Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans

Air handlers and fans

Information

This package contains models used for validation purposes.

Extends from Modelica.Icons.Package (Icon for standard packages).

Package Content

Name Description
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZBase VAVMZBase Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilElectricHeating VAVMZCoilElectricHeating Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorMultiStage VAVMZCoilEvaporatorMultiStage Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorVariable VAVMZCoilEvaporatorVariable Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilWaterHeating3WVReheat VAVMZCoilWaterHeating3WVReheat Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Airflow VAVMZControlG36Airflow Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Pressure VAVMZControlG36Pressure Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZDedicatedDampersPressure VAVMZDedicatedDampersPressure Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanRelief VAVMZFanRelief Configuration of multiple-zone VAV
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanSupplyBlowThrough VAVMZFanSupplyBlowThrough Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZBase Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZBase

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZBase

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Outdoor air sectionNo economizer
Relief/return air sectionNo economizer

Extends from VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedHeatingcoiHeaPreredeclare inner Buildings.Te...Heating coil in preheat position
WaterBasedCoolingcoiCooredeclare inner Buildings.Te...Cooling coil
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZBase "Configuration of multiple-zone VAV" extends VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", nZon=2); end VAVMZBase;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilElectricHeating Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilElectricHeating

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilElectricHeating

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Heating coilModulating electric heating coil - Preheat position

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedCoolingcoiCooredeclare inner Buildings.Te...Cooling coil
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZCoilElectricHeating "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", redeclare replaceable Buildings.Templates.Components.Coils.ElectricHeating coiHeaPre "Modulating electric heating coil", nZon=2); end VAVMZCoilElectricHeating;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorMultiStage Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorMultiStage

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorMultiStage

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Cooling coilEvaporator coil with multi-stage compressor

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedHeatingcoiHeaPreredeclare inner Buildings.Te...Heating coil in preheat position
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZCoilEvaporatorMultiStage "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", nZon=2, redeclare replaceable Buildings.Templates.Components.Coils.EvaporatorMultiStage coiCoo); end VAVMZCoilEvaporatorMultiStage;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorVariable Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorVariable

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorVariable

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Cooling coilEvaporator coil with variable speed compressor

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedHeatingcoiHeaPreredeclare inner Buildings.Te...Heating coil in preheat position
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZCoilEvaporatorVariable "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", nZon=2, redeclare replaceable Buildings.Templates.Components.Coils.EvaporatorVariableSpeed coiCoo); end VAVMZCoilEvaporatorVariable;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilWaterHeating3WVReheat Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilWaterHeating3WVReheat

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilWaterHeating3WVReheat

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Heating coilHot water coil - Three-way modulating valve - Reheat position

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedCoolingcoiCooredeclare inner Buildings.Te...Cooling coil
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZCoilWaterHeating3WVReheat "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", redeclare replaceable Buildings.Templates.Components.Coils.None coiHeaPre, redeclare replaceable Buildings.Templates.Components.Coils.WaterBasedHeating coiHeaReh( redeclare final package MediumHeaWat = MediumHeaWat, redeclare Buildings.Templates.Components.Valves.ThreeWayModulating val), nZon=2); end VAVMZCoilWaterHeating3WVReheat;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Airflow Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Airflow

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Airflow

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Heating coilHot water coil - Two-way modulating valve - Preheat position
Cooling coilChilled water coil - Two-way modulating valve
ControllerGuideline 36 controller - Return fan with airflow tracking control

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZControlG36Airflow "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( nZon=2, redeclare replaceable Buildings.Templates.Components.Coils.WaterBasedHeating coiHeaPre( redeclare final package MediumHeaWat = MediumHeaWat, redeclare replaceable Buildings.Templates.Components.Valves.TwoWayModulating val), redeclare replaceable Buildings.Templates.Components.Coils.WaterBasedCooling coiCoo( redeclare final package MediumChiWat = MediumChiWat, redeclare replaceable Buildings.Templates.Components.Valves.TwoWayModulating val) "Chilled water coil", redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.G36VAVMultiZone ctl( typCtlFanRet=Buildings.Templates.AirHandlersFans.Types.ControlFanReturn.AirflowMeasured, idZon={"Box_1","Box_1"}, namGro={"Floor_1"}, namGroZon={"Floor_1","Floor_1"})); end VAVMZControlG36Airflow;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Pressure Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Pressure

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Pressure

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Heating coilHot water coil - Two-way modulating valve - Preheat position
Cooling coilChilled water coil - Two-way modulating valve
ControllerGuideline 36 controller - Return fan with building pressure control

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZControlG36Pressure "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( nZon=2, redeclare replaceable Buildings.Templates.Components.Coils.WaterBasedHeating coiHeaPre( redeclare final package MediumHeaWat = MediumHeaWat, redeclare replaceable Buildings.Templates.Components.Valves.TwoWayModulating val), redeclare replaceable Buildings.Templates.Components.Coils.WaterBasedCooling coiCoo( redeclare final package MediumChiWat = MediumChiWat, redeclare replaceable Buildings.Templates.Components.Valves.TwoWayModulating val) "Chilled water coil", redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.G36VAVMultiZone ctl( typCtlFanRet=Buildings.Templates.AirHandlersFans.Types.ControlFanReturn.BuildingPressure, idZon={"Box_1","Box_1"}, namGro={"Floor_1"}, namGroZon={"Floor_1","Floor_1"})); end VAVMZControlG36Pressure;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZDedicatedDampersPressure Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZDedicatedDampersPressure

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZDedicatedDampersPressure

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Outdoor air sectionSeparate dedicated OA dampers with differential pressure sensor

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedHeatingcoiHeaPreredeclare inner Buildings.Te...Heating coil in preheat position
WaterBasedCoolingcoiCooredeclare inner Buildings.Te...Cooling coil
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZDedicatedDampersPressure "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", secOutRel(redeclare replaceable Buildings.Templates.AirHandlersFans.Components.OutdoorSection.DedicatedDampersPressure secOut "Dedicated minimum OA damper (two-position) with differential pressure sensor"), nZon=2); end VAVMZDedicatedDampersPressure;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanRelief Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanRelief

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanRelief

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Relief/return air sectionRelief fan with two-position relief damper
Return fanNo fan
Relief fanSingle fan - Variable speed

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
NonefanSupBloredeclare inner Buildings.Te...Supply fan - Blow through
SingleVariablefanSupDraredeclare inner Buildings.Te...Supply fan - Draw through
WaterBasedHeatingcoiHeaPreredeclare inner Buildings.Te...Heating coil in preheat position
WaterBasedCoolingcoiCooredeclare inner Buildings.Te...Cooling coil
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZFanRelief "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", secOutRel(redeclare replaceable Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection.ReliefFan secRel "Relief fan with two-position relief damper"), nZon=2); end VAVMZFanRelief;

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanSupplyBlowThrough Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanSupplyBlowThrough

Configuration of multiple-zone VAV

Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanSupplyBlowThrough

Information

This is a configuration model with the same default options as Buildings.Templates.AirHandlersFans.VAVMultiZone except for the following options.

ComponentConfiguration
Supply fanSingle fan - Variable speed - Blow-through position

Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).

Parameters

TypeNameDefaultDescription
replaceable package MediumAirAirAir medium
replaceable package MediumChiWatWaterCHW medium
replaceable package MediumHeaWatWaterHHW medium
VAVMultiZonedatredeclare Buildings.Template...Design and operating parameters
Configuration
IntegernZon2Number of served zones
MixedAirWithDampersecOutRel Outdoor/relief/return air section
WaterBasedHeatingcoiHeaPreredeclare inner Buildings.Te...Heating coil in preheat position
WaterBasedCoolingcoiCooredeclare inner Buildings.Te...Cooling coil
NonecoiHeaRehredeclare inner Buildings.Te...Heating coil in reheat position
Dynamics
Conservation equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversalLiqtrue= true to allow flow reversal, false restricts to design direction - CHW and HW side
Advanced
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at ports of subcomponents is computed

Connectors

TypeNameDescription
FluidPort_aport_OutOutdoor air intake
FluidPort_bport_SupSupply air
FluidPort_bport_SupColDual duct cold deck air supply
FluidPort_bport_SupHotDual duct hot deck air supply
FluidPort_aport_RetReturn air
FluidPort_bport_RelRelief (exhaust) air
FluidPort_bport_bChiWatCHW return port
FluidPort_aport_aChiWatCHW supply port
FluidPort_bport_bHeaWatHHW return port
FluidPort_aport_aHeaWatHHW supply port
BusbusAHU control bus
BusbusWeaWeather bus
BusbusTer[nZon]Terminal unit control bus

Modelica definition

model VAVMZFanSupplyBlowThrough "Configuration of multiple-zone VAV" extends Buildings.Templates.AirHandlersFans.VAVMultiZone( redeclare replaceable Buildings.Templates.AirHandlersFans.Components.Controls.OpenLoop ctl "Open loop controller", redeclare replaceable Buildings.Templates.Components.Fans.None fanSupDra, nZon=2, redeclare replaceable Buildings.Templates.Components.Fans.SingleVariable fanSupBlo); end VAVMZFanSupplyBlowThrough;