Performance data for chiller ElectricEIR
| Name | Description | 
|---|---|
| Generic data record for chiller ElectricEIR | |
| ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes | |
| ElectricEIRChiller York YT 563kW/10.61COP/Vanes | |
| ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes | |
| ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD | |
| ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes | |
| ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD | |
| ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD | |
| ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes | |
| ElectricEIRChiller York YT 897kW/7.60COP/VSD | |
| ElectricEIRChiller York YT 897kW/6.27COP/VSD | |
| ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD | |
| ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes | |
| ElectricEIRChiller York YT 960kW/4.64COP/Vanes | |
| ElectricEIRChiller York YT 1023kW/5.81COP/Vanes | |
| ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes | |
| ElectricEIRChiller York YT 1048kW/6.06COP/Vanes | |
| ElectricEIRChiller York YT 1055kW/5.96COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes | |
| ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes | |
| ElectricEIRChiller York YT 1090kW/7.57COP/VSD | |
| ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes | |
| ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes | |
| ElectricEIRChiller York YT 1125kW/7.92COP/VSD | |
| ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD | |
| ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD | |
| ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes | |
| ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD | |
| ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes | |
| ElectricEIRChiller York YK 1259kW/6.45COP/Vanes | |
| ElectricEIRChiller York YT 1266kW/4.39COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes | |
| ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD | |
| ElectricEIRChiller York YT 1368kW/7.35COP/VSD | |
| ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes | |
| ElectricEIRChiller York YT 1396kW/7.35COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD | |
| ElectricEIRChiller York YT 1403kW/6.94COP/VSD | |
| ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD | |
| ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD | |
| ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD | |
| ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD | |
| ElectricEIRChiller York YT 1459kW/6.40COP/VSD | |
| ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD | |
| ElectricEIRChiller York YT 1495kW/7.51COP/VSD | |
| ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD | |
| ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD | |
| ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD | |
| ElectricEIRChiller York YT 1663kW/9.34COP/Vanes | |
| ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes | |
| ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD | |
| ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes | |
| ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes | |
| ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes | |
| ElectricEIRChiller York YT 1758kW/5.76COP/VSD | |
| ElectricEIRChiller York YT 1758kW/6.26COP/Vanes | |
| ElectricEIRChiller York YT 1758kW/5.96COP/Vanes | |
| ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes | |
| ElectricEIRChiller York YT 1758kW/6.28COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD | |
| ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD | |
| ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes | |
| ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes | |
| ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes | |
| ElectricEIRChiller York YT 1794kW/8.11COP/Vanes | |
| ElectricEIRChiller York YT 1794kW/7.90COP/VSD | |
| ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD | |
| ElectricEIRChiller York YT 1867kW/10.09COP/Vanes | |
| ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes | |
| ElectricEIRChiller York YT 1881kW/6.77COP/VSD | |
| ElectricEIRChiller York YK 1881kW/6.53COP/Vanes | |
| ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes | |
| ElectricEIRChiller York YT 1934kW/7.55COP/Vanes | |
| ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes | |
| ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes | |
| ElectricEIRChiller York YK 1997kW/7.24COP/Vanes | |
| ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes | |
| ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes | |
| ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes | |
| ElectricEIRChiller York YT 2110kW/7.15COP/Vanes | |
| ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes | |
| ElectricEIRChiller York YK 2159kW/6.85COP/Vanes | |
| ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes | |
| ElectricEIRChiller York YK 2201kW/6.69COP/Vanes | |
| ElectricEIRChiller York YT 2233kW/9.54COP/VSD | |
| ElectricEIRChiller York YK 2237kW/6.41COP/Vanes | |
| ElectricEIRChiller York YK 2275kW/6.32COP/Vanes | |
| ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes | |
| ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD | |
| ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes | |
| ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD | |
| ElectricEIRChiller York YK 2412kW/5.58COP/Vanes | |
| ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes | |
| ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD | |
| ElectricEIRChiller York YK 2771kW/6.84COP/VSD | |
| ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes | |
| ElectricEIRChiller York YT 3133kW/9.16COP/Vanes | |
| ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes | |
| ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes | |
| ElectricEIRChiller York YK 4396kW/6.63COP/Vanes | |
| ElectricEIRChiller York YK 4477kW/6.64COP/Vanes | |
| ElectricEIRChiller York YK 4515kW/6.22COP/Vanes | |
| ElectricEIRChiller York YK 4537kW/6.28COP/Vanes | |
| ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes | |
| ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes | |
| ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes | |
| ElectricEIRChiller York YK 4966kW/6.05COP/Vanes | |
| ElectricEIRChiller York YK 4969kW/7.14COP/Vanes | |
| ElectricEIRChiller York YK 4969kW/7.07COP/Vanes | |
| ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes | |
| ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes | |
| ElectricEIRChiller York YK 5170kW/7.15COP/Vanes | |
| ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes | |
| ElectricEIRChiller York YK 5465kW/6.94COP/Vanes | |
| ElectricEIRChiller York YK 5549kW/6.50COP/Vanes | |
| ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes | |
| DOE-2 Centrifugal/5.50COP | |
| ElectricEIRChiller Multistack MS 172kW/3.67COP/None | |
| DOE-2 Reciprocating/3.67COP | |
| ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve | |
| ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve | |
| ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve | |
| ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve | |
| ElectricEIRChiller York YS 672kW/7.90COP/Valve | |
| ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve | |
| ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve | |
| ElectricEIRChiller York YS 756kW/7.41COP/Valve | |
| ElectricEIRChiller York YS 781kW/5.42COP/Valve | |
| ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve | |
| ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve | |
| ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve | |
| ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve | |
| ElectricEIRChiller York YS 879kW/5.82COP/Valve | |
| ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve | |
| ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve | |
| ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve | |
| ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve | |
| ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve | |
| ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve | |
| ElectricEIRChiller York YS 1171kW/9.15COP/Valve | |
| ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve | |
| ElectricEIRChiller York YS 1554kW/9.31COP/Valve | |
| ElectricEIRChiller York YS 1758kW/5.84COP/Valve | |
| ElectricEIRChiller Trane CGWD 207kW/3.99COP/None | 
Buildings.Fluid.Chillers.Data.ElectricEIR.GenericGeneric data record for chiller ElectricEIR
Extends from Buildings.Fluid.Chillers.Data.BaseClasses.Chiller (Base classes for chiller models).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | Maximum part load ratio | |
| Real | PLRMinUnl | Minimum part unload ratio | |
| Real | PLRMin | Minimum part load ratio | |
| Real | etaMotor | Fraction of compressor motor heat entering refrigerant | |
| Temperature | TConEnt_nominal | Temperature of fluid entering condenser at nominal condition [K] | |
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | Reference capacity (negative number) [W] | |
| Real | COP_nominal | Reference coefficient of performance | |
| MassFlowRate | mEva_flow_nominal | Nominal mass flow at evaporator [kg/s] | |
| MassFlowRate | mCon_flow_nominal | Nominal mass flow at condenser [kg/s] | |
| Temperature | TEvaLvg_nominal | Temperature of fluid leaving evaporator at nominal condition [K] | |
| Performance curves | |||
| Integer | nCapFunT | 6 | Number of coefficients for capFunT | 
| Integer | nEIRFunT | 6 | Number of coefficients for capFunT | 
| Integer | nEIRFunPLR | 3 | Number of coefficients for capFunT | 
| Real | capFunT[nCapFunT] | Biquadratic coefficients for capFunT | |
| Real | EIRFunT[nEIRFunT] | Biquadratic coefficients for EIRFunT | |
| Real | EIRFunPLR[nEIRFunPLR] | Coefficients for EIRFunPLR | |
| Temperature | TEvaLvgMin | Minimum value for leaving evaporator temperature [K] | |
| Temperature | TEvaLvgMax | Maximum value for leaving evaporator temperature [K] | |
| Temperature | TConEntMin | Minimum value for entering condenser temperature [K] | |
| Temperature | TConEntMax | Maximum value for entering condenser temperature [K] | |
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_471kW_5_89COP_VanesElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes,  !- Name
    471200,                  !- Reference Capacity {W}
    5.89,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01035,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01924,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.15,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.15 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -471200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.89 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01035 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01924 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.521130E-01,1.324053E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.475238E-01,-2.588210E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.778889E-01,2.338363E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_563kW_10_61COP_VanesElectricEIRChiller York YT 563kW/10.61COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 563kW/10.61COP/Vanes,  !- Name
    562600,                  !- Reference Capacity {W}
    10.61,                   !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01514,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0241,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 563kW/10.61COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -562600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 10.61 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-1.288612E-01,-8.919540E-02... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {-5.781003E-01,-1.169130E-01... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {5.203969E-01,-7.775900E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_703kW_7_03COP_VanesElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes,  !- Name
    703300,                  !- Reference Capacity {W}
    7.03,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02019,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.02902,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -703300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.03 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02019 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.02902 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.779439E-01,1.073486E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.234029E-01,-1.171542E-01,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.864389E-01,-2.522595E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_724kW_6_04COP_VanesElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes,  !- Name
    724400,                  !- Reference Capacity {W}
    6.04,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    21.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01779,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01956,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -724400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.04 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.418712E-01,-8.384251E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.059102E-01,-1.621557E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.879418E-01,3.562862E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 13.75 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_742kW_5_42COP_VSDElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD,  !- Name
    742000,                  !- Reference Capacity {W}
    5.42,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    21.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01779,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01956,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -742000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.42 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.797101E-01,-2.895701E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.946139E-01,-4.829399E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.202277E-01,1.396384E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_816kW_6_74COP_VanesElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes,  !- Name
    815800,                  !- Reference Capacity {W}
    6.74,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01748,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04164,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -815800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.74 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01748 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04164 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.862590E-01,5.799373E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.335321E-01,4.465107E-04,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.070136E-01,8.654874E-02,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_819kW_8_11COP_VanesElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes,  !- Name
    819300,                  !- Reference Capacity {W}
    8.11,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02524,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03785,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -819300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.11 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02524 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.392673E-01,4.328784E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.925176E-01,-1.908391E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.830681E-01,2.254147E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_VanesElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes,  !- Name
    822900,                  !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04744,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -822900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.28 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.573150E-01,8.714616E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.029134E-01,2.171359E-02,2... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.965419E-01,4.689744E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_869kW_5_57COP_VSDElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD,  !- Name
    868600,                  !- Reference Capacity {W}
    5.57,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01754,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.02593,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -868600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.57 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01754 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.02593 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.406799E-01,1.253709E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.943721E-01,1.079147E-01,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.501042E-01,-6.804336E-02,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_897kW_7_23COP_VSDElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD,  !- Name
    896700,                  !- Reference Capacity {W}
    7.23,                    !- Reference COP {W/W}
    9.82,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0436,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.23 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0436 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.559679E-01,7.630860E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.511011E-01,4.948557E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.036380E-01,-3.913200E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_897kW_6_50COP_VanesElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes,  !- Name
    896700,                  !- Reference Capacity {W}
    6.50,                    !- Reference COP {W/W}
    9.82,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04423,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.50 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04423 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.009156E-01,2.151274E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.527749E-01,-4.336881E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.323416E-01,2.561103E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_897kW_7_60COP_VSDElectricEIRChiller York YT 897kW/7.60COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 897kW/7.60COP/VSD,  !- Name
    896700,                  !- Reference Capacity {W}
    7.60,                    !- Reference COP {W/W}
    9.83,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 897kW/7.60COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.60 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 9.83 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.699948E-01,2.961470E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.526128E-01,3.299472E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {4.708628E-02,7.070062E-02,8... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_897kW_6_27COP_VSDElectricEIRChiller York YT 897kW/6.27COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 897kW/6.27COP/VSD,  !- Name
    896700,                  !- Reference Capacity {W}
    6.27,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 897kW/6.27COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.27 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.197991E-01,1.568955E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.530767E-01,-5.683068E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.836320E-02,-1.638320E-02,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_897kW_6_23COP_VSDElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD,  !- Name
    896700,                  !- Reference Capacity {W}
    6.23,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04442,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.23 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04442 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.862185E-01,3.144947E-02,2... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.606461E-01,-1.202294E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.075556E-01,-2.126466E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_932kW_5_09COP_VanesElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes,  !- Name
    931900,                  !- Reference Capacity {W}
    5.09,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03785,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -931900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.09 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.182278E+00,3.259490E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.053491E-01,-1.089778E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {6.823245E-02,6.672421E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_960kW_4_64COP_VanesElectricEIRChiller York YT 960kW/4.64COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 960kW/4.64COP/Vanes,  !- Name
    960000,                  !- Reference Capacity {W}
    4.64,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03785,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 960kW/4.64COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.09,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.09 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -960000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 4.64 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-2.278537E-01,4.055945E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.735924E-01,2.270414E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.737941E-01,3.141127E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1023kW_5_81COP_VanesElectricEIRChiller York YT 1023kW/5.81COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1023kW/5.81COP/Vanes,  !- Name
    1023300,                 !- Reference Capacity {W}
    5.81,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02366,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1023kW/5.81COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1023300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.81 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02366 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.571195E-01,-1.571421E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.254964E-01,-1.972389E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.368399E-01,3.286421E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1030kW_8_58COP_VanesElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes,  !- Name
    1030300,                 !- Reference Capacity {W}
    8.58,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02378,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03407,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.08,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.08,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.08 | Minimum part unload ratio | 
| Real | PLRMin | 0.08 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1030300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.58 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02378 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03407 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.736028E-01,5.571395E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.125878E-01,1.388940E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.215320E-01,-9.188416E-03,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1048kW_6_06COP_VanesElectricEIRChiller York YT 1048kW/6.06COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1048kW/6.06COP/Vanes,  !- Name
    1047900,                 !- Reference Capacity {W}
    6.06,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04542,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05678,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1048kW/6.06COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1047900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.06 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04542 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.238221E-01,1.747548E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.255594E-01,-3.502968E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.543796E-01,7.276121E-01,1... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1055kW_5_96COP_VanesElectricEIRChiller York YT 1055kW/5.96COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes,  !- Name
    1055000,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02839,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05678,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1055000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.96 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02839 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.785912E-01,-5.900023E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.245110E-01,-2.850126E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.619878E-01,2.393605E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1076kW_5_52COP_VanesElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes,  !- Name
    1076100,                 !- Reference Capacity {W}
    5.52,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04744,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1076100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.52 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.187704E-01,4.509452E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.511044E-01,2.415573E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.315760E-01,-3.004087E-02,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1080kW_7_39COP_VanesElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes,  !- Name
    1079600,                 !- Reference Capacity {W}
    7.39,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.61,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06416,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.61 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1079600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.39 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06416 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.365583E-01,-3.677215E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.608716E-01,-5.637178E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.789841E-01,2.976513E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 16.24 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.61 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1090kW_7_57COP_VSDElectricEIRChiller York YT 1090kW/7.57COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1090kW/7.57COP/VSD,  !- Name
    1090100,                 !- Reference Capacity {W}
    7.57,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1090kW/7.57COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.14 | Minimum part unload ratio | 
| Real | PLRMin | 0.14 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1090100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.57 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.769028E-01,5.711844E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.241019E-01,-4.961574E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.431969E-01,-4.920686E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1104kW_8_00COP_VanesElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes,  !- Name
    1104200,                 !- Reference Capacity {W}
    8.00,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02423,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03028,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.08,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.08,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.08 | Minimum part unload ratio | 
| Real | PLRMin | 0.08 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1104200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.00 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02423 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03028 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.210185E-01,4.386152E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.655242E-01,-3.808337E-04,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.091150E-01,-1.089639E-02,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_VanesElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes,  !- Name
    1125300,                 !- Reference Capacity {W}
    4.89,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02776,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.02618,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 4.89 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.02618 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.151549E-01,-1.181250E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.810580E-01,-4.344257E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.807198E-01,-1.469686E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1125kW_7_92COP_VSDElectricEIRChiller York YT 1125kW/7.92COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1125kW/7.92COP/VSD,  !- Name
    1125300,                 !- Reference Capacity {W}
    7.92,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03243,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05173,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1125kW/7.92COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.92 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.034212E-01,2.327078E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.542286E-01,-2.451604E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.147453E-01,4.231235E-02,8... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1129kW_7_19COP_VanesElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes,  !- Name
    1128800,                 !- Reference Capacity {W}
    7.19,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02776,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.15,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.15,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.15 | Minimum part unload ratio | 
| Real | PLRMin | 0.15 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1128800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.19 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.922479E-01,-4.388411E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.742142E-01,-5.536709E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.693841E-01,2.475201E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1143kW_6_57COP_VSDElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD,  !- Name
    1142900,                 !- Reference Capacity {W}
    6.57,                    !- Reference COP {W/W}
    10.00,                   !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02593,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1142900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.57 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 10.00 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.939538E-01,4.096493E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.475580E-01,-1.187942E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.408822E-01,-1.578153E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1157kW_5_62COP_VSDElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD,  !- Name
    1156900,                 !- Reference Capacity {W}
    5.62,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    21.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02801,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03186,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1156900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.62 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02801 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03186 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.076248E+00,5.436724E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.075567E+00,-3.893571E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.608589E-01,-2.058215E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1196kW_6_50COP_VanesElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes,  !- Name
    1195600,                 !- Reference Capacity {W}
    6.50,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03426,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04252,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.50 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.126801E+00,-4.220591E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.514432E-01,-2.252147E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.724491E-01,2.710369E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1213kW_7_78COP_VanesElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes,  !- Name
    1213200,                 !- Reference Capacity {W}
    7.78,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03243,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04782,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.17 | Minimum part unload ratio | 
| Real | PLRMin | 0.17 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1213200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.78 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04782 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.070437E-01,-7.437456E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.002142E+00,-2.505239E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.847744E-01,4.027863E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1231kW_6_18COP_VanesElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes,  !- Name
    1230800,                 !- Reference Capacity {W}
    6.18,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03533,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0511,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1230800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.18 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0511 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.152795E+00,9.770474E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.067591E-01,1.868314E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.117054E-01,4.263662E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1234kW_5_39COP_VSDElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD,  !- Name
    1234300,                 !- Reference Capacity {W}
    5.39,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02593,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03861,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1234300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.39 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03861 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.905815E-01,1.190927E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.771659E-01,1.144965E-01,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.495681E-01,-1.449639E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1259kW_6_26COP_VanesElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes,  !- Name
    1258900,                 !- Reference Capacity {W}
    6.26,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02593,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03823,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.26 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03823 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.082071E+00,3.200888E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.582035E-01,6.896017E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.226232E-01,5.199282E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_1259kW_6_45COP_VanesElectricEIRChiller York YK 1259kW/6.45COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 1259kW/6.45COP/Vanes,  !- Name
    1258900,                 !- Reference Capacity {W}
    6.45,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02631,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06246,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 1259kW/6.45COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.45 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.02631 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06246 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.609200E-01,7.223733E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.991536E-01,6.305932E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.014593E-01,6.216537E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1266kW_4_39COP_VanesElectricEIRChiller York YT 1266kW/4.39COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1266kW/4.39COP/Vanes,  !- Name
    1266000,                 !- Reference Capacity {W}
    4.39,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    35.00,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03533,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05773,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1266kW/4.39COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.11,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.11,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.11 | Minimum part unload ratio | 
| Real | PLRMin | 0.11 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 35.00 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1266000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 4.39 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05773 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.285663E-01,-2.860032E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.284925E-02,4.206167E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {7.326942E-01,-7.962527E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1284kW_6_20COP_VanesElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes,  !- Name
    1283500,                 !- Reference Capacity {W}
    6.20,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03684,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05337,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1283500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.20 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.119245E+00,-1.524417E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.815645E-01,-2.448971E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.324812E-01,7.690691E-01,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1294kW_7_61COP_VanesElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes,  !- Name
    1294100,                 !- Reference Capacity {W}
    7.61,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03243,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.16,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.16,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.16 | Minimum part unload ratio | 
| Real | PLRMin | 0.16 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1294100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.61 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.274222E-01,1.278683E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.085249E+00,-9.441252E-04,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.344563E-02,3.993002E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1329kW_5_38COP_VanesElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes,  !- Name
    1329300,                 !- Reference Capacity {W}
    5.38,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04732,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07098,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.29,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.29,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.29 | Minimum part unload ratio | 
| Real | PLRMin | 0.29 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1329300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.38 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04732 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07098 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.339754E-01,1.016009E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.074052E-01,3.355495E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {4.079777E-02,1.174456E+00,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1350kW_7_90COP_VSDElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD,  !- Name
    1350400,                 !- Reference Capacity {W}
    7.90,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03684,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05337,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1350400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.90 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.063866E+00,-1.448990E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.953536E-01,-3.118863E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.336374E-01,-4.098166E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1368kW_7_35COP_VSDElectricEIRChiller York YT 1368kW/7.35COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD,  !- Name
    1367900,                 !- Reference Capacity {W}
    7.35,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07571,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1367900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.35 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.832184E-01,-3.265439E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.227543E-01,-1.415418E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.483562E-02,1.521114E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1372kW_7_49COP_VanesElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes,  !- Name
    1371500,                 !- Reference Capacity {W}
    7.49,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07571,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.07 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.41 | Minimum part unload ratio | 
| Real | PLRMin | 0.41 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1371500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.49 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.993784E-01,6.523380E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.123765E-01,1.616509E-02,1... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {5.154478E-02,9.635713E-01,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1396kW_7_35COP_VanesElectricEIRChiller York YT 1396kW/7.35COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1396kW/7.35COP/Vanes,  !- Name
    1396100,                 !- Reference Capacity {W}
    7.35,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07571,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1396kW/7.35COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1396100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.35 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.167863E-01,-2.788454E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.207500E-01,-9.073869E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.043032E-01,3.720107E-02,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1403kW_7_09COP_VSDElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD,  !- Name
    1403100,                 !- Reference Capacity {W}
    7.09,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03426,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04252,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.17 | Minimum part unload ratio | 
| Real | PLRMin | 0.17 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.09 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.601814E-01,-3.596494E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.098641E+00,-2.485880E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {8.788698E-02,2.678891E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1403kW_6_94COP_VSDElectricEIRChiller York YT 1403kW/6.94COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1403kW/6.94COP/VSD,  !- Name
    1403100,                 !- Reference Capacity {W}
    6.94,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05047,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1403kW/6.94COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.1,                     !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.1 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.94 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-3.447077E-02,1.273138E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.983846E-01,2.396665E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.272242E-02,3.873540E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1407kW_7_14COP_VSDElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD,  !- Name
    1406600,                 !- Reference Capacity {W}
    7.14,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07571,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.14 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.521342E-01,5.248142E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.674858E-01,4.461513E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {5.963988E-02,3.503067E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_1407kW_6_60COP_VanesElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes,  !- Name
    1406600,                 !- Reference Capacity {W}
    6.60,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04038,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05804,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.60 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04038 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05804 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.191784E+00,2.070584E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.929709E-01,3.424884E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {7.700603E-02,5.414789E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1407kW_6_04COP_VSDElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD,  !- Name
    1406600,                 !- Reference Capacity {W}
    6.04,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06057,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07571,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.04 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.042261E+00,2.644821E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.026340E+00,-1.612819E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.188880E-01,6.723542E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 32.22 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1410kW_8_54COP_VSDElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD,  !- Name
    1410100,                 !- Reference Capacity {W}
    8.54,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04,                    !- Reference Chilled Water Flow Rate {m3/s}
    0.05861,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1410100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.54 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05861 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.597856E-01,-6.247187E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.131014E+00,-6.735406E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.662908E-02,7.475978E-01,1... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1442kW_6_61COP_VSDElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD,  !- Name
    1441800,                 !- Reference Capacity {W}
    6.61,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05047,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.07 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1441800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.61 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.007341E-01,1.148568E-03,1... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.287646E-01,-3.024605E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.299787E-02,3.244475E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1459kW_6_40COP_VSDElectricEIRChiller York YT 1459kW/6.40COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1459kW/6.40COP/VSD,  !- Name
    1459400,                 !- Reference Capacity {W}
    6.40,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05047,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1459kW/6.40COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.13,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.13 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1459400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.40 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-1.665585E-01,2.211580E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.438935E-01,9.821191E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.999642E-02,2.509430E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1484kW_9_96COP_VSDElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD,  !- Name
    1484000,                 !- Reference Capacity {W}
    9.96,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09085,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.24,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.24,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.24 | Minimum part unload ratio | 
| Real | PLRMin | 0.24 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1484000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.96 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-4.544480E-01,-3.615933E-02... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {-3.693940E-01,-6.387787E-02... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.353827E-01,1.385983E-02,8... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1495kW_7_51COP_VSDElectricEIRChiller York YT 1495kW/7.51COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD,  !- Name
    1494500,                 !- Reference Capacity {W}
    7.51,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0429,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.06719,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.11,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.11,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.11 | Minimum part unload ratio | 
| Real | PLRMin | 0.11 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1494500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.51 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0429 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06719 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.051921E+00,-1.632255E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.106985E-01,-2.087623E-01,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.517470E-01,-1.577252E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_VanesElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes,  !- Name
    1519200,                 !- Reference Capacity {W}
    7.10,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.08139,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1519200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.10 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.08139 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.265889E+00,3.401563E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.981236E-01,-1.060763E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.563837E-01,4.894381E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1558kW_5_81COP_VSDElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD,  !- Name
    1557800,                 !- Reference Capacity {W}
    5.81,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    21.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03785,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1557800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.81 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.034307E+00,2.390635E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.099343E+00,-3.132676E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.620909E-01,-2.553890E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 11.94 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1586kW_5_53COP_VSDElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD,  !- Name
    1586000,                 !- Reference Capacity {W}
    5.53,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03388,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04669,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1586000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.53 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03388 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04669 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.119233E+00,1.130501E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.110611E+00,-3.795765E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.996379E-01,-1.612021E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1635kW_7_47COP_VanesElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes,  !- Name
    1635200,                 !- Reference Capacity {W}
    7.47,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04416,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06624,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.08,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.08,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.08 | Minimum part unload ratio | 
| Real | PLRMin | 0.08 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.47 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04416 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06624 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.894188E-01,2.983148E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.040733E+00,-7.118888E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.836695E-01,5.781685E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1635kW_6_36COP_VanesElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes,  !- Name
    1635200,                 !- Reference Capacity {W}
    6.36,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03432,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05035,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.36 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03432 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05035 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.639212E-01,1.160405E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.355981E-01,-1.083354E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.581595E-01,2.707154E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1656kW_8_24COP_VSDElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD,  !- Name
    1656300,                 !- Reference Capacity {W}
    8.24,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04322,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06296,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.17 | Minimum part unload ratio | 
| Real | PLRMin | 0.17 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1656300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.24 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04322 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06296 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.611706E-01,-2.867067E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.730916E-01,-8.073559E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.982584E-01,4.414042E-02,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1663kW_9_34COP_VanesElectricEIRChiller York YT 1663kW/9.34COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1663kW/9.34COP/Vanes,  !- Name
    1663300,                 !- Reference Capacity {W}
    9.34,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04139,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0776,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1663kW/9.34COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.17 | Minimum part unload ratio | 
| Real | PLRMin | 0.17 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1663300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.34 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04139 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0776 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.112226E-01,-4.546497E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.028094E+00,-6.127553E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.127966E-01,3.131004E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1674kW_7_89COP_VanesElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes,  !- Name
    1673900,                 !- Reference Capacity {W}
    7.89,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09085,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.32,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.32,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.32 | Minimum part unload ratio | 
| Real | PLRMin | 0.32 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1673900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.89 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.925408E-01,-4.406182E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.868510E-01,-6.325526E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.386410E-01,2.621224E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_VanesElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes,  !- Name
    1680900,                 !- Reference Capacity {W}
    6.59,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04366,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1680900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.59 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04366 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.792987E-01,-5.291217E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.344630E-01,-5.781149E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.619116E-01,2.362420E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1723kW_8_32COP_VSDElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD,  !- Name
    1723100,                 !- Reference Capacity {W}
    8.32,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04757,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06934,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1723100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.32 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06934 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.742518E-01,-5.109937E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {2.950574E-01,-1.036684E-01,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.374010E-01,-1.796745E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1727kW_9_04COP_VanesElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes,  !- Name
    1726600,                 !- Reference Capacity {W}
    9.04,                    !- Reference COP {W/W}
    7.78,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03912,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07192,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.17 | Minimum part unload ratio | 
| Real | PLRMin | 0.17 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1726600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.04 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03912 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07192 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.509915E-01,2.567642E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.072553E+00,-8.058631E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.465824E-01,4.494453E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_1751kW_6_73COP_VanesElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes,  !- Name
    1751300,                 !- Reference Capacity {W}
    6.73,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04145,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09337,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1751300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.73 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.923045E-01,1.003672E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.089395E-01,2.628482E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.250725E-01,2.648297E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1758kW_5_96COP_VanesElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.96 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.074211E+00,7.710761E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.910329E-01,-9.895115E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.694797E-01,9.551656E-02,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_5_76COP_VSDElectricEIRChiller York YT 1758kW/5.76COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1758kW/5.76COP/VSD,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.76,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1758kW/5.76COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.76 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.575085E-01,1.313508E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.794525E-01,6.694756E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {7.859908E-02,1.950291E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.51 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_6_26COP_VanesElectricEIRChiller York YT 1758kW/6.26COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1758kW/6.26COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    6.26,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1758kW/6.26COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.14,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.14 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.26 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.975936E-01,-1.459740E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {2.311197E-01,9.581517E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.720545E-01,5.598164E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_5_96COP_VanesElectricEIRChiller York YT 1758kW/5.96COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1758kW/5.96COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1758kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.96 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.492365E-01,5.551947E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.949320E-01,9.099785E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.236154E-01,2.590053E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_VanesElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.96 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.566057E-02,-2.457943E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.243313E+00,-3.031784E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.871377E-01,5.849639E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_6_28COP_VanesElectricEIRChiller York YT 1758kW/6.28COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1758kW/6.28COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1758kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.28 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.079149E-01,-2.006276E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.605391E-01,-1.377994E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.861223E-01,5.482049E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1758kW_5_86COP_VSDElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.86,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06303,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07337,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.86 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07337 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.677279E-01,-3.175504E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.743365E-01,-5.054806E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.784580E-01,-5.498632E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1758kW_6_46COP_VSDElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD,  !- Name
    1758300,                 !- Reference Capacity {W}
    6.46,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.46 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.066671E+00,5.889240E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.989434E-02,2.062907E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.268954E-01,3.297771E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1758kW_6_87COP_VanesElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    6.87,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.87 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.085529E-01,3.412026E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.329473E-01,5.521802E-03,1... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.401900E-01,5.090345E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1776kW_8_00COP_VanesElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes,  !- Name
    1775900,                 !- Reference Capacity {W}
    8.00,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04757,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07003,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.17 | Minimum part unload ratio | 
| Real | PLRMin | 0.17 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1775900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.00 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07003 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.841535E-01,-3.584260E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.006719E-01,-3.137026E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.276235E-01,2.787167E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1779kW_6_18COP_VanesElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes,  !- Name
    1779400,                 !- Reference Capacity {W}
    6.18,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06303,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.08858,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.18 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.08858 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.703515E-01,-4.051337E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.872331E-01,-3.907248E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.090532E-01,2.641442E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1779kW_6_18COP_VanesElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes,  !- Name
    1779400,                 !- Reference Capacity {W}
    6.18,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04454,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.18 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04454 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.331346E-01,-5.678656E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.137523E-01,-1.879556E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.699409E-01,1.874304E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1794kW_8_11COP_VanesElectricEIRChiller York YT 1794kW/8.11COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1794kW/8.11COP/Vanes,  !- Name
    1793500,                 !- Reference Capacity {W}
    8.11,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05148,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09653,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1794kW/8.11COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.08,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.08 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.11 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.536140E+00,-1.630760E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.546274E-01,2.456473E-01,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.187543E-02,8.272483E-01,1... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1794kW_7_90COP_VSDElectricEIRChiller York YT 1794kW/7.90COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1794kW/7.90COP/VSD,  !- Name
    1793500,                 !- Reference Capacity {W}
    7.90,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05148,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09653,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1794kW/7.90COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.90 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.552268E-01,-1.553435E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.984829E-01,-1.552700E-01,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.445880E-01,1.059293E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1797kW_5_69COP_VanesElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes,  !- Name
    1797000,                 !- Reference Capacity {W}
    5.69,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07737,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09672,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.39,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.39,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.39 | Minimum part unload ratio | 
| Real | PLRMin | 0.39 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1797000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.69 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07737 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09672 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.084596E-01,4.671596E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.084290E+00,-4.318103E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {5.926251E-01,-2.657314E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1801kW_6_34COP_VSDElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD,  !- Name
    1800500,                 !- Reference Capacity {W}
    6.34,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05161,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06385,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1800500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.34 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05161 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06385 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.174861E-01,-7.299051E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.931082E-01,-1.885558E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.040764E-01,2.818752E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1867kW_10_09COP_VanesElectricEIRChiller York YT 1867kW/10.09COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1867kW/10.09COP/Vanes,  !- Name
    1867300,                 !- Reference Capacity {W}
    10.09,                   !- Reference COP {W/W}
    7.78,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09085,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1867kW/10.09COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1867300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 10.09 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.451516E-01,-1.252382E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.668391E-01,1.506485E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.157002E-01,2.251016E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1871kW_6_49COP_VanesElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes,  !- Name
    1870800,                 !- Reference Capacity {W}
    6.49,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06303,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0877,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1870800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.49 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0877 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.658630E-03,-3.836575E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.029608E+00,-7.149045E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.984908E-01,2.906868E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1881kW_6_77COP_VSDElectricEIRChiller York YT 1881kW/6.77COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1881kW/6.77COP/VSD,  !- Name
    1881400,                 !- Reference Capacity {W}
    6.77,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1881kW/6.77COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.77 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.065247E-01,-4.158206E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.175311E-01,-3.913241E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {6.087656E-02,4.842164E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_1881kW_6_53COP_VanesElectricEIRChiller York YK 1881kW/6.53COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 1881kW/6.53COP/Vanes,  !- Name
    1881400,                 !- Reference Capacity {W}
    6.53,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04397,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.1041,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 1881kW/6.53COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.53 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.561286E-01,4.130164E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.434989E-01,4.361264E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {5.272116E-02,4.176382E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 9.44 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1895kW_6_42COP_VanesElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes,  !- Name
    1895400,                 !- Reference Capacity {W}
    6.42,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09085,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.09,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.09 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1895400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.42 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.573195E-01,-1.131937E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.915073E-01,-4.399727E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.592598E-01,1.425462E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1934kW_7_55COP_VanesElectricEIRChiller York YT 1934kW/7.55COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1934kW/7.55COP/Vanes,  !- Name
    1934100,                 !- Reference Capacity {W}
    7.55,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    13.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05552,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.08675,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1934kW/7.55COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 13.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.55 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.08675 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.420318E-02,1.103599E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.173674E+00,-1.301647E-01,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.706237E-01,6.063362E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1934kW_6_01COP_VanesElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes,  !- Name
    1934100,                 !- Reference Capacity {W}
    6.01,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05552,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07981,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.08,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.08 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.01 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.893111E-01,-3.834949E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {2.885371E-01,-5.877829E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.849256E-01,-2.369152E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WDC_1973kW_6_28COP_VanesElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes,  !- Name
    1972800,                 !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04145,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09337,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1972800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.28 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.110884E+00,7.376077E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.097378E+00,-3.018324E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.282891E-01,2.722981E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_1997kW_7_24COP_VanesElectricEIRChiller York YK 1997kW/7.24COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 1997kW/7.24COP/Vanes,  !- Name
    1997400,                 !- Reference Capacity {W}
    7.24,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04397,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.1041,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 1997kW/7.24COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.18 | Minimum part unload ratio | 
| Real | PLRMin | 0.18 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1997400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.24 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.058272E-01,1.309175E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.188194E-01,8.769791E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.359332E-02,5.873752E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_2043kW_8_44COP_VanesElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes,  !- Name
    2043100,                 !- Reference Capacity {W}
    8.44,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04757,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06814,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.08,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.08,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.08 | Minimum part unload ratio | 
| Real | PLRMin | 0.08 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.44 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.06814 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.383569E-01,4.716323E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.891693E-01,1.168677E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.225600E-01,3.070007E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2043kW_9_08COP_VanesElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes,  !- Name
    2043100,                 !- Reference Capacity {W}
    9.08,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    18.33,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.09085,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.28,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.28,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.28 | Minimum part unload ratio | 
| Real | PLRMin | 0.28 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.08 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-1.340241E+00,7.634284E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.065177E-01,1.178669E-02,2... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.173752E-01,4.394720E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_2057kW_6_05COP_VanesElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes,  !- Name
    2057200,                 !- Reference Capacity {W}
    6.05,                    !- Reference COP {W/W}
    7.78,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.08322,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09722,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.28,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.28,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.28 | Minimum part unload ratio | 
| Real | PLRMin | 0.28 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2057200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.05 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.08322 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09722 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.737452E-01,-1.249478E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.623086E-01,-5.844490E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {4.041274E-01,-3.861525E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_2110kW_7_15COP_VanesElectricEIRChiller York YT 2110kW/7.15COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 2110kW/7.15COP/Vanes,  !- Name
    2110000,                 !- Reference Capacity {W}
    7.15,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06057,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 2110kW/7.15COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2110000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.15 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.359238E-01,1.785857E-02,1... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.270855E-01,-4.119654E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.469187E-01,1.862690E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_2124kW_6_03COP_VanesElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes,  !- Name
    2124000,                 !- Reference Capacity {W}
    6.03,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05552,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07981,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2124000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.03 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.040134E+00,-1.745650E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {1.157799E+00,-3.621524E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.051419E-01,2.033679E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2159kW_6_85COP_VanesElectricEIRChiller York YK 2159kW/6.85COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2159kW/6.85COP/Vanes,  !- Name
    2159200,                 !- Reference Capacity {W}
    6.85,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2159kW/6.85COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.14 | Minimum part unload ratio | 
| Real | PLRMin | 0.14 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2159200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.85 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.322235E-01,1.553954E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.106730E-01,-3.786410E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.595694E-01,1.889684E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2184kW_6_78COP_VanesElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes,  !- Name
    2183800,                 !- Reference Capacity {W}
    6.78,                    !- Reference COP {W/W}
    7.78,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04883,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2183800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.78 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04883 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.235680E+00,2.213527E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.877947E-01,-1.334886E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {8.942647E-02,5.249540E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2201kW_6_69COP_VanesElectricEIRChiller York YK 2201kW/6.69COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes,  !- Name
    2201400,                 !- Reference Capacity {W}
    6.69,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.14 | Minimum part unload ratio | 
| Real | PLRMin | 0.14 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2201400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.69 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.474968E-01,-4.800356E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.234137E-01,1.308264E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.653493E-01,1.444620E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_2233kW_9_54COP_VSDElectricEIRChiller York YT 2233kW/9.54COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 2233kW/9.54COP/VSD,  !- Name
    2233000,                 !- Reference Capacity {W}
    9.54,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06107,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11451,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 2233kW/9.54COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2233000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.54 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06107 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11451 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.585741E-01,-5.127829E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.563409E-01,-1.966623E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {6.917141E-02,1.743339E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2237kW_6_41COP_VanesElectricEIRChiller York YK 2237kW/6.41COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2237kW/6.41COP/Vanes,  !- Name
    2236600,                 !- Reference Capacity {W}
    6.41,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2237kW/6.41COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.13,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.13,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.13 | Minimum part unload ratio | 
| Real | PLRMin | 0.13 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2236600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.41 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.899710E-01,-1.413334E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.567950E-01,3.354557E-03,1... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.605354E-01,2.125571E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2275kW_6_32COP_VanesElectricEIRChiller York YK 2275kW/6.32COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes,  !- Name
    2275200,                 !- Reference Capacity {W}
    6.32,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.13,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.13,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.13 | Minimum part unload ratio | 
| Real | PLRMin | 0.13 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2275200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.32 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.034673E+00,-1.091064E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.326094E-01,-6.056615E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.735485E-01,2.163041E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2300kW_8_10COP_VanesElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes,  !- Name
    2299900,                 !- Reference Capacity {W}
    8.10,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09085,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.23,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.23,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.23 | Minimum part unload ratio | 
| Real | PLRMin | 0.23 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2299900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 8.10 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.268137E-01,3.920902E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.178121E-01,6.561784E-03,8... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.161399E-01,4.347344E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2317kW_6_33COP_VSDElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD,  !- Name
    2317400,                 !- Reference Capacity {W}
    6.33,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.09085,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2317400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.33 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.277716E-01,1.018101E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {3.502330E-01,-2.301510E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.861441E-02,5.297727E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_2391kW_6_77COP_VanesElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes,  !- Name
    2391300,                 !- Reference Capacity {W}
    6.77,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06858,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0846,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.77 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.266646E-01,-2.367443E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.036386E-01,2.524850E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_2391kW_6_44COP_VSDElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD,  !- Name
    2391300,                 !- Reference Capacity {W}
    6.44,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06858,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0846,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.44 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.230142E-01,-2.371649E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.774812E-02,2.490111E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2412kW_5_58COP_VanesElectricEIRChiller York YK 2412kW/5.58COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2412kW/5.58COP/Vanes,  !- Name
    2412400,                 !- Reference Capacity {W}
    5.58,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.09085,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2412kW/5.58COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.12,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.12,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.12 | Minimum part unload ratio | 
| Real | PLRMin | 0.12 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2412400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.58 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.473817E-01,8.069214E-03,8... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.626807E-01,-2.305674E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.472427E-01,7.531481E-01,8... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_2462kW_6_67COP_VanesElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes,  !- Name
    2461600,                 !- Reference Capacity {W}
    6.67,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07066,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.10157,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2461600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.67 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07066 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.10157 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.561527E-01,5.742999E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.462893E-01,2.854651E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {9.222135E-02,5.830980E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2567kW_11_77COP_VSDElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD,  !- Name
    2567100,                 !- Reference Capacity {W}
    11.77,                   !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.12113,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.15142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.11,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.11,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.11 | Minimum part unload ratio | 
| Real | PLRMin | 0.11 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2567100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 11.77 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.12113 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.549428E-01,2.748161E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.561990E-01,-3.333063E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.039419E-01,4.184975E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2771kW_6_84COP_VSDElectricEIRChiller York YK 2771kW/6.84COP/VSD
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2771kW/6.84COP/VSD,  !- Name
    2771100,                 !- Reference Capacity {W}
    6.84,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.10094,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.15142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2771kW/6.84COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2771100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.84 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.10094 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.734286E-01,4.848829E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.203736E-01,1.030460E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {8.653354E-02,1.737382E-01,7... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2799kW_6_40COP_VanesElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes,  !- Name
    2799200,                 !- Reference Capacity {W}
    6.40,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.09893,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.13761,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -2799200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.40 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.09893 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.13761 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.210324E-01,-2.752320E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {2.267558E-01,-7.615857E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.023576E-01,-2.893592E-02,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_3133kW_9_16COP_VanesElectricEIRChiller York YT 3133kW/9.16COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 3133kW/9.16COP/Vanes,  !- Name
    3133300,                 !- Reference Capacity {W}
    9.16,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.08076,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.12618,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 3133kW/9.16COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.07,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.07,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.07 | Minimum part unload ratio | 
| Real | PLRMin | 0.07 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -3133300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.16 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.08076 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.12618 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.607419E-01,1.323998E-02,6... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.150153E-01,-3.956395E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.387579E-01,6.435208E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_VanesElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes,  !- Name
    3165000,                 !- Reference Capacity {W}
    6.48,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.09085,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.13627,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -3165000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.48 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.13627 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.342558E+00,7.520735E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.347904E-01,6.551597E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.054110E-01,4.090646E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_VanesElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes,  !- Name
    4019500,                 !- Reference Capacity {W}
    7.35,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07874,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09842,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.14 | Minimum part unload ratio | 
| Real | PLRMin | 0.14 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4019500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.35 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07874 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09842 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.958422E-01,3.762768E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.322623E-01,-2.157964E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {5.763566E-02,5.964012E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4396kW_6_63COP_VanesElectricEIRChiller York YK 4396kW/6.63COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4396kW/6.63COP/Vanes,  !- Name
    4395800,                 !- Reference Capacity {W}
    6.63,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4396kW/6.63COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.41 | Minimum part unload ratio | 
| Real | PLRMin | 0.41 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4395800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.63 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.693621E-01,-7.284715E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.913358E-01,-5.974145E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.021070E-01,3.103971E-02,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4477kW_6_64COP_VanesElectricEIRChiller York YK 4477kW/6.64COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes,  !- Name
    4476700,                 !- Reference Capacity {W}
    6.64,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.41 | Minimum part unload ratio | 
| Real | PLRMin | 0.41 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4476700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.64 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.844230E-01,-9.879643E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.264570E-01,-3.391606E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.767206E-01,1.074393E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4515kW_6_22COP_VanesElectricEIRChiller York YK 4515kW/6.22COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4515kW/6.22COP/Vanes,  !- Name
    4515400,                 !- Reference Capacity {W}
    6.22,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4515kW/6.22COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.40 | Minimum part unload ratio | 
| Real | PLRMin | 0.40 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4515400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.22 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.732405E-01,-7.176618E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.908290E-01,1.028668E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.870815E-01,3.951784E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4537kW_6_28COP_VanesElectricEIRChiller York YK 4537kW/6.28COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4537kW/6.28COP/Vanes,  !- Name
    4536500,                 !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4537kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.40 | Minimum part unload ratio | 
| Real | PLRMin | 0.40 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4536500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.28 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.418253E-01,8.142292E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.709829E-01,-2.257680E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.528426E-01,2.920280E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_4610kW_6_34COP_VanesElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes,  !- Name
    4610300,                 !- Reference Capacity {W}
    6.34,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19129,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24757,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4610300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.34 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19129 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24757 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.614836E-01,-3.988130E-03,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.415078E-01,-4.779029E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.026691E-01,2.922585E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_4667kW_6_16COP_VanesElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes,  !- Name
    4666600,                 !- Reference Capacity {W}
    6.16,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.40 | Minimum part unload ratio | 
| Real | PLRMin | 0.40 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4666600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.16 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {4.084496E-01,-4.396326E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.214788E-01,-8.218594E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.771252E-01,2.854188E-02,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_4677kW_6_27COP_VanesElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes,  !- Name
    4677100,                 !- Reference Capacity {W}
    6.27,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.20138,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.41 | Minimum part unload ratio | 
| Real | PLRMin | 0.41 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4677100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.27 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.20138 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.449416E-01,-2.116553E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.283132E-01,-3.030491E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.531562E-01,-2.126229E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4966kW_6_05COP_VanesElectricEIRChiller York YK 4966kW/6.05COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4966kW/6.05COP/Vanes,  !- Name
    4965500,                 !- Reference Capacity {W}
    6.05,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.21198,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.26498,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4966kW/6.05COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.12,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.12,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.12 | Minimum part unload ratio | 
| Real | PLRMin | 0.12 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4965500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.05 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.21198 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.746486E-01,-3.051134E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {8.229769E-01,-8.128614E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.416463E-01,1.947185E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4969kW_7_14COP_VanesElectricEIRChiller York YK 4969kW/7.14COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes,  !- Name
    4969000,                 !- Reference Capacity {W}
    7.14,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.17665,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.26498,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.16,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.16,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.07 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.16 | Minimum part unload ratio | 
| Real | PLRMin | 0.16 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.14 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.817577E-01,-1.012013E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.382162E-01,-5.847442E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.259512E-01,2.320151E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4969kW_7_07COP_VanesElectricEIRChiller York YK 4969kW/7.07COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4969kW/7.07COP/Vanes,  !- Name
    4969000,                 !- Reference Capacity {W}
    7.07,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.17665,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.26498,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4969kW/7.07COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.16,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.16,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.06 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.16 | Minimum part unload ratio | 
| Real | PLRMin | 0.16 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.07 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.803605E-01,-9.685535E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.220087E-01,-4.480691E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.308102E-01,1.802734E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_4997kW_6_40COP_VanesElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes,  !- Name
    4997200,                 !- Reference Capacity {W}
    6.40,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.40 | Minimum part unload ratio | 
| Real | PLRMin | 0.40 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -4997200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.40 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {7.122762E-02,2.550937E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.685097E-01,-2.541433E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.364887E-01,2.122607E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_5148kW_6_34COP_VanesElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes,  !- Name
    5148400,                 !- Reference Capacity {W}
    6.34,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.18283,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.25526,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -5148400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.34 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.25526 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {3.564454E-01,2.020689E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.426449E-01,3.961314E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.883602E-01,5.018646E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_5170kW_7_15COP_VanesElectricEIRChiller York YK 5170kW/7.15COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 5170kW/7.15COP/Vanes,  !- Name
    5169500,                 !- Reference Capacity {W}
    7.15,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.17665,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.26498,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 5170kW/7.15COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.15,                    !- Minimum Part Load Ratio
    1.08,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.15,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.08 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.15 | Minimum part unload ratio | 
| Real | PLRMin | 0.15 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -5169500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.15 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.675697E-01,-1.191228E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.894383E-01,-2.926530E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.497273E-01,1.011288E-01,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_5208kW_6_88COP_VanesElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes,  !- Name
    5208200,                 !- Reference Capacity {W}
    6.88,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.18283,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.25293,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -5208200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.88 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.25293 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.563516E-01,-4.106264E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.198204E-01,-1.523340E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.334262E-01,3.926783E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_5465kW_6_94COP_VanesElectricEIRChiller York YK 5465kW/6.94COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 5465kW/6.94COP/Vanes,  !- Name
    5464900,                 !- Reference Capacity {W}
    6.94,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.18296,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.27444,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 5465kW/6.94COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.07 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.14 | Minimum part unload ratio | 
| Real | PLRMin | 0.14 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -5464900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.94 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.092441E-01,-1.225892E-01,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.396022E-01,-5.954060E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.795792E-01,7.872758E-02,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_5549kW_6_50COP_VanesElectricEIRChiller York YK 5549kW/6.50COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 5549kW/6.50COP/Vanes,  !- Name
    5549300,                 !- Reference Capacity {W}
    6.50,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.18296,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.27444,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 5549kW/6.50COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.05 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.14 | Minimum part unload ratio | 
| Real | PLRMin | 0.14 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -5549300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.50 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-1.402079E-01,1.836029E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.989980E-01,-8.246157E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.336623E-01,1.901320E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_VanesElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes,  !- Name
    5651300,                 !- Reference Capacity {W}
    5.50,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.18927,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.18927,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.19 | Minimum part unload ratio | 
| Real | PLRMin | 0.19 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -5651300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.50 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.18927 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.18927 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.299676E+00,1.790645E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.853207E-01,-1.652255E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.629327E-01,5.709336E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.DOE_2_Centrifugal_5_50COPDOE-2 Centrifugal/5.50COP
Chiller:Electric:EIR,
    DOE-2 Centrifugal/5.50COP,  !- Name
    Autosize,                !- Reference Capacity {W}
    5.5,                     !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.4,                    !- Reference Entering Condenser Fluid Temperature {C}
    Autosize,                !- Reference Chilled Water Flow Rate {m3/s}
    Autosize,                !- Reference Condenser Water Flow Rate {m3/s}
    DOE-2 Centrifugal/5.50COP CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    DOE-2 Centrifugal/5.50COP EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    DOE-2 Centrifugal/5.50COP EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.1,                     !- Minimum Part Load Ratio
    1.0,                     !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.2,                     !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow;            !- Chiller Flow Mode
    
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.0 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.2 | Minimum part unload ratio | 
| Real | PLRMin | 0.1 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.5 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0041 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {0.257896E+00,0.389016E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {0.933884E+00,-0.582120E-01,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {0.222903,0.313387,0.463710} | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Multistack_MS_172kW_3_67COP_NoneElectricEIRChiller Multistack MS 172kW/3.67COP/None
Chiller:Electric:EIR,
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None,  !- Name
    172300,                  !- Reference Capacity {W}
    3.67,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    18.33,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.00738,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.00959,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.40 | Minimum part unload ratio | 
| Real | PLRMin | 0.40 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -172300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 3.67 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.00738 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.00959 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.839419E-01,1.094957E-01,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.396181E-01,-5.754225E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {4.747786E-03,1.072374E+00,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.DOE_2_Reciprocating_3_67COPDOE-2 Reciprocating/3.67COP
Chiller:Electric:EIR,
    DOE-2 Reciprocating/3.67COP,  !- Name
    Autosize,                !- Reference Capacity {W}
    3.67,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.4,                    !- Reference Entering Condenser Fluid Temperature {C}
    Autosize,                !- Reference Chilled Water Flow Rate {m3/s}
    Autosize,                !- Reference Condenser Water Flow Rate {m3/s}
    DOE-2 Reciprocating/3.67COP CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    DOE-2 Reciprocating/3.67COP EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    DOE-2 Reciprocating/3.67COP EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.1,                     !- Minimum Part Load Ratio
    1.0,                     !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.2,                     !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow;            !- Chiller Flow Mode
    
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.0 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.2 | Minimum part unload ratio | 
| Real | PLRMin | 0.1 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 3.67 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0044 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {0.507883E+00,0.145228E+00,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {0.103076E+01,-0.103536E+00,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {0.088065,1.137742,-0.225806} | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTWA_383kW_4_17COP_ValveElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve,  !- Name
    383300,                  !- Reference Capacity {W}
    4.17,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0165,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.02063,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.25,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.25,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.25 | Minimum part unload ratio | 
| Real | PLRMin | 0.25 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -383300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 4.17 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0165 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.02063 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.830684E-01,3.676199E-02,5... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.228513E-01,-8.700783E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.295553E-02,9.114398E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_531kW_4_83COP_ValveElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve,  !- Name
    531000,                  !- Reference Capacity {W}
    4.83,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0135,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.01577,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -531000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 4.83 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0135 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.434012E-01,1.630729E-02,8... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.524778E-01,1.045156E-04,6... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.980020E-01,2.733157E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_538kW_5_12COP_ValveElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve,  !- Name
    538000,                  !- Reference Capacity {W}
    5.12,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01375,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01956,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -538000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.12 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01375 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.344780E-01,2.760000E-02,3... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.455087E-01,-9.301201E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.816950E-01,3.731838E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_542kW_5_26COP_ValveElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve,  !- Name
    541500,                  !- Reference Capacity {W}
    5.26,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    21.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01363,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01577,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -541500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.26 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01363 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.226438E-01,2.878831E-02,3... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.953775E-01,-1.359340E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.057645E-01,-1.548084E-01,... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_672kW_7_90COP_ValveElectricEIRChiller York YS 672kW/7.90COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 672kW/7.90COP/Valve,  !- Name
    671600,                  !- Reference Capacity {W}
    7.90,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    15.56,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01514,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0241,                  !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 672kW/7.90COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -671600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.90 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.274375E-01,2.846559E-02,4... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.069331E-01,-6.420922E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.936152E-01,3.375574E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_686kW_5_91COP_ValveElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve,  !- Name
    685700,                  !- Reference Capacity {W}
    5.91,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    23.74,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0571,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.03255,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -685700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.91 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03255 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {2.903523E-01,-2.676742E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.014060E-01,1.561000E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.113934E-01,4.190226E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_ValveElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve,  !- Name
    706800,                  !- Reference Capacity {W}
    7.77,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    15.56,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04921,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03268,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.28,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.28,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.28 | Minimum part unload ratio | 
| Real | PLRMin | 0.28 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -706800 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.77 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03268 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.362925E-01,2.940722E-02,5... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.497944E-01,6.883157E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.997099E-01,6.754676E-01,1... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 11.11 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_756kW_7_41COP_ValveElectricEIRChiller York YS 756kW/7.41COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 756kW/7.41COP/Valve,  !- Name
    756000,                  !- Reference Capacity {W}
    7.41,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    16.06,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 756kW/7.41COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.11,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.11,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.11 | Minimum part unload ratio | 
| Real | PLRMin | 0.11 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 16.06 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -756000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 7.41 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.432455E-01,2.794778E-02,2... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.917947E-01,-1.929936E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.929778E-01,1.673799E-02,6... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 16.06 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_781kW_5_42COP_ValveElectricEIRChiller York YS 781kW/5.42COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 781kW/5.42COP/Valve,  !- Name
    780700,                  !- Reference Capacity {W}
    5.42,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.01893,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03785,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 781kW/5.42COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -780700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.42 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.01893 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.002148E+00,3.300191E-02,3... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.475957E-01,-1.054652E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.519108E-01,2.756914E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_830kW_6_97COP_ValveElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve,  !- Name
    829900,                  !- Reference Capacity {W}
    6.97,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04744,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -829900 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.97 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.198506E-01,4.299516E-03,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.610959E-01,-1.560459E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.307464E-01,7.784162E-01,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 14.17 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_862kW_6_11COP_ValveElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve,  !- Name
    861500,                  !- Reference Capacity {W}
    6.11,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04296,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.11 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-3.646458E-02,-6.061334E-02... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.420642E-01,-2.110032E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.292819E-01,3.662723E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_862kW_6_84COP_ValveElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve,  !- Name
    861500,                  !- Reference Capacity {W}
    6.84,                    !- Reference COP {W/W}
    9.69,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04296,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.84 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 9.69 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {-4.535842E-02,-6.253871E-02... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.930611E-01,-2.082914E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.145826E-01,7.340475E-01,1... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_865kW_6_05COP_ValveElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve,  !- Name
    865100,                  !- Reference Capacity {W}
    6.05,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03716,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04366,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -865100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.05 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03716 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04366 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.079758E-01,-2.344768E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.437328E-01,7.625344E-03,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.545235E-01,3.104981E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_879kW_5_82COP_ValveElectricEIRChiller York YS 879kW/5.82COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 879kW/5.82COP/Valve,  !- Name
    879100,                  !- Reference Capacity {W}
    5.82,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03785,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 879kW/5.82COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -879100 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.82 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.031429E+00,3.364723E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.595308E-01,-1.087985E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.029493E-01,3.223124E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_1009kW_5_37COP_ValveElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve,  !- Name
    1009200,                 !- Reference Capacity {W}
    5.37,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    24.86,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04618,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 24.86 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1009200 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.37 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04618 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.134633E+00,3.267210E-02,5... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.383883E-01,7.754235E-03,6... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.316727E-01,1.013111E+00,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 19.97 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 24.86 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_ValveElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve,  !- Name
    1051400,                 !- Reference Capacity {W}
    5.05,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04527,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05659,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1051400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.05 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04527 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05659 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.482157E-01,3.306737E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {4.904181E-01,-5.530317E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.590465E-01,2.148987E-01,5... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_ValveElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve,  !- Name
    1062000,                 !- Reference Capacity {W}
    5.50,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04573,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05716,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1062000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.50 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04573 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05716 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.025695E+00,2.327484E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {2.634070E-01,-7.025220E-03,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {2.576261E-01,3.416910E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_1066kW_5_73COP_ValveElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve,  !- Name
    1065500,                 !- Reference Capacity {W}
    5.73,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    25.28,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05142,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04416,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.30 | Minimum part unload ratio | 
| Real | PLRMin | 0.30 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 25.28 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1065500 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.73 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.05142 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04416 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.062396E+00,4.575299E-02,2... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {9.003080E-01,3.783201E-03,9... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.007344E-01,1.119205E+00,-... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 20.07 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 25.28 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_1094kW_6_55COP_ValveElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve,  !- Name
    1093600,                 !- Reference Capacity {W}
    6.55,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.33,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04921,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04524,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.25,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.25,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.25 | Minimum part unload ratio | 
| Real | PLRMin | 0.25 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.33 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1093600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.55 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04524 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.643756E-01,3.820069E-02,4... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.579136E-01,-1.133448E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.626466E-01,7.903550E-01,4... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1108kW_6_92COP_ValveElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve,  !- Name
    1107700,                 !- Reference Capacity {W}
    6.92,                    !- Reference COP {W/W}
    8.97,                    !- Reference Leaving Chilled Water Temperature {C}
    23.74,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0571,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1107700 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.92 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 8.97 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {6.631328E-01,-1.027433E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.668296E-01,-2.800906E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.370745E-01,8.374817E-01,2... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_1171kW_9_15COP_ValveElectricEIRChiller York YS 1171kW/9.15COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 1171kW/9.15COP/Valve,  !- Name
    1171000,                 !- Reference Capacity {W}
    9.15,                    !- Reference COP {W/W}
    6.11,                    !- Reference Leaving Chilled Water Temperature {C}
    15.56,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03249,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05173,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 1171kW/9.15COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.09 | Minimum part unload ratio | 
| Real | PLRMin | 0.09 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1171000 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.15 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03249 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.299045E-01,2.350383E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.325834E-01,-2.611733E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.889392E-01,4.684305E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1196kW_6_39COP_ValveElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve,  !- Name
    1195600,                 !- Reference Capacity {W}
    6.39,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03653,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04271,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.03 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 6.39 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.03653 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.04271 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {5.775948E-01,2.206074E-02,-... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.077824E-01,-1.608447E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.061065E-01,7.305514E-01,1... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_1554kW_9_31COP_ValveElectricEIRChiller York YS 1554kW/9.31COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 1554kW/9.31COP/Valve,  !- Name
    1554300,                 !- Reference Capacity {W}
    9.31,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    15.56,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0424,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.07949,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 1554kW/9.31COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.02 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.10 | Minimum part unload ratio | 
| Real | PLRMin | 0.10 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1554300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 9.31 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.0424 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.07949 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {1.083027E+00,9.278069E-03,1... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {5.099117E-01,1.379553E-02,-... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {1.720219E-01,5.084848E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_1758kW_5_84COP_ValveElectricEIRChiller York YS 1758kW/5.84COP/Valve
Chiller:Electric:EIR,
    ElectricEIRChiller York YS 1758kW/5.84COP/Valve,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.84,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YS 1758kW/5.84COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.04 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.20 | Minimum part unload ratio | 
| Real | PLRMin | 0.20 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 5.84 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {8.130185E-01,-1.425368E-02,... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {6.381264E-01,6.304193E-03,9... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {3.149879E-01,3.171267E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] | 
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CGWD_207kW_3_99COP_NoneElectricEIRChiller Trane CGWD 207kW/3.99COP/None
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CGWD 207kW/3.99COP/None,  !- Name
    207400,                  !- Reference Capacity {W}
    3.99,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.00898,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01122,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CGWD 207kW/3.99COP/None CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.25,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.25,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | PLRMax | 1.01 | Maximum part load ratio | 
| Real | PLRMinUnl | 0.25 | Minimum part unload ratio | 
| Real | PLRMin | 0.25 | Minimum part load ratio | 
| Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant | 
| Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] | 
| Nominal condition | |||
| HeatFlowRate | QEva_flow_nominal | -207400 | Reference capacity (negative number) [W] | 
| Real | COP_nominal | 3.99 | Reference coefficient of performance | 
| MassFlowRate | mEva_flow_nominal | 1000*0.00898 | Nominal mass flow at evaporator [kg/s] | 
| MassFlowRate | mCon_flow_nominal | 1000*0.01122 | Nominal mass flow at condenser [kg/s] | 
| Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] | 
| Performance curves | |||
| Real | capFunT[nCapFunT] | {9.441897E-01,3.371079E-02,9... | Biquadratic coefficients for capFunT | 
| Real | EIRFunT[nEIRFunT] | {7.273870E-01,-1.189276E-02,... | Biquadratic coefficients for EIRFunT | 
| Real | EIRFunPLR[nEIRFunPLR] | {4.146742E-02,6.543795E-01,3... | Coefficients for EIRFunPLR | 
| Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] | 
| Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] | 
| Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] | 
| Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |