Package with mass exchanger models
Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Name | Description |
---|---|
ConstantEffectiveness | Heat and moisture exchanger with constant effectiveness |
HumidifierPrescribed | Ideal humidifier or dehumidifier with prescribed water mass flow rate addition or subtraction |
Examples | Collection of models that illustrate model use and test models |
Heat and moisture exchanger with constant effectiveness
Model for a heat and moisture exchanger with constant effectiveness.
This model transfers heat and moisture in the amount of
Q = epsS * Q_max, m = epsL * mWat_max,
where epsS
and epsL
are constant effectiveness
for the sensible and latent heat transfer,
Q_max
is the maximum heat that can be transferred and
mWat_max
is the maximum moisture that can be transferred.
For a sensible heat exchanger, use Buildings.Fluid.HeatExchangers.ConstantEffectiveness instead of this model.
This model can only be used with medium models that define the integer constant
Water
which needs to be equal to the index of the water mass fraction
in the species vector.
Extends from Buildings.Fluid.HeatExchangers.BaseClasses.PartialEffectiveness (Partial model to implement heat exchangers based on effectiveness model).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium1 | PartialMedium | Medium 1 in the component | |
replaceable package Medium2 | PartialMedium | Medium 2 in the component | |
HeatFlowRate | Q1_flow | epsS*QMax_flow | Heat transfered into the medium 1 [W] |
MassFlowRate | mWat1_flow | +mWat_flow | Moisture mass flow rate added to the medium 1 [kg/s] |
HeatFlowRate | Q2_flow | -Q1_flow | Heat transfered into the medium 2 [W] |
MassFlowRate | mWat2_flow | -mWat_flow | Moisture mass flow rate added to the medium 2 [kg/s] |
Boolean | sensibleOnly1 | false | Set to true if sensible exchange only for medium 1 |
Boolean | sensibleOnly2 | false | Set to true if sensible exchange only for medium 2 |
Real | epsS | 0.8 | Sensible heat exchanger effectiveness |
Real | epsL | 0.8 | Latent heat exchanger effectiveness |
Nominal condition | |||
MassFlowRate | m1_flow_nominal | Nominal mass flow rate [kg/s] | |
MassFlowRate | m2_flow_nominal | Nominal mass flow rate [kg/s] | |
Pressure | dp1_nominal | Pressure [Pa] | |
Pressure | dp2_nominal | Pressure [Pa] | |
Initialization | |||
MassFlowRate | m1_flow.start | 0 | Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) [kg/s] |
Pressure | dp1.start | 0 | Pressure difference between port_a1 and port_b1 [Pa] |
MassFlowRate | m2_flow.start | 0 | Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) [kg/s] |
Pressure | dp2.start | 0 | Pressure difference between port_a2 and port_b2 [Pa] |
Assumptions | |||
Boolean | allowFlowReversal1 | system.allowFlowReversal | = true to allow flow reversal in medium 1, false restricts to design direction (port_a -> port_b) |
Boolean | allowFlowReversal2 | system.allowFlowReversal | = true to allow flow reversal in medium 2, false restricts to design direction (port_a -> port_b) |
Advanced | |||
Initialization | |||
SpecificEnthalpy | h_outflow_a1_start | Medium1.h_default | Start value for enthalpy flowing out of port a1 [J/kg] |
SpecificEnthalpy | h_outflow_b1_start | Medium1.h_default | Start value for enthalpy flowing out of port b1 [J/kg] |
SpecificEnthalpy | h_outflow_a2_start | Medium2.h_default | Start value for enthalpy flowing out of port a2 [J/kg] |
SpecificEnthalpy | h_outflow_b2_start | Medium2.h_default | Start value for enthalpy flowing out of port b2 [J/kg] |
MassFlowRate | m1_flow_small | 1E-4*abs(m1_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
MassFlowRate | m2_flow_small | 1E-4*abs(m2_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Boolean | homotopyInitialization | true | = true, use homotopy method |
Diagnostics | |||
Boolean | show_T | false | = true, if actual temperature at port is computed |
Flow resistance | |||
Medium 1 | |||
Boolean | from_dp1 | false | = true, use m_flow = f(dp) else dp = f(m_flow) |
Boolean | linearizeFlowResistance1 | false | = true, use linear relation between m_flow and dp for any flow rate |
Real | deltaM1 | 0.1 | Fraction of nominal flow rate where flow transitions to laminar |
Medium 2 | |||
Boolean | from_dp2 | false | = true, use m_flow = f(dp) else dp = f(m_flow) |
Boolean | linearizeFlowResistance2 | false | = true, use linear relation between m_flow and dp for any flow rate |
Real | deltaM2 | 0.1 | Fraction of nominal flow rate where flow transitions to laminar |
Type | Name | Description |
---|---|---|
replaceable package Medium1 | Medium 1 in the component | |
replaceable package Medium2 | Medium 2 in the component | |
FluidPort_a | port_a1 | Fluid connector a1 (positive design flow direction is from port_a1 to port_b1) |
FluidPort_b | port_b1 | Fluid connector b1 (positive design flow direction is from port_a1 to port_b1) |
FluidPort_a | port_a2 | Fluid connector a2 (positive design flow direction is from port_a2 to port_b2) |
FluidPort_b | port_b2 | Fluid connector b2 (positive design flow direction is from port_a2 to port_b2) |
Ideal humidifier or dehumidifier with prescribed water mass flow rate addition or subtraction
Model for an air humidifier or dehumidifier.
This model adds (or removes) moisture from the air stream. The amount of exchanged moisture is equal to
ṁwat = u ṁwat,nom,
where u is the control input signal and
ṁwat,nom is equal to the parameter mWat_flow_nominal
.
The parameter mWat_flow_nominal
can be positive or negative.
If ṁwat is positive, then moisture is added
to the air stream, otherwise it is removed.
If the connector T_in
is left unconnected, the value
set by the parameter T
is used for the temperature of the water that is
added to the air stream.
This model can only be used with medium models that define the integer constant
Water
which needs to be equal to the index of the water mass fraction
in the species vector.
Extends from Buildings.Fluid.Interfaces.TwoPortHeatMassExchanger (Partial model transporting one fluid stream with storing mass or energy).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Boolean | use_T_in | false | Get the temperature from the input connector |
Temperature | T | 293.15 | Temperature of water that is added to the fluid stream (used if use_T_in=false) [K] |
MassFlowRate | mWat_flow_nominal | Water mass flow rate at u=1, positive for humidification [kg/s] | |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Pressure | dp_nominal | Pressure [Pa] | |
Initialization | |||
MassFlowRate | m_flow.start | 0 | Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s] |
Pressure | dp.start | 0 | Pressure difference between port_a and port_b [Pa] |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Advanced | |||
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Boolean | homotopyInitialization | true | = true, use homotopy method |
Diagnostics | |||
Boolean | show_T | false | = true, if actual temperature at port is computed |
Flow resistance | |||
Boolean | from_dp | false | = true, use m_flow = f(dp) else dp = f(m_flow) |
Boolean | linearizeFlowResistance | false | = true, use linear relation between m_flow and dp for any flow rate |
Real | deltaM | 0.1 | Fraction of nominal flow rate where flow transitions to laminar |
Dynamics | |||
Nominal condition | |||
Time | tau | 30 | Time constant at nominal flow (if energyDynamics <> SteadyState) [s] |
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Formulation of energy balance |
Dynamics | massDynamics | energyDynamics | Formulation of mass balance |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
Type | Name | Description |
---|---|---|
replaceable package Medium | Medium in the component | |
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
input RealInput | T_in | Temperature of water added to the fluid stream |
input RealInput | u | Control input |