XR 1407kW/6.04COP/VSD |
ReformEIRChiller_Carrier_19XR_1410kW_8_54COP_VSD | ReformEIRChiller Carrier 19XR 1410kW/8.54COP/VSD |
ReformEIRChiller_Trane_CVHE_1442kW_6_61COP_VSD | ReformEIRChiller Trane CVHE 1442kW/6.61COP/VSD |
ReformEIRChiller_York_YT_1459kW_6_40COP_VSD | ReformEIRChiller York YT 1459kW/6.40COP/VSD |
ReformEIRChiller_Trane_CVHE_1484kW_9_96COP_VSD | ReformEIRChiller Trane CVHE 1484kW/9.96COP/VSD |
ReformEIRChiller_York_YT_1495kW_7_51COP_VSD | ReformEIRChiller York YT 1495kW/7.51COP/VSD |
ReformEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes | ReformEIRChiller McQuay WSC 1519kW/7.10COP/Vanes |
ReformEIRChiller_Carrier_19XR_1558kW_5_81COP_VSD | ReformEIRChiller Carrier 19XR 1558kW/5.81COP/VSD |
ReformEIRChiller_Carrier_19XR_1586kW_5_53COP_VSD | ReformEIRChiller Carrier 19XR 1586kW/5.53COP/VSD |
ReformEIRChiller_McQuay_PEH_1635kW_7_47COP_Vanes | ReformEIRChiller McQuay PEH 1635kW/7.47COP/Vanes |
ReformEIRChiller_Carrier_19XR_1635kW_6_36COP_Vanes | ReformEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes |
ReformEIRChiller_Carrier_19XR_1656kW_8_24COP_VSD | ReformEIRChiller Carrier 19XR 1656kW/8.24COP/VSD |
ReformEIRChiller_York_YT_1663kW_9_34COP_Vanes | ReformEIRChiller York YT 1663kW/9.34COP/Vanes |
ReformEIRChiller_Carrier_19XL_1674kW_7_89COP_Vanes | ReformEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes |
ReformEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes | ReformEIRChiller Trane CVHF 1681kW/6.59COP/Vanes |
ReformEIRChiller_Carrier_19XR_1723kW_8_32COP_VSD | ReformEIRChiller Carrier 19XR 1723kW/8.32COP/VSD |
ReformEIRChiller_Carrier_19XR_1727kW_9_04COP_Vanes | ReformEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes |
ReformEIRChiller_McQuay_WSC_1751kW_6_73COP_Vanes | ReformEIRChiller McQuay WSC 1751kW/6.73COP/Vanes |
ReformEIRChiller_Trane_CVHF_1758kW_5_96COP_Vanes | ReformEIRChiller Trane CVHF 1758kW/5.96COP/Vanes |
ReformEIRChiller_York_YT_1758kW_5_76COP_VSD | ReformEIRChiller York YT 1758kW/5.76COP/VSD |
ReformEIRChiller_York_YT_1758kW_6_26COP_Vanes | ReformEIRChiller York YT 1758kW/6.26COP/Vanes |
ReformEIRChiller_York_YT_1758kW_5_96COP_Vanes | ReformEIRChiller York YT 1758kW/5.96COP/Vanes |
ReformEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes | ReformEIRChiller Trane CVHE 1758kW/5.96COP/Vanes |
ReformEIRChiller_York_YT_1758kW_6_28COP_Vanes | ReformEIRChiller York YT 1758kW/6.28COP/Vanes |
ReformEIRChiller_Carrier_19XR_1758kW_5_86COP_VSD | ReformEIRChiller Carrier 19XR 1758kW/5.86COP/VSD |
ReformEIRChiller_Trane_CVHF_1758kW_6_46COP_VSD | ReformEIRChiller Trane CVHF 1758kW/6.46COP/VSD |
ReformEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes | ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes |
ReformEIRChiller_Carrier_19XR_1776kW_8_00COP_Vanes | ReformEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes |
ReformEIRChiller_Carrier_19XL_1779kW_6_18COP_Vanes | ReformEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes |
ReformEIRChiller_Trane_CVHF_1779kW_6_18COP_Vanes | ReformEIRChiller Trane CVHF 1779kW/6.18COP/Vanes |
ReformEIRChiller_York_YT_1794kW_8_11COP_Vanes | ReformEIRChiller York YT 1794kW/8.11COP/Vanes |
ReformEIRChiller_York_YT_1794kW_7_90COP_VSD | ReformEIRChiller York YT 1794kW/7.90COP/VSD |
ReformEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes | ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes |
ReformEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD | ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD |
ReformEIRChiller_York_YT_1867kW_10_09COP_Vanes | ReformEIRChiller York YT 1867kW/10.09COP/Vanes |
ReformEIRChiller_Carrier_19XL_1871kW_6_49COP_Vanes | ReformEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes |
ReformEIRChiller_York_YT_1881kW_6_77COP_VSD | ReformEIRChiller York YT 1881kW/6.77COP/VSD |
ReformEIRChiller_York_YK_1881kW_6_53COP_Vanes | ReformEIRChiller York YK 1881kW/6.53COP/Vanes |
ReformEIRChiller_McQuay_PEH_1895kW_6_42COP_Vanes | ReformEIRChiller McQuay PEH 1895kW/6.42COP/Vanes |
ReformEIRChiller_York_YT_1934kW_7_55COP_Vanes | ReformEIRChiller York YT 1934kW/7.55COP/Vanes |
ReformEIRChiller_McQuay_PEH_1934kW_6_01COP_Vanes | ReformEIRChiller McQuay PEH 1934kW/6.01COP/Vanes |
ReformEIRChiller_McQuay_WDC_1973kW_6_28COP_Vanes | ReformEIRChiller McQuay WDC 1973kW/6.28COP/Vanes |
ReformEIRChiller_York_YK_1997kW_7_24COP_Vanes | ReformEIRChiller York YK 1997kW/7.24COP/Vanes |
ReformEIRChiller_McQuay_PFH_2043kW_8_44COP_Vanes | ReformEIRChiller McQuay PFH 2043kW/8.44COP/Vanes |
ReformEIRChiller_Trane_CVHF_2043kW_9_08COP_Vanes | ReformEIRChiller Trane CVHF 2043kW/9.08COP/Vanes |
ReformEIRChiller_Carrier_19XL_2057kW_6_05COP_Vanes | ReformEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes |
ReformEIRChiller_York_YT_2110kW_7_15COP_Vanes | ReformEIRChiller York YT 2110kW/7.15COP/Vanes |
ReformEIRChiller_McQuay_PFH_2124kW_6_03COP_Vanes | ReformEIRChiller McQuay PFH 2124kW/6.03COP/Vanes |
ReformEIRChiller_York_YK_2159kW_6_85COP_Vanes | ReformEIRChiller York YK 2159kW/6.85COP/Vanes |
ReformEIRChiller_Trane_CVHF_2184kW_6_78COP_Vanes | ReformEIRChiller Trane CVHF 2184kW/6.78COP/Vanes |
ReformEIRChiller_York_YK_2201kW_6_69COP_Vanes | ReformEIRChiller York YK 2201kW/6.69COP/Vanes |
ReformEIRChiller_York_YT_2233kW_9_54COP_VSD | ReformEIRChiller York YT 2233kW/9.54COP/VSD |
ReformEIRChiller_York_YK_2237kW_6_41COP_Vanes | ReformEIRChiller York YK 2237kW/6.41COP/Vanes |
ReformEIRChiller_York_YK_2275kW_6_32COP_Vanes | ReformEIRChiller York YK 2275kW/6.32COP/Vanes |
ReformEIRChiller_Trane_CVHF_2300kW_8_10COP_Vanes | ReformEIRChiller Trane CVHF 2300kW/8.10COP/Vanes |
ReformEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD | ReformEIRChiller Trane CVHF 2317kW/6.33COP/VSD |
ReformEIRChiller_Carrier_19XR_2391kW_6_77COP_Vanes | ReformEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes |
ReformEIRChiller_Carrier_19XR_2391kW_6_44COP_VSD | ReformEIRChiller Carrier 19XR 2391kW/6.44COP/VSD |
ReformEIRChiller_York_YK_2412kW_5_58COP_Vanes | ReformEIRChiller York YK 2412kW/5.58COP/Vanes |
ReformEIRChiller_McQuay_PFH_2462kW_6_67COP_Vanes | ReformEIRChiller McQuay PFH 2462kW/6.67COP/Vanes |
ReformEIRChiller_Trane_CVHG670_44_86_2490kW_6_5COP | ReformEIRChiller Trane CVHG670-44&86 2490kW/6.5COP |
ReformEIRChiller_Trane_CVHF_2567kW_11_77COP_VSD | ReformEIRChiller Trane CVHF 2567kW/11.77COP/VSD |
ReformEIRChiller_York_YK_2771kW_6_84COP_VSD | ReformEIRChiller York YK 2771kW/6.84COP/VSD |
ReformEIRChiller_Trane_CVHF_2799kW_6_40COP_Vanes | ReformEIRChiller Trane CVHF 2799kW/6.40COP/Vanes |
ReformEIRChiller_York_YT_3133kW_9_16COP_Vanes | ReformEIRChiller York YT 3133kW/9.16COP/Vanes |
ReformEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes | ReformEIRChiller McQuay PFH 3165kW/6.48COP/Vanes |
ReformEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes | ReformEIRChiller McQuay PFH 4020kW/7.35COP/Vanes |
ReformEIRChiller_York_YK_4396kW_6_63COP_Vanes | ReformEIRChiller York YK 4396kW/6.63COP/Vanes |
ReformEIRChiller_York_YK_4477kW_6_64COP_Vanes | ReformEIRChiller York YK 4477kW/6.64COP/Vanes |
ReformEIRChiller_York_YK_4515kW_6_22COP_Vanes | ReformEIRChiller York YK 4515kW/6.22COP/Vanes |
ReformEIRChiller_York_YK_4537kW_6_28COP_Vanes | ReformEIRChiller York YK 4537kW/6.28COP/Vanes |
ReformEIRChiller_Trane_CVHF_4610kW_6_34COP_Vanes | ReformEIRChiller Trane CVHF 4610kW/6.34COP/Vanes |
ReformEIRChiller_Carrier_19EX_4667kW_6_16COP_Vanes | ReformEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes |
ReformEIRChiller_Trane_CVHF_4677kW_6_27COP_Vanes | ReformEIRChiller Trane CVHF 4677kW/6.27COP/Vanes |
ReformEIRChiller_York_YK_4966kW_6_05COP_Vanes | ReformEIRChiller York YK 4966kW/6.05COP/Vanes |
ReformEIRChiller_York_YK_4969kW_7_14COP_Vanes | ReformEIRChiller York YK 4969kW/7.14COP/Vanes |
ReformEIRChiller_York_YK_4969kW_7_07COP_Vanes | ReformEIRChiller York YK 4969kW/7.07COP/Vanes |
ReformEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes | ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes |
ReformEIRChiller_Carrier_19EX_5148kW_6_34COP_Vanes | ReformEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes |
ReformEIRChiller_York_YK_5170kW_7_15COP_Vanes | ReformEIRChiller York YK 5170kW/7.15COP/Vanes |
ReformEIRChiller_Carrier_19EX_5208kW_6_88COP_Vanes | ReformEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes |
ReformEIRChiller_York_YK_5465kW_6_94COP_Vanes | ReformEIRChiller York YK 5465kW/6.94COP/Vanes |
ReformEIRChiller_York_YK_5549kW_6_50COP_Vanes | ReformEIRChiller York YK 5549kW/6.50COP/Vanes |
ReformEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes | ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes |
ReformEIRChiller_Multistack_MS_172kW_3_67COP_None | ReformEIRChiller Multistack MS 172kW/3.67COP/None |
ReformEIRChiller_Trane_RTWA_383kW_4_17COP_Valve | ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve |
ReformEIRChiller_Trane_RTHB_531kW_4_83COP_Valve | ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve |
ReformEIRChiller_Trane_RTHB_538kW_5_12COP_Valve | ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve |
ReformEIRChiller_Trane_RTHB_542kW_5_26COP_Valve | ReformEIRChiller Trane RTHB 542kW/5.26COP/Valve |
ReformEIRChiller_York_YS_672kW_7_90COP_Valve | ReformEIRChiller York YS 672kW/7.90COP/Valve |
ReformEIRChiller_Carrier_23XL_686kW_5_91COP_Valve | ReformEIRChiller Carrier 23XL 686kW/5.91COP/Valve |
ReformEIRChiller_Trane_RTHC_707kW_7_77COP_Valve | ReformEIRChiller Trane RTHC 707kW/7.77COP/Valve |
ReformEIRChiller_York_YS_756kW_7_41COP_Valve | ReformEIRChiller York YS 756kW/7.41COP/Valve |
ReformEIRChiller_York_YS_781kW_5_42COP_Valve | ReformEIRChiller York YS 781kW/5.42COP/Valve |
ReformEIRChiller_Carrier_23XL_830kW_6_97COP_Valve | ReformEIRChiller Carrier 23XL 830kW/6.97COP/Valve |
ReformEIRChiller_Carrier_23XL_862kW_6_11COP_Valve | ReformEIRChiller Carrier 23XL 862kW/6.11COP/Valve |
ReformEIRChiller_Carrier_23XL_862kW_6_84COP_Valve | ReformEIRChiller Carrier 23XL 862kW/6.84COP/Valve |
ReformEIRChiller_Carrier_23XL_865kW_6_05COP_Valve | ReformEIRChiller Carrier 23XL 865kW/6.05COP/Valve |
ReformEIRChiller_York_YS_879kW_5_82COP_Valve | ReformEIRChiller York YS 879kW/5.82COP/Valve |
ReformEIRChiller_Trane_RTHC_1009kW_5_37COP_Valve | ReformEIRChiller Trane RTHC 1009kW/5.37COP/Valve |
ReformEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve | ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve |
ReformEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve | ReformEIRChiller Carrier 23XL 1062kW/5.50COP/Valve |
ReformEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve | ReformEIRChiller Trane RTHC 1066kW/5.73COP/Valve |
ReformEIRChiller_Trane_RTHC_1094kW_6_55COP_Valve | ReformEIRChiller Trane RTHC 1094kW/6.55COP/Valve |
ReformEIRChiller_Carrier_23XL_1108kW_6_92COP_Valve | ReformEIRChiller Carrier 23XL 1108kW/6.92COP/Valve |
ReformEIRChiller_York_YS_1171kW_9_15COP_Valve | ReformEIRChiller York YS 1171kW/9.15COP/Valve |
ReformEIRChiller_Carrier_23XL_1196kW_6_39COP_Valve | ReformEIRChiller Carrier 23XL 1196kW/6.39COP/Valve |
ReformEIRChiller_York_YS_1554kW_9_31COP_Valve | ReformEIRChiller York YS 1554kW/9.31COP/Valve |
ReformEIRChiller_York_YS_1758kW_5_84COP_Valve | ReformEIRChiller York YS 1758kW/5.84COP/Valve |
ReformEIRChiller_Trane_CGWD_207kW_3_99COP_None | ReformEIRChiller Trane CGWD 207kW/3.99COP/None |
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic
Generic data record for chiller ElectricReformulatedEIR
Information
This record is used as a template for performance data for the chiller model Buildings.Fluid.Chillers.ElectricReformulatedEIR. To provide performance data for Buildings.Fluid.Chillers.ElectricEIR, use Buildings.Fluid.Chillers.Data.ElectricEIR.Generic instead.Extends from Buildings.Fluid.Chillers.Data.BaseClasses.Chiller (Base classes for chiller models).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | Maximum part load ratio | |
Real | PLRMinUnl | Minimum part unload ratio | |
Real | PLRMin | Minimum part load ratio | |
Real | etaMotor | Fraction of compressor motor heat entering refrigerant | |
Temperature | TConLvg_nominal | Temperature of fluid leaving condenser at nominal condition [K] | |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | Reference capacity (negative number) [W] | |
Real | COP_nominal | Reference coefficient of performance | |
MassFlowRate | mEva_flow_nominal | Nominal mass flow at evaporator [kg/s] | |
MassFlowRate | mCon_flow_nominal | Nominal mass flow at condenser [kg/s] | |
Temperature | TEvaLvg_nominal | Temperature of fluid leaving evaporator at nominal condition [K] | |
Performance curves | |||
Integer | nCapFunT | 6 | Number of coefficients for capFunT |
Integer | nEIRFunT | 6 | Number of coefficients for EIRFunT |
Integer | nEIRFunPLR | 10 | Number of coefficients for EIRFunPLR |
Real | capFunT[nCapFunT] | Biquadratic coefficients for capFunT | |
Real | EIRFunT[nEIRFunT] | Biquadratic coefficients for EIRFunT | |
Real | EIRFunPLR[nEIRFunPLR] | Coefficients for EIRFunPLR | |
Temperature | TEvaLvgMin | Minimum value for leaving evaporator temperature [K] | |
Temperature | TEvaLvgMax | Maximum value for leaving evaporator temperature [K] | |
Temperature | TConLvgMin | Minimum value for leaving condenser temperature [K] | |
Temperature | TConLvgMax | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_WSC_471kW_5_89COP_Vanes
ReformEIRChiller McQuay WSC 471kW/5.89COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay WSC 471kW/5.89COP/Vanes, !- Name 471200, !- Reference Capacity {W} 5.89, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 33.52, !- Reference Leaving Condenser Water Temperature {C} 0.01035, !- Reference Chilled Water Flow Rate {m3/s} 0.01924, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay WSC 471kW/5.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 33.52 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -471200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01035 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01924 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-4.862465E-01,-7.293218E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.522647E-01,-3.311790E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.215998E-01,-2.209969E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.81 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.09 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_563kW_10_61COP_Vanes
ReformEIRChiller York YT 563kW/10.61COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 563kW/10.61COP/Vanes, !- Name 562600, !- Reference Capacity {W} 10.61, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 18.89, !- Reference Leaving Condenser Water Temperature {C} 0.01514, !- Reference Chilled Water Flow Rate {m3/s} 0.0241, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 563kW/10.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 563kW/10.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 563kW/10.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 18.89 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -562600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.841837E-01,-1.006253E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-5.308783E-01,-8.364102E-02... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.931998E+00,-2.128161E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.47 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.52 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes
ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes, !- Name 703300, !- Reference Capacity {W} 7.03, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.40, !- Reference Leaving Condenser Water Temperature {C} 0.02019, !- Reference Chilled Water Flow Rate {m3/s} 0.02902, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.40 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -703300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02019 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02902 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.336180E-01,6.473161E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.177961E-01,-1.756394E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.342644E+00,-1.060883E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.28 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.25 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes
ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes, !- Name 724400, !- Reference Capacity {W} 6.04, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.44, !- Reference Leaving Condenser Water Temperature {C} 0.01779, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.44 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -724400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.116010E-01,-1.058351E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.899136E-01,1.976846E-02,8... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.645490E-01,2.732140E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.12 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.40 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_742kW_5_42COP_VSD
ReformEIRChiller Carrier 19XR 742kW/5.42COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 742kW/5.42COP/VSD, !- Name 742000, !- Reference Capacity {W} 5.42, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.86, !- Reference Leaving Condenser Water Temperature {C} 0.01779, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 742kW/5.42COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.86 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -742000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.769438E-01,-2.149731E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.131963E+00,-4.201196E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.301853E-02,1.740092E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.11 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.90 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_WSC_816kW_6_74COP_Vanes
ReformEIRChiller McQuay WSC 816kW/6.74COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay WSC 816kW/6.74COP/Vanes, !- Name 815800, !- Reference Capacity {W} 6.74, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 32.05, !- Reference Leaving Condenser Water Temperature {C} 0.01748, !- Reference Chilled Water Flow Rate {m3/s} 0.04164, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay WSC 816kW/6.74COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.05 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -815800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.74 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01748 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04164 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.237537E-01,1.013316E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.251890E-01,-1.477434E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.166838E-01,-1.114911E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.41 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.45 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_819kW_8_11COP_Vanes
ReformEIRChiller McQuay PEH 819kW/8.11COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 819kW/8.11COP/Vanes, !- Name 819300, !- Reference Capacity {W} 8.11, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 18.59, !- Reference Leaving Condenser Water Temperature {C} 0.02524, !- Reference Chilled Water Flow Rate {m3/s} 0.03785, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 819kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 18.59 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -819300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02524 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.519141E-01,1.393287E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.447588E-01,-3.185710E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.038400E-01,1.702895E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.51 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.07 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes
ReformEIRChiller Carrier 19XR 823kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 823kW/6.28COP/Vanes, !- Name 822900, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.70, !- Reference Leaving Condenser Water Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 823kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.70 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -822900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.746558E-01,8.556337E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.280652E-01,3.277907E-02,7... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.057586E-01,1.472161E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.99 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 29.36 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_869kW_5_57COP_VSD
ReformEIRChiller Carrier 19XR 869kW/5.57COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 869kW/5.57COP/VSD, !- Name 868600, !- Reference Capacity {W} 5.57, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 36.12, !- Reference Leaving Condenser Water Temperature {C} 0.01754, !- Reference Chilled Water Flow Rate {m3/s} 0.02593, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 869kW/5.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 36.12 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -868600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01754 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02593 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.989856E-01,1.069929E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.173193E-01,7.303695E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.317677E-01,-7.501960E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.63 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.94 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_897kW_7_23COP_VSD
ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD, !- Name 896700, !- Reference Capacity {W} 7.23, !- Reference COP {W/W} 9.82, !- Reference Leaving Chilled Water Temperature {C} 29.49, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.0436, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.49 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0436 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.211989E-01,7.968670E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.970381E-01,5.701647E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.280764E-01,-5.949776E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.72 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.41 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_897kW_6_50COP_Vanes
ReformEIRChiller Carrier 19XR 897kW/6.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 897kW/6.50COP/Vanes, !- Name 896700, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 9.82, !- Reference Leaving Chilled Water Temperature {C} 29.49, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04423, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 897kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.49 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04423 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.761951E-01,5.897243E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.192535E-01,9.218992E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-5.497250E-01,5.035076E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.06 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 29.67 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_897kW_7_60COP_VSD
ReformEIRChiller York YT 897kW/7.60COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 897kW/7.60COP/VSD, !- Name 896700, !- Reference Capacity {W} 7.60, !- Reference COP {W/W} 9.83, !- Reference Leaving Chilled Water Temperature {C} 27.50, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 897kW/7.60COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 897kW/7.60COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 897kW/7.60COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 27.50 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.83 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.548168E-01,3.801839E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.207123E-01,5.394605E-05,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.019329E+00,8.590218E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.28 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 28.76 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_897kW_6_27COP_VSD
ReformEIRChiller York YT 897kW/6.27COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 897kW/6.27COP/VSD, !- Name 896700, !- Reference Capacity {W} 6.27, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 27.61, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 897kW/6.27COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 897kW/6.27COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 897kW/6.27COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 27.61 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.279200E-01,1.653602E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.276702E-01,-7.003986E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-3.773762E-02,1.134114E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.59 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 29.04 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_897kW_6_23COP_VSD
ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD, !- Name 896700, !- Reference Capacity {W} 6.23, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.49, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04442, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.49 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04442 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.691024E-01,2.885812E-02,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.640049E-01,5.766109E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.617997E-01,-8.158350E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.61 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.29 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes
ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes, !- Name 931900, !- Reference Capacity {W} 5.09, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 31.75, !- Reference Leaving Condenser Water Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.75 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -931900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.021236E+00,-1.680220E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.854031E-01,-1.891596E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.391619E-03,9.094277E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.66 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.59 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_960kW_4_64COP_Vanes
ReformEIRChiller York YT 960kW/4.64COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 960kW/4.64COP/Vanes, !- Name 960000, !- Reference Capacity {W} 4.64, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 32.01, !- Reference Leaving Condenser Water Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 960kW/4.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 960kW/4.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 960kW/4.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.1, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.1 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.01 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -960000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.474613E-01,4.071500E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.522319E-01,-1.649356E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.303041E-01,-1.499923E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.04 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.78 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1023kW_5_81COP_Vanes
ReformEIRChiller York YT 1023kW/5.81COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1023kW/5.81COP/Vanes, !- Name 1023300, !- Reference Capacity {W} 5.81, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 35.51, !- Reference Leaving Condenser Water Temperature {C} 0.02366, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1023kW/5.81COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1023kW/5.81COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1023kW/5.81COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.51 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1023300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.395788E-01,-3.084319E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.129429E-01,-1.403780E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.511511E-01,8.555669E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.34 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.55 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_1030kW_8_58COP_Vanes
ReformEIRChiller McQuay PEH 1030kW/8.58COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 1030kW/8.58COP/Vanes, !- Name 1030300, !- Reference Capacity {W} 8.58, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 20.86, !- Reference Leaving Condenser Water Temperature {C} 0.02378, !- Reference Chilled Water Flow Rate {m3/s} 0.03407, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 1030kW/8.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 20.86 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1030300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02378 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03407 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.367679E-01,2.637864E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.347930E-01,-1.901560E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.869427E-01,-1.316341E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.86 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.69 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1048kW_6_06COP_Vanes
ReformEIRChiller York YT 1048kW/6.06COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1048kW/6.06COP/Vanes, !- Name 1047900, !- Reference Capacity {W} 6.06, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.59, !- Reference Leaving Condenser Water Temperature {C} 0.04542, !- Reference Chilled Water Flow Rate {m3/s} 0.05678, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1048kW/6.06COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1048kW/6.06COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1048kW/6.06COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.59 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1047900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.06 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04542 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.846663E-01,1.059863E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.745270E-01,-3.256346E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.753623E-01,-1.409335E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.43 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 39.72 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1055kW_5_96COP_Vanes
ReformEIRChiller York YT 1055kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1055kW/5.96COP/Vanes, !- Name 1055000, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.63, !- Reference Leaving Condenser Water Temperature {C} 0.02839, !- Reference Chilled Water Flow Rate {m3/s} 0.05678, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1055000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02839 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.707500E-01,-6.904583E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.864611E-01,-1.981483E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.585491E-01,8.250769E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.24 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 39.89 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1076kW_5_52COP_Vanes
ReformEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes, !- Name 1076100, !- Reference Capacity {W} 5.52, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.30, !- Reference Leaving Condenser Water Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.30 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1076100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.52 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.850533E-01,2.837149E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.658820E-01,1.245831E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-4.774361E-01,5.162751E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.50 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.15 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1080kW_7_39COP_Vanes
ReformEIRChiller Trane CVHE 1080kW/7.39COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1080kW/7.39COP/Vanes, !- Name 1079600, !- Reference Capacity {W} 7.39, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.18, !- Reference Leaving Condenser Water Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.06416, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1080kW/7.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.18 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1079600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.621590E-01,-5.637755E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.583099E-01,-5.295487E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.528901E-01,5.293978E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.34 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 28.77 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1090kW_7_57COP_VSD
ReformEIRChiller York YT 1090kW/7.57COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1090kW/7.57COP/VSD, !- Name 1090100, !- Reference Capacity {W} 7.57, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 28.52, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1090kW/7.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1090kW/7.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1090kW/7.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.52 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1090100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.432784E-01,4.854908E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.635874E-01,-6.482460E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.594094E+00,1.294337E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.00 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.79 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes
ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes, !- Name 1104200, !- Reference Capacity {W} 8.00, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 22.59, !- Reference Leaving Condenser Water Temperature {C} 0.02423, !- Reference Chilled Water Flow Rate {m3/s} 0.03028, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 22.59 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1104200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02423 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03028 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.757836E-01,1.723720E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.355874E-01,-1.291195E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.216357E-01,6.972382E-03,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.59 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.29 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes
ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes, !- Name 1125300, !- Reference Capacity {W} 4.89, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 36.27, !- Reference Leaving Condenser Water Temperature {C} 0.02776, !- Reference Chilled Water Flow Rate {m3/s} 0.02618, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 36.27 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.738655E-01,-1.966419E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.744658E-01,-3.998991E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.526188E-01,-2.052741E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 26.10 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.56 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1125kW_7_92COP_VSD
ReformEIRChiller York YT 1125kW/7.92COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1125kW/7.92COP/VSD, !- Name 1125300, !- Reference Capacity {W} 7.92, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 18.64, !- Reference Leaving Condenser Water Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.05173, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1125kW/7.92COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1125kW/7.92COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1125kW/7.92COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 18.64 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.825851E-01,-1.890742E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.772525E-01,-1.573620E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.110875E-01,-5.972965E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.64 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.75 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1129kW_7_19COP_Vanes
ReformEIRChiller Trane CVHE 1129kW/7.19COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1129kW/7.19COP/Vanes, !- Name 1128800, !- Reference Capacity {W} 7.19, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.87, !- Reference Leaving Condenser Water Temperature {C} 0.02776, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1129kW/7.19COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.15, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.15, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.87 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1128800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.19 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.234935E-02,-6.711406E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.480712E-01,-5.163331E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.681887E-01,-1.329414E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.75 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.64 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1143kW_6_57COP_VSD
ReformEIRChiller Carrier 19XR 1143kW/6.57COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1143kW/6.57COP/VSD, !- Name 1142900, !- Reference Capacity {W} 6.57, !- Reference COP {W/W} 10.00, !- Reference Leaving Chilled Water Temperature {C} 32.79, !- Reference Leaving Condenser Water Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1143kW/6.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.79 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1142900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 10.00 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.863855E-01,3.259744E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.612126E-01,-1.211702E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.922490E-02,1.026695E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.02 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.61 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD
ReformEIRChiller Carrier 19XR 1157kW/5.62COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1157kW/5.62COP/VSD, !- Name 1156900, !- Reference Capacity {W} 5.62, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.34, !- Reference Leaving Condenser Water Temperature {C} 0.02801, !- Reference Chilled Water Flow Rate {m3/s} 0.03186, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1157kW/5.62COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.34 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1156900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.62 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02801 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03186 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.095494E+00,-5.546137E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.221566E+00,-2.771462E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.260949E-01,-1.619690E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.97 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.50 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1196kW_6_50COP_Vanes
ReformEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes, !- Name 1195600, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 31.65, !- Reference Leaving Condenser Water Temperature {C} 0.03426, !- Reference Chilled Water Flow Rate {m3/s} 0.04252, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.65 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.006647E+00,-3.596242E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.001094E+00,-1.641469E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.659565E-01,2.824668E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.72 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.03 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1213kW_7_78COP_Vanes
ReformEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes, !- Name 1213200, !- Reference Capacity {W} 7.78, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 19.63, !- Reference Leaving Condenser Water Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.04782, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1213200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04782 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.578317E-01,-2.467497E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.009816E+00,-1.640134E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.257912E-01,3.697616E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.63 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.97 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_1231kW_6_18COP_Vanes
ReformEIRChiller McQuay PEH 1231kW/6.18COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 1231kW/6.18COP/Vanes, !- Name 1230800, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.47, !- Reference Leaving Condenser Water Temperature {C} 0.03533, !- Reference Chilled Water Flow Rate {m3/s} 0.0511, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 1231kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.47 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1230800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0511 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.253381E+00,8.875124E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.880010E-01,-9.202757E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.651794E-01,-3.089335E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.98 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.25 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1234kW_5_39COP_VSD
ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD, !- Name 1234300, !- Reference Capacity {W} 5.39, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 35.73, !- Reference Leaving Condenser Water Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.03861, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.73 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1234300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.134255E-01,1.092476E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.746375E-01,9.120326E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.207212E-01,-9.914826E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.24 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.28 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes
ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes, !- Name 1258900, !- Reference Capacity {W} 6.26, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 35.80, !- Reference Leaving Condenser Water Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.03823, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.80 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03823 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.013444E+00,-3.162384E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.661241E-01,1.157734E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.602131E-02,2.433945E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.61 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.74 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_1259kW_6_45COP_Vanes
ReformEIRChiller York YK 1259kW/6.45COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 1259kW/6.45COP/Vanes, !- Name 1258900, !- Reference Capacity {W} 6.45, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 32.24, !- Reference Leaving Condenser Water Temperature {C} 0.02631, !- Reference Chilled Water Flow Rate {m3/s} 0.06246, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 1259kW/6.45COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 1259kW/6.45COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 1259kW/6.45COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.24 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.45 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02631 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06246 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.917669E-01,7.718144E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.207755E+00,2.704147E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-3.830726E-01,3.222162E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.63 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.83 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1266kW_4_39COP_Vanes
ReformEIRChiller York YT 1266kW/4.39COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1266kW/4.39COP/Vanes, !- Name 1266000, !- Reference Capacity {W} 4.39, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 41.44, !- Reference Leaving Condenser Water Temperature {C} 0.03533, !- Reference Chilled Water Flow Rate {m3/s} 0.05773, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1266kW/4.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1266kW/4.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1266kW/4.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 41.44 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1266000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05773 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.556501E-03,-4.410896E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.265473E-01,5.028662E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.253346E+00,-3.406609E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.28 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 42.31 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1284kW_6_20COP_Vanes
ReformEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes, !- Name 1283500, !- Reference Capacity {W} 6.20, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.46, !- Reference Leaving Condenser Water Temperature {C} 0.03684, !- Reference Chilled Water Flow Rate {m3/s} 0.05337, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.46 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1283500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.20 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.115795E+00,-2.963853E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.586434E-01,-1.231609E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.435414E-01,-6.553709E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.55 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.85 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1294kW_7_61COP_Vanes
ReformEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes, !- Name 1294100, !- Reference Capacity {W} 7.61, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 20.18, !- Reference Leaving Condenser Water Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 20.18 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1294100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.542077E-01,-5.459736E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.167182E+00,-4.534610E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.942311E-02,2.842914E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.18 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.56 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes
ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes, !- Name 1329300, !- Reference Capacity {W} 5.38, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 34.80, !- Reference Leaving Condenser Water Temperature {C} 0.04732, !- Reference Chilled Water Flow Rate {m3/s} 0.07098, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.29, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.29, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.29 | Minimum part unload ratio |
Real | PLRMin | 0.29 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.80 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1329300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.38 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04732 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07098 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.971340E-01,1.063097E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.460623E-01,3.685465E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-9.512023E-02,8.704652E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 26.77 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 41.98 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1350kW_7_90COP_VSD
ReformEIRChiller Carrier 19XR 1350kW/7.90COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1350kW/7.90COP/VSD, !- Name 1350400, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 19.60, !- Reference Leaving Condenser Water Temperature {C} 0.03684, !- Reference Chilled Water Flow Rate {m3/s} 0.05337, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1350kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.60 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1350400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.060586E+00,-2.817204E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.661627E-01,-1.568504E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.868582E+00,-1.412449E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.55 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.85 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1368kW_7_35COP_VSD
ReformEIRChiller York YT 1368kW/7.35COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1368kW/7.35COP/VSD, !- Name 1367900, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.80, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1368kW/7.35COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1368kW/7.35COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1368kW/7.35COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.80 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1367900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.988920E-01,-1.019014E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.787713E-01,-1.943742E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-4.466479E-01,1.188856E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.76 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.51 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1372kW_7_49COP_Vanes
ReformEIRChiller Trane CVHE 1372kW/7.49COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1372kW/7.49COP/Vanes, !- Name 1371500, !- Reference Capacity {W} 7.49, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.80, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1372kW/7.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.11, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.11 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.80 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1371500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.397637E-01,3.431595E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.033692E+00,3.558404E-02,3... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.723036E-01,8.571830E-03,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.87 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.26 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1396kW_7_35COP_Vanes
ReformEIRChiller York YT 1396kW/7.35COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1396kW/7.35COP/Vanes, !- Name 1396100, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.90, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1396kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1396kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1396kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.90 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1396100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.601322E-02,-9.771124E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.546708E-01,3.725193E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.549993E-01,1.161730E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.94 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.67 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD
ReformEIRChiller Carrier 19XR 1403kW/7.09COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1403kW/7.09COP/VSD, !- Name 1403100, !- Reference Capacity {W} 7.09, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 21.78, !- Reference Leaving Condenser Water Temperature {C} 0.03426, !- Reference Chilled Water Flow Rate {m3/s} 0.04252, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1403kW/7.09COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 21.78 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.573696E-01,-3.077045E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.172049E+00,-1.768334E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.386665E-01,4.836823E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.77 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.09 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1403kW_6_94COP_VSD
ReformEIRChiller York YT 1403kW/6.94COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1403kW/6.94COP/VSD, !- Name 1403100, !- Reference Capacity {W} 6.94, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.50, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1403kW/6.94COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1403kW/6.94COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1403kW/6.94COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.13, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.13 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.50 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.721714E+00,8.594308E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.348381E-01,-1.779962E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.005500E+00,3.906974E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.33 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.28 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1407kW_7_14COP_VSD
ReformEIRChiller Trane CVHE 1407kW/7.14COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1407kW/7.14COP/VSD, !- Name 1406600, !- Reference Capacity {W} 7.14, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.96, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1407kW/7.14COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.96 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.098635E-01,-4.154795E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.391346E-01,5.159383E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.754461E-01,6.701607E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.66 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.28 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_1407kW_6_60COP_Vanes
ReformEIRChiller McQuay PFH 1407kW/6.60COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 1407kW/6.60COP/Vanes, !- Name 1406600, !- Reference Capacity {W} 6.60, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.45, !- Reference Leaving Condenser Water Temperature {C} 0.04038, !- Reference Chilled Water Flow Rate {m3/s} 0.05804, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 1407kW/6.60COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.45 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04038 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05804 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.857520E-01,-1.139327E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.392120E-01,3.430098E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-6.446736E-01,5.352860E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.90 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.26 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1407kW_6_04COP_VSD
ReformEIRChiller Carrier 19XR 1407kW/6.04COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1407kW/6.04COP/VSD, !- Name 1406600, !- Reference Capacity {W} 6.04, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.63, !- Reference Leaving Condenser Water Temperature {C} 0.06057, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1407kW/6.04COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.006457E-01,-1.139681E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.174615E+00,-1.237741E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-5.839828E-01,4.640814E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.11 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 37.42 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1410kW_8_54COP_VSD
ReformEIRChiller Carrier 19XR 1410kW/8.54COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1410kW/8.54COP/VSD, !- Name 1410100, !- Reference Capacity {W} 8.54, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 19.21, !- Reference Leaving Condenser Water Temperature {C} 0.04, !- Reference Chilled Water Flow Rate {m3/s} 0.05861, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1410kW/8.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.21 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1410100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.053779E-01,-1.615047E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.074067E+00,-6.702565E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-6.984658E-02,2.103714E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.05 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.63 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1442kW_6_61COP_VSD
ReformEIRChiller Trane CVHE 1442kW/6.61COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1442kW/6.61COP/VSD, !- Name 1441800, !- Reference Capacity {W} 6.61, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.76, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1442kW/6.61COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.76 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1441800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.660651E-01,-2.114972E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.807134E-01,-2.285082E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-5.842314E-01,5.001539E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.72 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 41.41 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1459kW_6_40COP_VSD
ReformEIRChiller York YT 1459kW/6.40COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1459kW/6.40COP/VSD, !- Name 1459400, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.89, !- Reference Leaving Condenser Water Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1459kW/6.40COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1459kW/6.40COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1459kW/6.40COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.17, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.17 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.89 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1459400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.194034E+00,2.466392E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-6.559788E-02,4.189764E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.614787E-01,6.417258E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.15 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 37.17 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1484kW_9_96COP_VSD
ReformEIRChiller Trane CVHE 1484kW/9.96COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1484kW/9.96COP/VSD, !- Name 1484000, !- Reference Capacity {W} 9.96, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 17.08, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1484kW/9.96COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.24, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.24, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.24 | Minimum part unload ratio |
Real | PLRMin | 0.24 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 17.08 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1484000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-9.759100E-01,-1.446866E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-6.183288E-01,-1.151565E-01... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.203029E-01,9.195177E-02,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.08 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.97 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1495kW_7_51COP_VSD
ReformEIRChiller York YT 1495kW/7.51COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1495kW/7.51COP/VSD, !- Name 1494500, !- Reference Capacity {W} 7.51, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 29.92, !- Reference Leaving Condenser Water Temperature {C} 0.0429, !- Reference Chilled Water Flow Rate {m3/s} 0.06719, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1495kW/7.51COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1495kW/7.51COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1495kW/7.51COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.92 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1494500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.51 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0429 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06719 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.015487E-01,-1.630120E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.954138E-01,-1.627980E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.377828E-01,-3.620643E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.69 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 41.38 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes
ReformEIRChiller McQuay WSC 1519kW/7.10COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay WSC 1519kW/7.10COP/Vanes, !- Name 1519200, !- Reference Capacity {W} 7.10, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 31.76, !- Reference Leaving Condenser Water Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.08139, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay WSC 1519kW/7.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.76 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1519200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08139 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.244930E+00,-3.988254E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.087821E+00,-2.763242E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.209093E-01,-1.860468E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.71 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.53 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1558kW_5_81COP_VSD
ReformEIRChiller Carrier 19XR 1558kW/5.81COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1558kW/5.81COP/VSD, !- Name 1557800, !- Reference Capacity {W} 5.81, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.61, !- Reference Leaving Condenser Water Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1558kW/5.81COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.61 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1557800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.062937E+00,1.795402E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.228621E+00,-2.576180E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.269754E-01,-2.384434E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.93 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.69 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1586kW_5_53COP_VSD
ReformEIRChiller Carrier 19XR 1586kW/5.53COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1586kW/5.53COP/VSD, !- Name 1586000, !- Reference Capacity {W} 5.53, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 36.26, !- Reference Leaving Condenser Water Temperature {C} 0.03388, !- Reference Chilled Water Flow Rate {m3/s} 0.04669, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1586kW/5.53COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 36.26 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1586000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03388 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04669 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.132174E+00,8.236001E-04,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.223690E+00,-3.668987E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.381660E-01,-2.323866E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.36 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.72 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_1635kW_7_47COP_Vanes
ReformEIRChiller McQuay PEH 1635kW/7.47COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 1635kW/7.47COP/Vanes, !- Name 1635200, !- Reference Capacity {W} 7.47, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 19.47, !- Reference Leaving Condenser Water Temperature {C} 0.04416, !- Reference Chilled Water Flow Rate {m3/s} 0.06624, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 1635kW/7.47COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.47 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.47 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04416 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06624 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.307757E-01,-2.169411E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.029659E+00,-6.966329E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-6.247932E-02,1.538879E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.47 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.79 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1635kW_6_36COP_Vanes
ReformEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes, !- Name 1635200, !- Reference Capacity {W} 6.36, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 35.66, !- Reference Leaving Condenser Water Temperature {C} 0.03432, !- Reference Chilled Water Flow Rate {m3/s} 0.05035, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.66 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.36 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03432 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05035 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.092875E-01,-3.293511E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.499856E-01,-6.235681E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.206254E-01,-1.310337E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.44 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.54 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1656kW_8_24COP_VSD
ReformEIRChiller Carrier 19XR 1656kW/8.24COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1656kW/8.24COP/VSD, !- Name 1656300, !- Reference Capacity {W} 8.24, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 19.83, !- Reference Leaving Condenser Water Temperature {C} 0.04322, !- Reference Chilled Water Flow Rate {m3/s} 0.06296, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1656kW/8.24COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.83 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1656300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.653257E-01,-6.139152E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.129183E-01,-9.725092E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.682264E-01,5.313899E-02,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.63 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.21 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1663kW_9_34COP_Vanes
ReformEIRChiller York YT 1663kW/9.34COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1663kW/9.34COP/Vanes, !- Name 1663300, !- Reference Capacity {W} 9.34, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 18.45, !- Reference Leaving Condenser Water Temperature {C} 0.04139, !- Reference Chilled Water Flow Rate {m3/s} 0.0776, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1663kW/9.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1663kW/9.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1663kW/9.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 18.45 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1663300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04139 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0776 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.972683E-01,-9.692349E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.477120E-01,-3.913396E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.131373E-01,-3.438844E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.45 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.43 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XL_1674kW_7_89COP_Vanes
ReformEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes, !- Name 1673900, !- Reference Capacity {W} 7.89, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 17.74, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.32, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.32, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.32 | Minimum part unload ratio |
Real | PLRMin | 0.32 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 17.74 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1673900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.604710E-01,-5.170996E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.038212E+00,-5.515980E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.276299E-01,-2.633919E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.74 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.74 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes
ReformEIRChiller Trane CVHF 1681kW/6.59COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 1681kW/6.59COP/Vanes, !- Name 1680900, !- Reference Capacity {W} 6.59, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.90, !- Reference Leaving Condenser Water Temperature {C} 0.04366, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 1681kW/6.59COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.90 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1680900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.59 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.849319E-01,-9.745913E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.325528E-01,2.791268E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.598454E+00,9.989791E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 27.96 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.43 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1723kW_8_32COP_VSD
ReformEIRChiller Carrier 19XR 1723kW/8.32COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1723kW/8.32COP/VSD, !- Name 1723100, !- Reference Capacity {W} 8.32, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 19.44, !- Reference Leaving Condenser Water Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.06934, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1723kW/8.32COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.44 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1723100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06934 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.239005E-01,-7.123944E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-1.372893E-01,-1.137042E-01... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.363743E+00,-2.534882E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.07 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.40 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1727kW_9_04COP_Vanes
ReformEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes, !- Name 1726600, !- Reference Capacity {W} 9.04, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 19.16, !- Reference Leaving Condenser Water Temperature {C} 0.03912, !- Reference Chilled Water Flow Rate {m3/s} 0.07192, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.16 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1726600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03912 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07192 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.574689E-01,2.272600E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.247058E+00,-1.353289E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.552467E-02,1.482533E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.94 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.13 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_WSC_1751kW_6_73COP_Vanes
ReformEIRChiller McQuay WSC 1751kW/6.73COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay WSC 1751kW/6.73COP/Vanes, !- Name 1751300, !- Reference Capacity {W} 6.73, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 31.82, !- Reference Leaving Condenser Water Temperature {C} 0.04145, !- Reference Chilled Water Flow Rate {m3/s} 0.09337, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay WSC 1751kW/6.73COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.82 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1751300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.997155E-01,1.013018E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.968396E-01,2.738711E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-4.199061E-01,3.348162E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.25 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.66 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_1758kW_5_96COP_Vanes
ReformEIRChiller Trane CVHF 1758kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.23, !- Reference Leaving Condenser Water Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.23 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.152910E+00,-3.989989E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.175819E-02,-9.767577E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-3.445966E+00,3.643598E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.13 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.40 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1758kW_5_76COP_VSD
ReformEIRChiller York YT 1758kW/5.76COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1758kW/5.76COP/VSD, !- Name 1758300, !- Reference Capacity {W} 5.76, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.27, !- Reference Leaving Condenser Water Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1758kW/5.76COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/5.76COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/5.76COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.27 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.76 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.960842E-01,1.462778E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.622331E-01,8.325124E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.914420E-01,-3.736264E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.51 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.27 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.81 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1758kW_6_26COP_Vanes
ReformEIRChiller York YT 1758kW/6.26COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1758kW/6.26COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.26, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.18, !- Reference Leaving Condenser Water Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1758kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.16, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.16 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.18 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.841919E-01,-2.437152E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.729452E-01,9.227136E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.471258E-01,-4.669457E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.48 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.76 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1758kW_5_96COP_Vanes
ReformEIRChiller York YT 1758kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.23, !- Reference Leaving Condenser Water Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.23 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.075668E-01,5.287917E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.593808E-01,-1.873181E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.303414E-01,1.618347E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.29 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.53 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes
ReformEIRChiller Trane CVHE 1758kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHE 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.63, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHE 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.784203E-01,-8.333229E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.583438E+00,-3.412919E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.466664E+00,-4.222011E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 28.68 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.15 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1758kW_6_28COP_Vanes
ReformEIRChiller York YT 1758kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1758kW/6.28COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.60, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1758kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1758kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.60 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.062633E-01,-9.373882E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.699849E-01,-9.813327E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.911331E-01,-4.317969E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.46 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 39.72 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1758kW_5_86COP_VSD
ReformEIRChiller Carrier 19XR 1758kW/5.86COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1758kW/5.86COP/VSD, !- Name 1758300, !- Reference Capacity {W} 5.86, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.15, !- Reference Leaving Condenser Water Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.07337, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1758kW/5.86COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.15 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.86 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.528317E-02,-4.119086E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-6.333861E-02,-5.533069E-02... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.251509E+00,-9.433150E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.86 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.43 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_1758kW_6_46COP_VSD
ReformEIRChiller Trane CVHF 1758kW/6.46COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 1758kW/6.46COP/VSD, !- Name 1758300, !- Reference Capacity {W} 6.46, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.14, !- Reference Leaving Condenser Water Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 1758kW/6.46COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.14 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.46 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.155538E+00,-6.017270E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-2.601408E-01,2.870346E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.842588E-01,5.105821E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.10 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.22 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes
ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.87, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.08, !- Reference Leaving Condenser Water Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.08 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.87 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.950124E-01,3.170632E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.428117E-01,1.299499E-02,5... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.682807E-01,-3.888781E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.44 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.98 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1776kW_8_00COP_Vanes
ReformEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes, !- Name 1775900, !- Reference Capacity {W} 8.00, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 19.60, !- Reference Leaving Condenser Water Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.07003, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.60 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1775900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07003 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.221213E-01,-6.119865E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.400829E-01,-2.067083E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.623059E-01,-3.289272E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.69 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.73 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XL_1779kW_6_18COP_Vanes
ReformEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes, !- Name 1779400, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.69, !- Reference Leaving Condenser Water Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.08858, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.69 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08858 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-7.421879E-02,-6.864609E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.396428E-01,-3.183208E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.137642E-01,-3.096191E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.83 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.12 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_1779kW_6_18COP_Vanes
ReformEIRChiller Trane CVHF 1779kW/6.18COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 1779kW/6.18COP/Vanes, !- Name 1779400, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 33.51, !- Reference Leaving Condenser Water Temperature {C} 0.04454, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 33.51 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04454 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.379667E-01,-8.817299E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.679272E-01,3.649996E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.454991E-03,1.094255E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 27.96 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.47 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1794kW_8_11COP_Vanes
ReformEIRChiller York YT 1794kW/8.11COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1794kW/8.11COP/Vanes, !- Name 1793500, !- Reference Capacity {W} 8.11, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 28.88, !- Reference Leaving Condenser Water Temperature {C} 0.05148, !- Reference Chilled Water Flow Rate {m3/s} 0.09653, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1794kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1794kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1794kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.88 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.475615E+00,-2.480005E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.190864E+00,3.400270E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-9.081317E-02,1.524614E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.71 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.34 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1794kW_7_90COP_VSD
ReformEIRChiller York YT 1794kW/7.90COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1794kW/7.90COP/VSD, !- Name 1793500, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 28.90, !- Reference Leaving Condenser Water Temperature {C} 0.05148, !- Reference Chilled Water Flow Rate {m3/s} 0.09653, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1794kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1794kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1794kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.90 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.431766E-01,-1.738759E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.622079E-01,-1.249125E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.828090E-01,-1.598908E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.43 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.71 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes
ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes, !- Name 1797000, !- Reference Capacity {W} 5.69, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.67, !- Reference Leaving Condenser Water Temperature {C} 0.07737, !- Reference Chilled Water Flow Rate {m3/s} 0.09672, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.39, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.39, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.39 | Minimum part unload ratio |
Real | PLRMin | 0.39 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.67 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1797000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07737 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09672 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.173209E-01,4.990036E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.079738E+00,-4.447776E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.147565E+00,-1.604653E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 26.59 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.91 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD
ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD, !- Name 1800500, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 31.70, !- Reference Leaving Condenser Water Temperature {C} 0.05161, !- Reference Chilled Water Flow Rate {m3/s} 0.06385, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.70 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1800500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05161 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06385 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.277256E-01,-9.423458E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.993760E-01,3.436644E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-3.986781E-03,2.064845E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.63 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.95 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1867kW_10_09COP_Vanes
ReformEIRChiller York YT 1867kW/10.09COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1867kW/10.09COP/Vanes, !- Name 1867300, !- Reference Capacity {W} 10.09, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 18.18, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1867kW/10.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1867kW/10.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1867kW/10.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 18.18 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1867300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-8.621766E-02,-4.282771E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.584483E-01,1.696214E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-3.108659E-01,5.639190E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.96 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 39.35 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XL_1871kW_6_49COP_Vanes
ReformEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes, !- Name 1870800, !- Reference Capacity {W} 6.49, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 32.00, !- Reference Leaving Condenser Water Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.0877, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.00 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1870800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0877 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-7.422008E-01,-5.893189E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.182368E+00,-6.852914E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.085769E+00,-5.971095E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.92 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.06 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1881kW_6_77COP_VSD
ReformEIRChiller York YT 1881kW/6.77COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1881kW/6.77COP/VSD, !- Name 1881400, !- Reference Capacity {W} 6.77, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.35, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1881kW/6.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1881kW/6.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1881kW/6.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.35 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.510830E-01,-3.997687E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.450343E-01,-3.893169E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.949889E-02,2.267854E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.80 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.02 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_1881kW_6_53COP_Vanes
ReformEIRChiller York YK 1881kW/6.53COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 1881kW/6.53COP/Vanes, !- Name 1881400, !- Reference Capacity {W} 6.53, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 31.65, !- Reference Leaving Condenser Water Temperature {C} 0.04397, !- Reference Chilled Water Flow Rate {m3/s} 0.1041, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 1881kW/6.53COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 1881kW/6.53COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 1881kW/6.53COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.65 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.031671E-01,3.618657E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.262865E-01,4.727402E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.470999E-01,-4.530708E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 15.00 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.45 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_1895kW_6_42COP_Vanes
ReformEIRChiller McQuay PEH 1895kW/6.42COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 1895kW/6.42COP/Vanes, !- Name 1895400, !- Reference Capacity {W} 6.42, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.66, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 1895kW/6.42COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.1, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.1 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.66 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1895400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.518352E-01,-1.535612E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.851189E-01,-3.198165E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.912394E-02,1.922190E-02,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.93 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.14 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_1934kW_7_55COP_Vanes
ReformEIRChiller York YT 1934kW/7.55COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 1934kW/7.55COP/Vanes, !- Name 1934100, !- Reference Capacity {W} 7.55, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 19.93, !- Reference Leaving Condenser Water Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.08675, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 1934kW/7.55COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 1934kW/7.55COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 1934kW/7.55COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.93 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08675 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-8.034452E-01,5.620880E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.464148E+00,-1.335550E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.339218E-01,-3.184317E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.55 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.11 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PEH_1934kW_6_01COP_Vanes
ReformEIRChiller McQuay PEH 1934kW/6.01COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PEH 1934kW/6.01COP/Vanes, !- Name 1934100, !- Reference Capacity {W} 6.01, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.54, !- Reference Leaving Condenser Water Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.07981, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PEH 1934kW/6.01COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.54 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.01 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-4.043899E-01,-5.695254E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.191090E-01,7.702949E-04,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.000427E+00,-3.176111E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.00 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.60 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_WDC_1973kW_6_28COP_Vanes
ReformEIRChiller McQuay WDC 1973kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay WDC 1973kW/6.28COP/Vanes, !- Name 1972800, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 32.53, !- Reference Leaving Condenser Water Temperature {C} 0.04145, !- Reference Chilled Water Flow Rate {m3/s} 0.09337, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay WDC 1973kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.53 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1972800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.327385E+00,5.589128E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.179827E+00,-5.349290E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-9.986603E-01,7.542346E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.36 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.81 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_1997kW_7_24COP_Vanes
ReformEIRChiller York YK 1997kW/7.24COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 1997kW/7.24COP/Vanes, !- Name 1997400, !- Reference Capacity {W} 7.24, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 31.89, !- Reference Leaving Condenser Water Temperature {C} 0.04397, !- Reference Chilled Water Flow Rate {m3/s} 0.1041, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 1997kW/7.24COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 1997kW/7.24COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 1997kW/7.24COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.89 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1997400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.039493E+00,1.593009E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.550813E-01,1.022114E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.838759E-01,-1.009515E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.16 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.70 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_2043kW_8_44COP_Vanes
ReformEIRChiller McQuay PFH 2043kW/8.44COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 2043kW/8.44COP/Vanes, !- Name 2043100, !- Reference Capacity {W} 8.44, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 20.80, !- Reference Leaving Condenser Water Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.06814, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 2043kW/8.44COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 20.80 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06814 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.565419E-01,1.690707E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.806067E-01,5.701621E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-7.300240E-01,6.016914E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.80 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.72 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_2043kW_9_08COP_Vanes
ReformEIRChiller Trane CVHF 2043kW/9.08COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 2043kW/9.08COP/Vanes, !- Name 2043100, !- Reference Capacity {W} 9.08, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 23.11, !- Reference Leaving Condenser Water Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 2043kW/9.08COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 23.11 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.08 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.215335E+00,-3.294601E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.008753E+00,3.282653E-02,3... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.696812E-01,3.068332E-02,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.06 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.90 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XL_2057kW_6_05COP_Vanes
ReformEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes, !- Name 2057200, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 29.79, !- Reference Leaving Condenser Water Temperature {C} 0.08322, !- Reference Chilled Water Flow Rate {m3/s} 0.09722, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.79 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2057200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09722 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.448091E-01,-3.315001E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.341312E-01,-7.592418E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.353291E-01,-5.973382E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.89 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.37 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_2110kW_7_15COP_Vanes
ReformEIRChiller York YT 2110kW/7.15COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 2110kW/7.15COP/Vanes, !- Name 2110000, !- Reference Capacity {W} 7.15, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 29.97, !- Reference Leaving Condenser Water Temperature {C} 0.06057, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 2110kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 2110kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 2110kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.97 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2110000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.132568E-02,-1.142230E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.140372E-01,-4.277763E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.834325E-01,-1.806511E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.99 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.89 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_2124kW_6_03COP_Vanes
ReformEIRChiller McQuay PFH 2124kW/6.03COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 2124kW/6.03COP/Vanes, !- Name 2124000, !- Reference Capacity {W} 6.03, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 31.31, !- Reference Leaving Condenser Water Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.07981, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 2124kW/6.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.31 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2124000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.466662E-01,-3.809647E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.198331E+00,-5.731652E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.353862E+00,9.444334E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.28 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.13 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_2159kW_6_85COP_Vanes
ReformEIRChiller York YK 2159kW/6.85COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 2159kW/6.85COP/Vanes, !- Name 2159200, !- Reference Capacity {W} 6.85, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.32, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 2159kW/6.85COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 2159kW/6.85COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 2159kW/6.85COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.32 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2159200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.85 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-5.164056E-02,-7.384855E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.013059E+00,2.176325E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.315688E-02,2.746250E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.13 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.75 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_2184kW_6_78COP_Vanes
ReformEIRChiller Trane CVHF 2184kW/6.78COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 2184kW/6.78COP/Vanes, !- Name 2183800, !- Reference Capacity {W} 6.78, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 35.55, !- Reference Leaving Condenser Water Temperature {C} 0.04883, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 2184kW/6.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.55 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2183800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04883 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.214452E+00,-1.495671E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.286650E+00,3.478277E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.473025E+00,-1.277887E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 30.67 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.06 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_2201kW_6_69COP_Vanes
ReformEIRChiller York YK 2201kW/6.69COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 2201kW/6.69COP/Vanes, !- Name 2201400, !- Reference Capacity {W} 6.69, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.44, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.44 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2201400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.132698E-01,-9.712289E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.761500E-01,2.513467E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.515554E-03,3.070346E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.11 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.92 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_2233kW_9_54COP_VSD
ReformEIRChiller York YT 2233kW/9.54COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 2233kW/9.54COP/VSD, !- Name 2233000, !- Reference Capacity {W} 9.54, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 17.93, !- Reference Leaving Condenser Water Temperature {C} 0.06107, !- Reference Chilled Water Flow Rate {m3/s} 0.11451, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 2233kW/9.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 2233kW/9.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 2233kW/9.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 17.93 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2233000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06107 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11451 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.939632E-01,-9.743766E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.177745E-01,-9.460212E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.637900E-01,-3.344690E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.93 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.11 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_2237kW_6_41COP_Vanes
ReformEIRChiller York YK 2237kW/6.41COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 2237kW/6.41COP/Vanes, !- Name 2236600, !- Reference Capacity {W} 6.41, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.56, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 2237kW/6.41COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 2237kW/6.41COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 2237kW/6.41COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.13, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.13, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.56 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2236600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.686272E-01,-4.051077E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.801548E-01,2.026687E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.013555E-01,1.055744E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.30 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.03 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_2275kW_6_32COP_Vanes
ReformEIRChiller York YK 2275kW/6.32COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 2275kW/6.32COP/Vanes, !- Name 2275200, !- Reference Capacity {W} 6.32, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.66, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 2275kW/6.32COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 2275kW/6.32COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 2275kW/6.32COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.13, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.13, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.66 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2275200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.227391E-01,-3.381914E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.910758E-01,4.115735E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.464807E-01,6.198472E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.78 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.17 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_2300kW_8_10COP_Vanes
ReformEIRChiller Trane CVHF 2300kW/8.10COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 2300kW/8.10COP/Vanes, !- Name 2299900, !- Reference Capacity {W} 8.10, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 19.58, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 2300kW/8.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.23, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.23, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.23 | Minimum part unload ratio |
Real | PLRMin | 0.23 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.58 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2299900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.945951E-02,1.763194E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.870347E-01,1.176508E-02,5... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-8.187804E-01,9.052788E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.58 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.79 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD
ReformEIRChiller Trane CVHF 2317kW/6.33COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 2317kW/6.33COP/VSD, !- Name 2317400, !- Reference Capacity {W} 6.33, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 35.10, !- Reference Leaving Condenser Water Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 2317kW/6.33COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.10 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2317400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.33 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.632457E-01,4.608638E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.905409E-01,-2.093028E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-4.540034E-01,3.433262E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.67 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.67 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_2391kW_6_77COP_Vanes
ReformEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes, !- Name 2391300, !- Reference Capacity {W} 6.77, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 31.65, !- Reference Leaving Condenser Water Temperature {C} 0.06858, !- Reference Chilled Water Flow Rate {m3/s} 0.0846, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.65 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.092340E-01,-7.214951E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.095032E-01,-1.108553E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.306200E-01,-7.328716E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.72 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.63 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_2391kW_6_44COP_VSD
ReformEIRChiller Carrier 19XR 2391kW/6.44COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19XR 2391kW/6.44COP/VSD, !- Name 2391300, !- Reference Capacity {W} 6.44, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 31.70, !- Reference Leaving Condenser Water Temperature {C} 0.06858, !- Reference Chilled Water Flow Rate {m3/s} 0.0846, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19XR 2391kW/6.44COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.70 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.105784E-01,-7.215657E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.030335E-01,-1.099862E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.309393E-01,1.443518E-02,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.76 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.68 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_2412kW_5_58COP_Vanes
ReformEIRChiller York YK 2412kW/5.58COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 2412kW/5.58COP/Vanes, !- Name 2412400, !- Reference Capacity {W} 5.58, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 32.10, !- Reference Leaving Condenser Water Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 2412kW/5.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 2412kW/5.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 2412kW/5.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.12, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.12, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.10 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2412400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.042244E-01,-5.282819E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.175495E-01,-2.563749E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-8.659288E-02,4.280342E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.30 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.78 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_2462kW_6_67COP_Vanes
ReformEIRChiller McQuay PFH 2462kW/6.67COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 2462kW/6.67COP/Vanes, !- Name 2461600, !- Reference Capacity {W} 6.67, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Leaving Condenser Water Temperature {C} 0.07066, !- Reference Chilled Water Flow Rate {m3/s} 0.10157, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 2462kW/6.67COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.44 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2461600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07066 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.10157 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.142265E-01,1.542602E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.570216E-01,9.193251E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-8.594949E-01,6.566973E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.31 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.55 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHG670_44_86_2490kW_6_5COP
ReformEIRChiller Trane CVHG670-44&86 2490kW/6.5COP
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHG670-44&86 2490kW/6.5COP, !- Name 2490036, !- Reference Capacity {W} 6.505, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 35.24, !- Reference Leaving Condenser Water Temperature {C} 0.08894, !- Reference Chilled Water Flow Rate {m3/s} 0.13400, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHG670-44&86 2490kW/6.5COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHG670-44&86 2490kW/6.5COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHG670-44&86 2490kW/6.5COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.087, !- Minimum Part Load Ratio 1.001, !- Maximum Part Load Ratio 0.801, !- Optimum Part Load Ratio 0.087, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 5.6, !- Leaving Chilled Water Lower Temperature Limit {C} VariableFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.001 | Maximum part load ratio |
Real | PLRMinUnl | 0.087 | Minimum part unload ratio |
Real | PLRMin | 0.087 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.24 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2490036 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.505 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08894 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13400 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {0.403602663,-0.006794189,-0... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.056335684,0.045975279,0.0... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.243594787,-0.017680952,0.... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.60 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.20 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 30.8 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 36.9 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_2567kW_11_77COP_VSD
ReformEIRChiller Trane CVHF 2567kW/11.77COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 2567kW/11.77COP/VSD, !- Name 2567100, !- Reference Capacity {W} 11.77, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 17.18, !- Reference Leaving Condenser Water Temperature {C} 0.12113, !- Reference Chilled Water Flow Rate {m3/s} 0.15142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 2567kW/11.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 17.18 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2567100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 11.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.12113 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.150690E-01,7.668658E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.654848E-01,-3.708915E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.955643E-01,2.586243E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.02 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.24 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_2771kW_6_84COP_VSD
ReformEIRChiller York YK 2771kW/6.84COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 2771kW/6.84COP/VSD, !- Name 2771100, !- Reference Capacity {W} 6.84, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.91, !- Reference Leaving Condenser Water Temperature {C} 0.10094, !- Reference Chilled Water Flow Rate {m3/s} 0.15142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 2771kW/6.84COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 2771kW/6.84COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 2771kW/6.84COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.91 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2771100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.10094 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.744171E-01,3.178084E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.286811E-01,2.304403E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-6.205477E-01,5.913283E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.24 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.26 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_2799kW_6_40COP_Vanes
ReformEIRChiller Trane CVHF 2799kW/6.40COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 2799kW/6.40COP/Vanes, !- Name 2799200, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.74, !- Reference Leaving Condenser Water Temperature {C} 0.09893, !- Reference Chilled Water Flow Rate {m3/s} 0.13761, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 2799kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.74 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2799200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13761 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.176308E-01,-4.941294E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-1.986966E-02,-7.848021E-02... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.516172E-01,9.213025E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.38 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.07 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YT_3133kW_9_16COP_Vanes
ReformEIRChiller York YT 3133kW/9.16COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YT 3133kW/9.16COP/Vanes, !- Name 3133300, !- Reference Capacity {W} 9.16, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 19.37, !- Reference Leaving Condenser Water Temperature {C} 0.08076, !- Reference Chilled Water Flow Rate {m3/s} 0.12618, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YT 3133kW/9.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YT 3133kW/9.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YT 3133kW/9.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.07, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.07, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.07 | Minimum part unload ratio |
Real | PLRMin | 0.07 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 19.37 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -3133300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08076 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.12618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.112157E-01,-1.430728E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.749714E-01,-2.881975E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.389568E-01,-1.864923E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.37 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.91 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes
ReformEIRChiller McQuay PFH 3165kW/6.48COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 3165kW/6.48COP/Vanes, !- Name 3165000, !- Reference Capacity {W} 6.48, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.19, !- Reference Leaving Condenser Water Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.13627, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 3165kW/6.48COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.19 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -3165000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.48 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13627 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.575783E+00,3.340085E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.176153E+00,2.944151E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.080715E+00,7.856030E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.90 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.43 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes
ReformEIRChiller McQuay PFH 4020kW/7.35COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller McQuay PFH 4020kW/7.35COP/Vanes, !- Name 4019500, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.88, !- Reference Leaving Condenser Water Temperature {C} 0.07874, !- Reference Chilled Water Flow Rate {m3/s} 0.09842, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller McQuay PFH 4020kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 23.88 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4019500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07874 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09842 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.840238E-01,-2.030602E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.146197E-01,-2.888281E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-6.055569E-01,4.924519E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.88 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.13 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4396kW_6_63COP_Vanes
ReformEIRChiller York YK 4396kW/6.63COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4396kW/6.63COP/Vanes, !- Name 4395800, !- Reference Capacity {W} 6.63, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.58, !- Reference Leaving Condenser Water Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4396kW/6.63COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4396kW/6.63COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4396kW/6.63COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.58 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4395800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.63 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-7.935103E-01,-1.859711E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.992978E-01,-5.787211E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.551587E-01,-8.505111E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.53 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.58 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4477kW_6_64COP_Vanes
ReformEIRChiller York YK 4477kW/6.64COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4477kW/6.64COP/Vanes, !- Name 4476700, !- Reference Capacity {W} 6.64, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.67, !- Reference Leaving Condenser Water Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.67 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4476700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-5.612561E-01,-2.094117E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.597687E-01,-3.513678E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.263474E-01,-1.468760E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.50 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.67 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4515kW_6_22COP_Vanes
ReformEIRChiller York YK 4515kW/6.22COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4515kW/6.22COP/Vanes, !- Name 4515400, !- Reference Capacity {W} 6.22, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.76, !- Reference Leaving Condenser Water Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4515kW/6.22COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4515kW/6.22COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4515kW/6.22COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.76 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4515400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.22 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.075078E-01,-1.981043E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.011575E-01,1.661031E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.069612E-01,-1.915921E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.15 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.76 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4537kW_6_28COP_Vanes
ReformEIRChiller York YK 4537kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4537kW/6.28COP/Vanes, !- Name 4536500, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.78, !- Reference Leaving Condenser Water Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4537kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4537kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4537kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.78 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4536500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.769339E-01,8.033367E-04,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.920183E-01,-1.501518E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.718938E-01,6.637990E-03,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 19.77 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.78 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_4610kW_6_34COP_Vanes
ReformEIRChiller Trane CVHF 4610kW/6.34COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 4610kW/6.34COP/Vanes, !- Name 4610300, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.27, !- Reference Leaving Condenser Water Temperature {C} 0.19129, !- Reference Chilled Water Flow Rate {m3/s} 0.24757, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 4610kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.27 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4610300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19129 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24757 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.054195E-01,-1.086306E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.849506E-01,-4.909207E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-7.113458E-02,1.278078E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.15 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.76 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19EX_4667kW_6_16COP_Vanes
ReformEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes, !- Name 4666600, !- Reference Capacity {W} 6.16, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.94, !- Reference Leaving Condenser Water Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.94 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4666600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-8.915725E-02,-6.491327E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.382224E-01,2.679869E-03,4... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.967050E-01,-1.472448E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.77 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.94 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CVHF_4677kW_6_27COP_Vanes
ReformEIRChiller Trane CVHF 4677kW/6.27COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CVHF 4677kW/6.27COP/Vanes, !- Name 4677100, !- Reference Capacity {W} 6.27, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.94, !- Reference Leaving Condenser Water Temperature {C} 0.20138, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CVHF 4677kW/6.27COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.94 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4677100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.20138 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.138295E-01,-2.315871E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.371931E-01,-1.837487E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-3.243462E-01,1.463635E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.51 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.94 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4966kW_6_05COP_Vanes
ReformEIRChiller York YK 4966kW/6.05COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4966kW/6.05COP/Vanes, !- Name 4965500, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.33, !- Reference Leaving Condenser Water Temperature {C} 0.21198, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4966kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4966kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4966kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.12, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.12, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.33 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4965500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.21198 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.672989E-01,-3.881077E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.536699E-01,3.487393E-04,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.620385E-01,1.209698E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.07 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.01 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4969kW_7_14COP_Vanes
ReformEIRChiller York YK 4969kW/7.14COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4969kW/7.14COP/Vanes, !- Name 4969000, !- Reference Capacity {W} 7.14, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.23, !- Reference Leaving Condenser Water Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.23 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.811615E-03,-1.788883E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.916913E-01,-4.760980E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.289463E-01,6.642124E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.57 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.55 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_4969kW_7_07COP_Vanes
ReformEIRChiller York YK 4969kW/7.07COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 4969kW/7.07COP/Vanes, !- Name 4969000, !- Reference Capacity {W} 7.07, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.23, !- Reference Leaving Condenser Water Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 4969kW/7.07COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 4969kW/7.07COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 4969kW/7.07COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.23 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.07 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.238406E+00,-2.167075E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.217115E-01,-3.596981E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.117270E-01,1.022191E-03,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.30 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.56 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes
ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes, !- Name 4997200, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 32.28, !- Reference Leaving Condenser Water Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.28 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4997200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.686142E-01,-4.640249E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.502378E-01,-8.546174E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.778244E-01,-1.674571E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.18 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.28 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19EX_5148kW_6_34COP_Vanes
ReformEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes, !- Name 5148400, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.70, !- Reference Leaving Condenser Water Temperature {C} 0.18283, !- Reference Chilled Water Flow Rate {m3/s} 0.25526, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.70 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5148400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25526 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.011196E-01,-1.084580E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.139244E-01,1.237345E-02,8... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.989462E-01,-1.736649E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.87 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.96 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_5170kW_7_15COP_Vanes
ReformEIRChiller York YK 5170kW/7.15COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 5170kW/7.15COP/Vanes, !- Name 5169500, !- Reference Capacity {W} 7.15, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.43, !- Reference Leaving Condenser Water Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 5170kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 5170kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 5170kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.15, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.15, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.43 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5169500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.064004E+00,-2.233223E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.056958E-01,-2.296962E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.949169E-01,9.107817E-04,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.30 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.88 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19EX_5208kW_6_88COP_Vanes
ReformEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes, !- Name 5208200, !- Reference Capacity {W} 6.88, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.75, !- Reference Leaving Condenser Water Temperature {C} 0.18283, !- Reference Chilled Water Flow Rate {m3/s} 0.25293, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.75 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5208200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.88 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25293 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.254471E-01,-1.028175E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.363910E-01,-8.005283E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.759577E-01,-1.540144E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.08 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.31 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_5465kW_6_94COP_Vanes
ReformEIRChiller York YK 5465kW/6.94COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 5465kW/6.94COP/Vanes, !- Name 5464900, !- Reference Capacity {W} 6.94, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.56, !- Reference Leaving Condenser Water Temperature {C} 0.18296, !- Reference Chilled Water Flow Rate {m3/s} 0.27444, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 5465kW/6.94COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 5465kW/6.94COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 5465kW/6.94COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.56 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5464900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.004987E+00,-2.020843E-01... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.844853E-01,-4.786810E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.903067E-01,-1.058205E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.03 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.99 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YK_5549kW_6_50COP_Vanes
ReformEIRChiller York YK 5549kW/6.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YK 5549kW/6.50COP/Vanes, !- Name 5549300, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 31.69, !- Reference Leaving Condenser Water Temperature {C} 0.18296, !- Reference Chilled Water Flow Rate {m3/s} 0.27444, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YK 5549kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YK 5549kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YK 5549kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.69 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5549300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-8.620027E-01,6.692796E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.302868E-01,-8.254126E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.179058E-01,-2.419877E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.38 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.70 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes
ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes, !- Name 5651300, !- Reference Capacity {W} 5.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 37.89, !- Reference Leaving Condenser Water Temperature {C} 0.18927, !- Reference Chilled Water Flow Rate {m3/s} 0.18927, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 37.89 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5651300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18927 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.18927 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.205097E-01,-7.830750E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.804871E-01,3.853907E-04,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.360532E-01,8.642703E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 26.23 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 39.12 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Multistack_MS_172kW_3_67COP_None
ReformEIRChiller Multistack MS 172kW/3.67COP/None
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Multistack MS 172kW/3.67COP/None, !- Name 172300, !- Reference Capacity {W} 3.67, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 23.82, !- Reference Leaving Condenser Water Temperature {C} 0.00738, !- Reference Chilled Water Flow Rate {m3/s} 0.00959, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Multistack MS 172kW/3.67COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Multistack MS 172kW/3.67COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Multistack MS 172kW/3.67COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 23.82 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -172300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00738 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.00959 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.127280E+00,1.221754E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.822430E-01,-6.747171E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.368265E-01,-2.032253E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.82 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.51 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTWA_383kW_4_17COP_Valve
ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve, !- Name 383300, !- Reference Capacity {W} 4.17, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.95, !- Reference Leaving Condenser Water Temperature {C} 0.0165, !- Reference Chilled Water Flow Rate {m3/s} 0.02063, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.95 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -383300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.17 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0165 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02063 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.005026E+00,3.896773E-02,9... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.171417E-01,-4.530431E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.660765E+00,1.117605E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 29.19 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.69 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHB_531kW_4_83COP_Valve
ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve, !- Name 531000, !- Reference Capacity {W} 4.83, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 33.61, !- Reference Leaving Condenser Water Temperature {C} 0.0135, !- Reference Chilled Water Flow Rate {m3/s} 0.01577, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 33.61 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -531000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.83 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0135 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.079958E-01,1.147213E-02,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.048223E-01,1.023123E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.560311E+00,-2.031290E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 25.39 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.83 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHB_538kW_5_12COP_Valve
ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve, !- Name 538000, !- Reference Capacity {W} 5.12, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.75, !- Reference Leaving Condenser Water Temperature {C} 0.01375, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.75 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -538000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.12 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01375 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.326777E-01,2.745642E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.761769E-01,-3.860230E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.185505E+00,-9.516501E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.52 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.74 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHB_542kW_5_26COP_Valve
ReformEIRChiller Trane RTHB 542kW/5.26COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHB 542kW/5.26COP/Valve, !- Name 541500, !- Reference Capacity {W} 5.26, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 30.89, !- Reference Leaving Condenser Water Temperature {C} 0.01363, !- Reference Chilled Water Flow Rate {m3/s} 0.01577, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHB 542kW/5.26COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 30.89 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -541500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01363 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.292432E-01,2.977220E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.877196E-01,-1.191161E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.837065E+00,-7.719197E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 25.39 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 34.83 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_672kW_7_90COP_Valve
ReformEIRChiller York YS 672kW/7.90COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 672kW/7.90COP/Valve, !- Name 671600, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 23.07, !- Reference Leaving Condenser Water Temperature {C} 0.01514, !- Reference Chilled Water Flow Rate {m3/s} 0.0241, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 672kW/7.90COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 672kW/7.90COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 672kW/7.90COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 23.07 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -671600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.653043E-01,3.117948E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.199355E-01,-6.676229E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.456160E-01,-2.835399E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 23.07 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.60 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_686kW_5_91COP_Valve
ReformEIRChiller Carrier 23XL 686kW/5.91COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 686kW/5.91COP/Valve, !- Name 685700, !- Reference Capacity {W} 5.91, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 29.63, !- Reference Leaving Condenser Water Temperature {C} 0.0571, !- Reference Chilled Water Flow Rate {m3/s} 0.03255, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 686kW/5.91COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -685700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.91 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03255 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.248877E-02,-3.890734E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.449412E-01,1.058205E-02,5... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.479846E-01,-1.132553E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.39 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.39 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHC_707kW_7_77COP_Valve
ReformEIRChiller Trane RTHC 707kW/7.77COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHC 707kW/7.77COP/Valve, !- Name 706800, !- Reference Capacity {W} 7.77, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.40, !- Reference Leaving Condenser Water Temperature {C} 0.04921, !- Reference Chilled Water Flow Rate {m3/s} 0.03268, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHC 707kW/7.77COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 21.40 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -706800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03268 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.650754E-01,3.116480E-02,6... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.777406E-01,1.234139E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.383290E+00,-1.536137E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 11.11 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.40 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.31 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_756kW_7_41COP_Valve
ReformEIRChiller York YS 756kW/7.41COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 756kW/7.41COP/Valve, !- Name 756000, !- Reference Capacity {W} 7.41, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 20.05, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 756kW/7.41COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 756kW/7.41COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 756kW/7.41COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 20.05 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -756000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.642889E-01,2.866413E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.354619E-01,-1.370325E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.261074E+00,1.245378E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.05 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 28.28 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_781kW_5_42COP_Valve
ReformEIRChiller York YS 781kW/5.42COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 781kW/5.42COP/Valve, !- Name 780700, !- Reference Capacity {W} 5.42, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 35.29, !- Reference Leaving Condenser Water Temperature {C} 0.01893, !- Reference Chilled Water Flow Rate {m3/s} 0.03785, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 781kW/5.42COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 781kW/5.42COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 781kW/5.42COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.29 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -780700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.033403E+00,3.515774E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.008316E-01,-6.141937E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.519460E-01,-1.406889E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.31 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 41.08 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_830kW_6_97COP_Valve
ReformEIRChiller Carrier 23XL 830kW/6.97COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 830kW/6.97COP/Valve, !- Name 829900, !- Reference Capacity {W} 6.97, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 28.67, !- Reference Leaving Condenser Water Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 830kW/6.97COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 28.67 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -829900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.97 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.593802E-01,3.128246E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.680542E-01,-1.666432E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.035259E-01,-2.731638E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.74 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 28.78 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_862kW_6_11COP_Valve
ReformEIRChiller Carrier 23XL 862kW/6.11COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 862kW/6.11COP/Valve, !- Name 861500, !- Reference Capacity {W} 6.11, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.47, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04296, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 862kW/6.11COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.47 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.979107E-01,-5.151176E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.091020E-01,-1.121376E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.107206E-01,-2.005785E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 16.41 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 29.48 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_862kW_6_84COP_Valve
ReformEIRChiller Carrier 23XL 862kW/6.84COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 862kW/6.84COP/Valve, !- Name 861500, !- Reference Capacity {W} 6.84, !- Reference COP {W/W} 9.69, !- Reference Leaving Chilled Water Temperature {C} 29.39, !- Reference Leaving Condenser Water Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04296, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 862kW/6.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.39 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.69 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.092995E-01,-5.286556E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.678615E-01,-9.383184E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.851376E-01,-3.243560E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 16.41 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 29.48 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_865kW_6_05COP_Valve
ReformEIRChiller Carrier 23XL 865kW/6.05COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 865kW/6.05COP/Valve, !- Name 865100, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 31.63, !- Reference Leaving Condenser Water Temperature {C} 0.03716, !- Reference Chilled Water Flow Rate {m3/s} 0.04366, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 865kW/6.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -865100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03716 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04366 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.094927E-01,-2.603658E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.716056E-01,1.224643E-02,5... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.633484E-01,2.429348E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 16.50 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.26 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_879kW_5_82COP_Valve
ReformEIRChiller York YS 879kW/5.82COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 879kW/5.82COP/Valve, !- Name 879100, !- Reference Capacity {W} 5.82, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 31.32, !- Reference Leaving Condenser Water Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 879kW/5.82COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 879kW/5.82COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 879kW/5.82COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.32 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -879100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.82 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.043132E+00,3.207323E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.260798E-01,-4.729537E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.727519E-01,1.350521E-04,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.15 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.12 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHC_1009kW_5_37COP_Valve
ReformEIRChiller Trane RTHC 1009kW/5.37COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHC 1009kW/5.37COP/Valve, !- Name 1009200, !- Reference Capacity {W} 5.37, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 31.06, !- Reference Leaving Condenser Water Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04618, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHC 1009kW/5.37COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.06 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1009200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.37 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.207602E+00,3.634622E-02,6... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.985801E-01,2.197522E-02,8... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.618518E+00,-6.247569E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 26.58 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.91 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve
ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve, !- Name 1051400, !- Reference Capacity {W} 5.05, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.77, !- Reference Leaving Condenser Water Temperature {C} 0.04527, !- Reference Chilled Water Flow Rate {m3/s} 0.05659, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.77 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1051400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04527 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05659 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.638196E-01,3.356030E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.638880E-01,7.313353E-04,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.132575E+01,7.315041E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 28.94 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.58 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve
ReformEIRChiller Carrier 23XL 1062kW/5.50COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 1062kW/5.50COP/Valve, !- Name 1062000, !- Reference Capacity {W} 5.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.70, !- Reference Leaving Condenser Water Temperature {C} 0.04573, !- Reference Chilled Water Flow Rate {m3/s} 0.05716, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 1062kW/5.50COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.70 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1062000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04573 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05716 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.054485E+00,1.015650E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.369592E-01,-5.681693E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.385765E+00,-3.549685E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 26.44 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 35.10 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve
ReformEIRChiller Trane RTHC 1066kW/5.73COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHC 1066kW/5.73COP/Valve, !- Name 1065500, !- Reference Capacity {W} 5.73, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 32.06, !- Reference Leaving Condenser Water Temperature {C} 0.05142, !- Reference Chilled Water Flow Rate {m3/s} 0.04416, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHC 1066kW/5.73COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 32.06 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1065500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05142 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.132006E+00,5.350322E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.270619E+00,2.714576E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-5.639468E-01,3.938489E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 27.08 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 33.00 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_RTHC_1094kW_6_55COP_Valve
ReformEIRChiller Trane RTHC 1094kW/6.55COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane RTHC 1094kW/6.55COP/Valve, !- Name 1093600, !- Reference Capacity {W} 6.55, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 30.00, !- Reference Leaving Condenser Water Temperature {C} 0.04921, !- Reference Chilled Water Flow Rate {m3/s} 0.04524, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane RTHC 1094kW/6.55COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 30.00 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1093600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04524 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.937063E-01,4.121201E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.406305E-01,-4.941735E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-5.793160E-01,4.173392E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 22.50 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 31.57 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_1108kW_6_92COP_Valve
ReformEIRChiller Carrier 23XL 1108kW/6.92COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 1108kW/6.92COP/Valve, !- Name 1107700, !- Reference Capacity {W} 6.92, !- Reference COP {W/W} 8.97, !- Reference Leaving Chilled Water Temperature {C} 29.64, !- Reference Leaving Condenser Water Temperature {C} 0.0571, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 1108kW/6.92COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 29.64 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1107700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.97 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.158330E-01,-2.311637E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.272297E-01,-1.879890E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.638449E+00,-1.139810E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 18.28 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.24 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_1171kW_9_15COP_Valve
ReformEIRChiller York YS 1171kW/9.15COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 1171kW/9.15COP/Valve, !- Name 1171000, !- Reference Capacity {W} 9.15, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 21.56, !- Reference Leaving Condenser Water Temperature {C} 0.03249, !- Reference Chilled Water Flow Rate {m3/s} 0.05173, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 1171kW/9.15COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 1171kW/9.15COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 1171kW/9.15COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 21.56 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1171000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03249 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.337294E-01,1.920636E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.293911E-01,-2.105626E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.154861E-01,3.786873E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 21.56 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 30.78 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_1196kW_6_39COP_Valve
ReformEIRChiller Carrier 23XL 1196kW/6.39COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Carrier 23XL 1196kW/6.39COP/Valve, !- Name 1195600, !- Reference Capacity {W} 6.39, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 31.63, !- Reference Leaving Condenser Water Temperature {C} 0.03653, !- Reference Chilled Water Flow Rate {m3/s} 0.04271, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Carrier 23XL 1196kW/6.39COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 31.63 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03653 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04271 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.031420E-01,6.667912E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.152368E-01,-1.274543E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-2.737954E-01,2.822257E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.39 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 32.63 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_1554kW_9_31COP_Valve
ReformEIRChiller York YS 1554kW/9.31COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 1554kW/9.31COP/Valve, !- Name 1554300, !- Reference Capacity {W} 9.31, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 20.74, !- Reference Leaving Condenser Water Temperature {C} 0.0424, !- Reference Chilled Water Flow Rate {m3/s} 0.07949, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 1554kW/9.31COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 1554kW/9.31COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 1554kW/9.31COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 20.74 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1554300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.31 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0424 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07949 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.158269E+00,9.811289E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.556656E-01,2.393674E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.590292E-01,-5.404650E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 20.74 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.06 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_York_YS_1758kW_5_84COP_Valve
ReformEIRChiller York YS 1758kW/5.84COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller York YS 1758kW/5.84COP/Valve, !- Name 1758300, !- Reference Capacity {W} 5.84, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 34.65, !- Reference Leaving Condenser Water Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller York YS 1758kW/5.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller York YS 1758kW/5.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller York YS 1758kW/5.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 34.65 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.348511E-01,-2.523830E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.492787E-01,1.912506E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {-1.522140E-01,2.440667E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 17.74 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 39.72 | Maximum value for leaving condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Trane_CGWD_207kW_3_99COP_None
ReformEIRChiller Trane CGWD 207kW/3.99COP/None
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:ReformulatedEIR, ReformEIRChiller Trane CGWD 207kW/3.99COP/None, !- Name 207400, !- Reference Capacity {W} 3.99, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 35.00, !- Reference Leaving Condenser Water Temperature {C} 0.00898, !- Reference Chilled Water Flow Rate {m3/s} 0.01122, !- Reference Condenser Water Flow Rate {m3/s} ReformEIRChiller Trane CGWD 207kW/3.99COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name ReformEIRChiller Trane CGWD 207kW/3.99COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ReformEIRChiller Trane CGWD 207kW/3.99COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode Type 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic (Generic data record for chiller ElectricReformulatedEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConLvg_nominal | 273.15 + 35.00 | Temperature of fluid leaving condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -207400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.99 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00898 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01122 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.585465E-01,3.516870E-02,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.327001E-01,-8.343605E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.086284E-02,2.787561E-03,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConLvgMin | 273.15 + 29.37 | Minimum value for leaving condenser temperature [K] |
Temperature | TConLvgMax | 273.15 + 40.94 | Maximum value for leaving condenser temperature [K] |