Performance data for chiller ElectricEIR
Information
Package with performance data for chillers.
Package Content
Generic data record for chiller ElectricEIR
Information
This record is used as a template for performance data
for the chiller model
Buildings.Fluid.Chillers.ElectricEIR.
Extends from Buildings.Fluid.Chillers.Data.BaseClasses.Chiller (Base classes for chiller models).
Parameters
Type | Name | Default | Description |
Real | PLRMax | | Maximum part load ratio |
Real | PLRMinUnl | | Minimum part unload ratio |
Real | PLRMin | | Minimum part load ratio |
Real | etaMotor | | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | | Reference capacity (negative number) [W] |
Real | COP_nominal | | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Integer | nCapFunT | 6 | Number of coefficients for capFunT |
Integer | nEIRFunT | 6 | Number of coefficients for capFunT |
Integer | nEIRFunPLR | 3 | Number of coefficients for capFunT |
Real | capFunT[nCapFunT] | | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | | Maximum value for entering condenser temperature [K] |
Modelica definition
record Generic "Generic data record for chiller ElectricEIR"
extends Buildings.Fluid.Chillers.Data.BaseClasses.Chiller(
final nCapFunT=6,
final nEIRFunT=6,
final nEIRFunPLR=3);
parameter Modelica.SIunits.Temperature TConEnt_nominal
"Temperature of fluid entering condenser at nominal condition";
parameter Modelica.SIunits.Temperature TConEntMin
"Minimum value for entering condenser temperature";
parameter Modelica.SIunits.Temperature TConEntMax
"Maximum value for entering condenser temperature";
end Generic;
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes, !- Name
471200, !- Reference Capacity {W}
5.89, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.01035, !- Reference Chilled Water Flow Rate {m3/s}
0.01924, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.15, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.15 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -471200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01035 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01924 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.521130E-01,1.324053E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.475238E-01,-2.588210E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.778889E-01,2.338363E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_WSC_471kW_5_89COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -471200,
COP_nominal = 5.89,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.15,
mEva_flow_nominal = 1000 * 0.01035,
mCon_flow_nominal = 1000 * 0.01924,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {2.521130E-01,1.324053E-02,-8.637329E-03,8.581056E-02,-4.261176E-03,8.661899E-03},
EIRFunT = {4.475238E-01,-2.588210E-02,-1.459053E-03,4.342595E-02,-1.000651E-03,1.920106E-03},
EIRFunPLR = {2.778889E-01,2.338363E-01,4.883748E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes";
ElectricEIRChiller York YT 563kW/10.61COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 563kW/10.61COP/Vanes, !- Name
562600, !- Reference Capacity {W}
10.61, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.01514, !- Reference Chilled Water Flow Rate {m3/s}
0.0241, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 563kW/10.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -562600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-1.288612E-01,-8.919540E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-5.781003E-01,-1.169130E-01... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.203969E-01,-7.775900E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_563kW_10_61COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -562600,
COP_nominal = 10.61,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.01514,
mCon_flow_nominal = 1000 * 0.0241,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {-1.288612E-01,-8.919540E-02,-2.190195E-03,1.538357E-01,-5.129402E-03,7.813636E-03},
EIRFunT = {-5.781003E-01,-1.169130E-01,-4.760535E-03,2.230082E-01,-5.313649E-03,6.846644E-03},
EIRFunPLR = {5.203969E-01,-7.775900E-01,1.255394E+00},
etaMotor = 1.0)
"ElectricEIRChiller York YT 563kW/10.61COP/Vanes";
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes, !- Name
703300, !- Reference Capacity {W}
7.03, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.02019, !- Reference Chilled Water Flow Rate {m3/s}
0.02902, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -703300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02019 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02902 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.779439E-01,1.073486E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.234029E-01,-1.171542E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.864389E-01,-2.522595E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -703300,
COP_nominal = 7.03,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.02019,
mCon_flow_nominal = 1000 * 0.02902,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {4.779439E-01,1.073486E-01,-1.055896E-02,4.208433E-02,-2.346870E-03,4.019632E-03},
EIRFunT = {8.234029E-01,-1.171542E-01,5.869351E-04,2.964642E-02,-9.190377E-04,5.035796E-03},
EIRFunPLR = {3.864389E-01,-2.522595E-01,8.672354E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes";
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes, !- Name
724400, !- Reference Capacity {W}
6.04, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
21.11, !- Reference Entering Condenser Fluid Temperature {C}
0.01779, !- Reference Chilled Water Flow Rate {m3/s}
0.01956, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -724400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.418712E-01,-8.384251E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.059102E-01,-1.621557E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.879418E-01,3.562862E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 13.75 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -724400,
COP_nominal = 6.04,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.01779,
mCon_flow_nominal = 1000 * 0.01956,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 21.11,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 13.75,
TConEntMax = 273.15 + 23.89,
capFunT = {4.418712E-01,-8.384251E-02,-2.190707E-03,8.594633E-02,-3.322575E-03,6.652189E-03},
EIRFunT = {5.059102E-01,-1.621557E-02,3.346388E-04,2.350906E-02,3.514201E-04,-6.342981E-04},
EIRFunPLR = {1.879418E-01,3.562862E-01,4.540392E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes";
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD, !- Name
742000, !- Reference Capacity {W}
5.42, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
21.11, !- Reference Entering Condenser Fluid Temperature {C}
0.01779, !- Reference Chilled Water Flow Rate {m3/s}
0.01956, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -742000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.797101E-01,-2.895701E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.946139E-01,-4.829399E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.202277E-01,1.396384E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_742kW_5_42COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -742000,
COP_nominal = 5.42,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.01779,
mCon_flow_nominal = 1000 * 0.01956,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 21.11,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 11.25,
TConEntMax = 273.15 + 23.89,
capFunT = {9.797101E-01,-2.895701E-03,-8.970718E-04,1.031440E-02,-7.431651E-04,1.453508E-03},
EIRFunT = {9.946139E-01,-4.829399E-02,4.674277E-04,-1.158726E-03,5.762583E-04,2.148192E-04},
EIRFunPLR = {1.202277E-01,1.396384E-01,7.394038E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD";
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes, !- Name
815800, !- Reference Capacity {W}
6.74, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.01748, !- Reference Chilled Water Flow Rate {m3/s}
0.04164, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -815800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.74 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01748 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04164 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.862590E-01,5.799373E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.335321E-01,4.465107E-04,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.070136E-01,8.654874E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_WSC_816kW_6_74COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -815800,
COP_nominal = 6.74,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.01748,
mCon_flow_nominal = 1000 * 0.04164,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {9.862590E-01,5.799373E-02,-5.355626E-03,-8.941705E-04,-1.670098E-03,4.733054E-03},
EIRFunT = {7.335321E-01,4.465107E-04,-3.448575E-03,3.770822E-03,-2.189675E-04,2.400267E-03},
EIRFunPLR = {3.070136E-01,8.654874E-02,6.081551E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes";
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes, !- Name
819300, !- Reference Capacity {W}
8.11, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.02524, !- Reference Chilled Water Flow Rate {m3/s}
0.03785, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -819300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02524 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.392673E-01,4.328784E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.925176E-01,-1.908391E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.830681E-01,2.254147E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_819kW_8_11COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -819300,
COP_nominal = 8.11,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.02524,
mCon_flow_nominal = 1000 * 0.03785,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.392673E-01,4.328784E-02,-4.529446E-03,1.525410E-02,-1.141458E-03,2.651124E-03},
EIRFunT = {5.925176E-01,-1.908391E-02,-1.852692E-03,4.051551E-02,-2.908719E-04,1.059047E-03},
EIRFunPLR = {2.830681E-01,2.254147E-01,4.916649E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes";
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes, !- Name
822900, !- Reference Capacity {W}
6.28, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.03186, !- Reference Chilled Water Flow Rate {m3/s}
0.04744, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -822900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.573150E-01,8.714616E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.029134E-01,2.171359E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.965419E-01,4.689744E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -822900,
COP_nominal = 6.28,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03186,
mCon_flow_nominal = 1000 * 0.04744,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {5.573150E-01,8.714616E-02,-2.917582E-03,2.500000E-02,-8.861538E-04,-3.184615E-04},
EIRFunT = {8.029134E-01,2.171359E-02,2.388123E-04,-1.096173E-02,1.065277E-03,-2.057538E-03},
EIRFunPLR = {2.965419E-01,4.689744E-01,2.332341E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes";
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD, !- Name
868600, !- Reference Capacity {W}
5.57, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.01754, !- Reference Chilled Water Flow Rate {m3/s}
0.02593, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -868600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01754 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02593 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.406799E-01,1.253709E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.943721E-01,1.079147E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.501042E-01,-6.804336E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_869kW_5_57COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -868600,
COP_nominal = 5.57,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.01754,
mCon_flow_nominal = 1000 * 0.02593,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {5.406799E-01,1.253709E-01,-8.025360E-03,-7.357554E-03,-4.477789E-04,2.140733E-03},
EIRFunT = {3.943721E-01,1.079147E-01,-8.912223E-03,-3.229487E-04,1.302402E-05,1.561862E-03},
EIRFunPLR = {1.501042E-01,-6.804336E-02,9.171460E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD";
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD, !- Name
896700, !- Reference Capacity {W}
7.23, !- Reference COP {W/W}
9.82, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.0436, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0436 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.559679E-01,7.630860E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.511011E-01,4.948557E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.036380E-01,-3.913200E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_897kW_7_23COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -896700,
COP_nominal = 7.23,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.0436,
TEvaLvg_nominal = 273.15 + 9.82,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {5.559679E-01,7.630860E-02,-1.431181E-03,2.167593E-02,-6.233447E-04,-9.876498E-04},
EIRFunT = {6.511011E-01,4.948557E-02,-8.152733E-04,2.322946E-02,1.990802E-04,-2.669401E-03},
EIRFunPLR = {2.036380E-01,-3.913200E-01,1.187172E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD";
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes, !- Name
896700, !- Reference Capacity {W}
6.50, !- Reference COP {W/W}
9.82, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.04423, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04423 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.009156E-01,2.151274E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.527749E-01,-4.336881E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.323416E-01,2.561103E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_897kW_6_50COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -896700,
COP_nominal = 6.50,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.04423,
TEvaLvg_nominal = 273.15 + 9.82,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {7.009156E-01,2.151274E-02,-6.029650E-04,1.864266E-02,-1.084545E-03,1.418575E-03},
EIRFunT = {8.527749E-01,-4.336881E-03,8.972177E-04,-1.888039E-03,8.648075E-04,-1.438797E-03},
EIRFunPLR = {3.323416E-01,2.561103E-01,4.106954E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes";
ElectricEIRChiller York YT 897kW/7.60COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 897kW/7.60COP/VSD, !- Name
896700, !- Reference Capacity {W}
7.60, !- Reference COP {W/W}
9.83, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 897kW/7.60COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.83 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.699948E-01,2.961470E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.526128E-01,3.299472E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.708628E-02,7.070062E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_897kW_7_60COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -896700,
COP_nominal = 7.60,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 9.83,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {5.699948E-01,2.961470E-02,-1.064930E-03,3.062313E-02,-1.753205E-03,2.142105E-03},
EIRFunT = {5.526128E-01,3.299472E-03,-7.981925E-04,4.245710E-02,-3.533658E-04,-9.415137E-04},
EIRFunPLR = {4.708628E-02,7.070062E-02,8.802198E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 897kW/7.60COP/VSD";
ElectricEIRChiller York YT 897kW/6.27COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 897kW/6.27COP/VSD, !- Name
896700, !- Reference Capacity {W}
6.27, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 897kW/6.27COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.197991E-01,1.568955E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.530767E-01,-5.683068E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.836320E-02,-1.638320E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_897kW_6_27COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -896700,
COP_nominal = 6.27,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.197991E-01,1.568955E-01,-4.426242E-03,3.449640E-02,-8.163597E-04,-2.236230E-03},
EIRFunT = {5.530767E-01,-5.683068E-02,4.423475E-03,6.472411E-02,-7.378933E-04,-2.491202E-03},
EIRFunPLR = {9.836320E-02,-1.638320E-02,9.127289E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 897kW/6.27COP/VSD";
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD, !- Name
896700, !- Reference Capacity {W}
6.23, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.04442, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04442 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.862185E-01,3.144947E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.606461E-01,-1.202294E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.075556E-01,-2.126466E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_897kW_6_23COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -896700,
COP_nominal = 6.23,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.04442,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {8.862185E-01,3.144947E-02,2.328997E-04,1.339712E-03,-2.923430E-04,2.320709E-04},
EIRFunT = {8.606461E-01,-1.202294E-03,9.398625E-04,2.983262E-03,4.119228E-04,-1.123884E-03},
EIRFunPLR = {2.075556E-01,-2.126466E-01,1.004182E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD";
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes, !- Name
931900, !- Reference Capacity {W}
5.09, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.03785, !- Reference Chilled Water Flow Rate {m3/s}
0.04732, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -931900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.182278E+00,3.259490E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.053491E-01,-1.089778E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.823245E-02,6.672421E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -931900,
COP_nominal = 5.09,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03785,
mCon_flow_nominal = 1000 * 0.04732,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 3.33,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {1.182278E+00,3.259490E-02,-3.904288E-03,4.579721E-03,-1.028178E-03,2.855063E-03},
EIRFunT = {6.053491E-01,-1.089778E-02,-1.511327E-03,1.902687E-02,-1.910750E-04,9.008184E-04},
EIRFunPLR = {6.823245E-02,6.672421E-01,2.654211E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes";
ElectricEIRChiller York YT 960kW/4.64COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 960kW/4.64COP/Vanes, !- Name
960000, !- Reference Capacity {W}
4.64, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.03785, !- Reference Chilled Water Flow Rate {m3/s}
0.04732, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 960kW/4.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.09, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.09 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -960000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-2.278537E-01,4.055945E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.735924E-01,2.270414E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.737941E-01,3.141127E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_960kW_4_64COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -960000,
COP_nominal = 4.64,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.09,
mEva_flow_nominal = 1000 * 0.03785,
mCon_flow_nominal = 1000 * 0.04732,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 3.33,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {-2.278537E-01,4.055945E-01,-3.246694E-02,3.788230E-03,-2.236584E-04,6.715520E-04},
EIRFunT = {5.735924E-01,2.270414E-02,-3.331832E-03,6.025574E-03,3.245033E-04,3.229690E-05},
EIRFunPLR = {2.737941E-01,3.141127E-01,4.113671E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 960kW/4.64COP/Vanes";
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes, !- Name
1023300, !- Reference Capacity {W}
5.81, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.02366, !- Reference Chilled Water Flow Rate {m3/s}
0.04732, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1023300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.571195E-01,-1.571421E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.254964E-01,-1.972389E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.368399E-01,3.286421E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1023kW_5_81COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1023300,
COP_nominal = 5.81,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.02366,
mCon_flow_nominal = 1000 * 0.04732,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {2.571195E-01,-1.571421E-02,-3.041761E-03,8.106512E-02,-2.568598E-03,4.247073E-03},
EIRFunT = {5.254964E-01,-1.972389E-02,3.441072E-04,1.651466E-02,2.005198E-04,-3.193246E-04},
EIRFunPLR = {2.368399E-01,3.286421E-01,4.344939E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1023kW/5.81COP/Vanes";
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes, !- Name
1030300, !- Reference Capacity {W}
8.58, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.02378, !- Reference Chilled Water Flow Rate {m3/s}
0.03407, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.08, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.08, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1030300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02378 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03407 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.736028E-01,5.571395E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.125878E-01,1.388940E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.215320E-01,-9.188416E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_1030kW_8_58COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1030300,
COP_nominal = 8.58,
PLRMin = 0.08,
PLRMinUnl = 0.08,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.02378,
mCon_flow_nominal = 1000 * 0.03407,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {7.736028E-01,5.571395E-02,-3.058312E-03,-1.789007E-04,-9.808878E-04,2.123462E-03},
EIRFunT = {7.125878E-01,1.388940E-02,-2.473407E-03,2.096719E-02,-1.566098E-04,6.035460E-04},
EIRFunPLR = {3.215320E-01,-9.188416E-03,6.881582E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes";
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes, !- Name
1047900, !- Reference Capacity {W}
6.06, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.04542, !- Reference Chilled Water Flow Rate {m3/s}
0.05678, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1047900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.06 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04542 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.238221E-01,1.747548E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.255594E-01,-3.502968E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.543796E-01,7.276121E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1048kW_6_06COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1047900,
COP_nominal = 6.06,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.04542,
mCon_flow_nominal = 1000 * 0.05678,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 35.00,
capFunT = {7.238221E-01,1.747548E-02,-4.524718E-03,2.138468E-02,-9.342801E-04,2.515069E-03},
EIRFunT = {7.255594E-01,-3.502968E-02,2.213476E-03,3.925410E-03,5.538176E-04,-8.638012E-04},
EIRFunPLR = {1.543796E-01,7.276121E-01,1.162393E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1048kW/6.06COP/Vanes";
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes, !- Name
1055000, !- Reference Capacity {W}
5.96, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.02839, !- Reference Chilled Water Flow Rate {m3/s}
0.05678, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1055000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02839 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.785912E-01,-5.900023E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.245110E-01,-2.850126E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.619878E-01,2.393605E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1055kW_5_96COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1055000,
COP_nominal = 5.96,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.02839,
mCon_flow_nominal = 1000 * 0.05678,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {1.785912E-01,-5.900023E-02,-5.946963E-04,9.297889E-02,-2.841024E-03,4.974221E-03},
EIRFunT = {5.245110E-01,-2.850126E-02,8.034720E-04,1.893133E-02,1.151629E-04,-9.340642E-05},
EIRFunPLR = {2.619878E-01,2.393605E-01,4.988306E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1055kW/5.96COP/Vanes";
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes, !- Name
1076100, !- Reference Capacity {W}
5.52, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.89, !- Reference Entering Condenser Fluid Temperature {C}
0.03186, !- Reference Chilled Water Flow Rate {m3/s}
0.04744, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1076100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.52 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.187704E-01,4.509452E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.511044E-01,2.415573E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.315760E-01,-3.004087E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1076kW_5_52COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1076100,
COP_nominal = 5.52,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03186,
mCon_flow_nominal = 1000 * 0.04744,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.89,
capFunT = {9.187704E-01,4.509452E-02,-5.119187E-03,-2.095629E-04,-6.432511E-04,2.791545E-03},
EIRFunT = {7.511044E-01,2.415573E-02,-5.310959E-03,-1.073812E-03,1.189538E-04,1.604476E-03},
EIRFunPLR = {1.315760E-01,-3.004087E-02,8.967180E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes";
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes, !- Name
1079600, !- Reference Capacity {W}
7.39, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.61, !- Reference Entering Condenser Fluid Temperature {C}
0.03186, !- Reference Chilled Water Flow Rate {m3/s}
0.06416, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.61 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1079600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.365583E-01,-3.677215E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.608716E-01,-5.637178E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.789841E-01,2.976513E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 16.24 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.61 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1080kW_7_39COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1079600,
COP_nominal = 7.39,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.03186,
mCon_flow_nominal = 1000 * 0.06416,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.61,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 16.24,
TConEntMax = 273.15 + 23.61,
capFunT = {4.365583E-01,-3.677215E-02,-2.779781E-03,6.063060E-02,-2.290704E-03,5.115883E-03},
EIRFunT = {3.608716E-01,-5.637178E-02,-3.428415E-04,4.230087E-02,-4.391632E-04,1.517182E-03},
EIRFunPLR = {1.789841E-01,2.976513E-01,5.243235E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes";
ElectricEIRChiller York YT 1090kW/7.57COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1090kW/7.57COP/VSD, !- Name
1090100, !- Reference Capacity {W}
7.57, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1090kW/7.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.14, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.14, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1090100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.769028E-01,5.711844E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.241019E-01,-4.961574E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.431969E-01,-4.920686E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1090kW_7_57COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1090100,
COP_nominal = 7.57,
PLRMin = 0.14,
PLRMinUnl = 0.14,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {6.769028E-01,5.711844E-02,-6.072310E-04,1.656541E-02,-8.087831E-04,2.303904E-04},
EIRFunT = {9.241019E-01,-4.961574E-02,1.291675E-04,3.299013E-02,-6.769477E-04,1.692815E-03},
EIRFunPLR = {1.431969E-01,-4.920686E-01,1.341333E+00},
etaMotor = 1.0) "ElectricEIRChiller York YT 1090kW/7.57COP/VSD";
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes, !- Name
1104200, !- Reference Capacity {W}
8.00, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.02423, !- Reference Chilled Water Flow Rate {m3/s}
0.03028, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.08, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.08, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1104200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02423 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03028 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.210185E-01,4.386152E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.655242E-01,-3.808337E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.091150E-01,-1.089639E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1104200,
COP_nominal = 8.00,
PLRMin = 0.08,
PLRMinUnl = 0.08,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.02423,
mCon_flow_nominal = 1000 * 0.03028,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {8.210185E-01,4.386152E-02,-1.521829E-03,-4.314921E-03,-7.251667E-04,1.497681E-03},
EIRFunT = {8.655242E-01,-3.808337E-04,-1.320050E-03,1.137834E-02,-4.095120E-05,6.531102E-04},
EIRFunPLR = {3.091150E-01,-1.089639E-02,7.022967E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes";
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes, !- Name
1125300, !- Reference Capacity {W}
4.89, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.02776, !- Reference Chilled Water Flow Rate {m3/s}
0.02618, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.151549E-01,-1.181250E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.810580E-01,-4.344257E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.807198E-01,-1.469686E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1125300,
COP_nominal = 4.89,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.02776,
mCon_flow_nominal = 1000 * 0.02618,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {6.151549E-01,-1.181250E-02,-1.491630E-03,3.326625E-02,-9.315000E-04,1.771875E-03},
EIRFunT = {5.810580E-01,-4.344257E-02,-5.369108E-04,2.844405E-02,-1.609390E-04,7.004346E-04},
EIRFunPLR = {1.807198E-01,-1.469686E-01,9.658417E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes";
ElectricEIRChiller York YT 1125kW/7.92COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1125kW/7.92COP/VSD, !- Name
1125300, !- Reference Capacity {W}
7.92, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03243, !- Reference Chilled Water Flow Rate {m3/s}
0.05173, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1125kW/7.92COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.034212E-01,2.327078E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.542286E-01,-2.451604E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.147453E-01,4.231235E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1125kW_7_92COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1125300,
COP_nominal = 7.92,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03243,
mCon_flow_nominal = 1000 * 0.05173,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.034212E-01,2.327078E-03,-9.117035E-04,9.104793E-02,-2.678967E-03,2.274649E-03},
EIRFunT = {6.542286E-01,-2.451604E-02,1.253508E-03,4.216477E-02,1.404867E-04,-1.508780E-03},
EIRFunPLR = {1.147453E-01,4.231235E-02,8.419681E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1125kW/7.92COP/VSD";
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes, !- Name
1128800, !- Reference Capacity {W}
7.19, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.02776, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.15, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.15, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1128800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.19 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.922479E-01,-4.388411E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.742142E-01,-5.536709E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.693841E-01,2.475201E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1129kW_7_19COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1128800,
COP_nominal = 7.19,
PLRMin = 0.15,
PLRMinUnl = 0.15,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.02776,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {3.922479E-01,-4.388411E-02,-2.748665E-03,6.894954E-02,-2.563738E-03,5.420187E-03},
EIRFunT = {3.742142E-01,-5.536709E-02,-8.199663E-04,4.655032E-02,-7.312591E-04,1.887184E-03},
EIRFunPLR = {1.693841E-01,2.475201E-01,5.836059E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes";
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD, !- Name
1142900, !- Reference Capacity {W}
6.57, !- Reference COP {W/W}
10.00, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.02593, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1142900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 10.00 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.939538E-01,4.096493E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.475580E-01,-1.187942E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.408822E-01,-1.578153E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1143kW_6_57COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1142900,
COP_nominal = 6.57,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.02593,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 10.00,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {7.939538E-01,4.096493E-02,-1.419397E-03,-1.639813E-03,-5.220497E-04,1.348786E-03},
EIRFunT = {9.475580E-01,-1.187942E-02,8.799326E-05,2.250775E-04,1.815775E-04,2.178409E-04},
EIRFunPLR = {1.408822E-01,-1.578153E-01,1.014316E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD";
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD, !- Name
1156900, !- Reference Capacity {W}
5.62, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
21.11, !- Reference Entering Condenser Fluid Temperature {C}
0.02801, !- Reference Chilled Water Flow Rate {m3/s}
0.03186, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1156900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.62 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02801 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03186 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.076248E+00,5.436724E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.075567E+00,-3.893571E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.608589E-01,-2.058215E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1156900,
COP_nominal = 5.62,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.02801,
mCon_flow_nominal = 1000 * 0.03186,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 21.11,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 11.25,
TConEntMax = 273.15 + 23.89,
capFunT = {1.076248E+00,5.436724E-03,-3.893302E-04,-4.353310E-03,-2.402031E-04,8.409080E-04},
EIRFunT = {1.075567E+00,-3.893571E-02,1.082499E-03,-5.782829E-03,6.574492E-04,-5.302886E-04},
EIRFunPLR = {1.608589E-01,-2.058215E-01,1.043133E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD";
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes, !- Name
1195600, !- Reference Capacity {W}
6.50, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.03426, !- Reference Chilled Water Flow Rate {m3/s}
0.04252, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.126801E+00,-4.220591E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.514432E-01,-2.252147E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.724491E-01,2.710369E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1196kW_6_50COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1195600,
COP_nominal = 6.50,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03426,
mCon_flow_nominal = 1000 * 0.04252,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.126801E+00,-4.220591E-03,-2.002964E-03,7.360880E-03,-1.156890E-03,3.064875E-03},
EIRFunT = {9.514432E-01,-2.252147E-02,-1.062456E-05,-1.383194E-04,3.914644E-04,8.126485E-05},
EIRFunPLR = {2.724491E-01,2.710369E-01,4.552356E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes";
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes, !- Name
1213200, !- Reference Capacity {W}
7.78, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03243, !- Reference Chilled Water Flow Rate {m3/s}
0.04782, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.17, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.17, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1213200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04782 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.070437E-01,-7.437456E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.002142E+00,-2.505239E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.847744E-01,4.027863E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1213kW_7_78COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1213200,
COP_nominal = 7.78,
PLRMin = 0.17,
PLRMinUnl = 0.17,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03243,
mCon_flow_nominal = 1000 * 0.04782,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {9.070437E-01,-7.437456E-03,-9.695325E-04,1.529092E-02,-1.069664E-03,1.994583E-03},
EIRFunT = {1.002142E+00,-2.505239E-02,5.169707E-04,6.321862E-03,5.116807E-04,-4.794244E-04},
EIRFunPLR = {2.847744E-01,4.027863E-01,3.114896E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes";
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes, !- Name
1230800, !- Reference Capacity {W}
6.18, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03533, !- Reference Chilled Water Flow Rate {m3/s}
0.0511, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1230800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0511 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.152795E+00,9.770474E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.067591E-01,1.868314E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.117054E-01,4.263662E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_1231kW_6_18COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1230800,
COP_nominal = 6.18,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03533,
mCon_flow_nominal = 1000 * 0.0511,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.152795E+00,9.770474E-02,-6.719705E-03,-2.123401E-02,-3.641998E-04,1.473439E-03},
EIRFunT = {8.067591E-01,1.868314E-02,-5.569088E-03,-4.309148E-03,1.373034E-04,2.394081E-03},
EIRFunPLR = {2.117054E-01,4.263662E-01,3.614654E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes";
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD, !- Name
1234300, !- Reference Capacity {W}
5.39, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.02593, !- Reference Chilled Water Flow Rate {m3/s}
0.03861, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1234300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.905815E-01,1.190927E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.771659E-01,1.144965E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.495681E-01,-1.449639E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1234kW_5_39COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1234300,
COP_nominal = 5.39,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.02593,
mCon_flow_nominal = 1000 * 0.03861,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {5.905815E-01,1.190927E-01,-6.727309E-03,-9.580836E-03,-3.034704E-04,1.540686E-03},
EIRFunT = {3.771659E-01,1.144965E-01,-8.186893E-03,-3.372584E-03,1.689440E-04,1.008523E-03},
EIRFunPLR = {1.495681E-01,-1.449639E-01,9.941070E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD";
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes, !- Name
1258900, !- Reference Capacity {W}
6.26, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.02593, !- Reference Chilled Water Flow Rate {m3/s}
0.03823, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03823 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.082071E+00,3.200888E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.582035E-01,6.896017E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.226232E-01,5.199282E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1258900,
COP_nominal = 6.26,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.02593,
mCon_flow_nominal = 1000 * 0.03823,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {1.082071E+00,3.200888E-02,-3.994780E-03,-5.789604E-03,-8.238938E-04,2.933539E-03},
EIRFunT = {7.582035E-01,6.896017E-03,-1.491911E-03,2.249459E-03,3.908697E-04,-1.735265E-04},
EIRFunPLR = {2.226232E-01,5.199282E-01,2.578470E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes";
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes, !- Name
1258900, !- Reference Capacity {W}
6.45, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.02631, !- Reference Chilled Water Flow Rate {m3/s}
0.06246, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.45 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02631 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06246 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.609200E-01,7.223733E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.991536E-01,6.305932E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.014593E-01,6.216537E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_1259kW_6_45COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1258900,
COP_nominal = 6.45,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.02631,
mCon_flow_nominal = 1000 * 0.06246,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {9.609200E-01,7.223733E-02,-1.693471E-03,2.543722E-03,-6.415570E-04,-3.028540E-04},
EIRFunT = {8.991536E-01,6.305932E-03,-3.756374E-04,-1.952076E-02,1.381302E-03,-1.615004E-03},
EIRFunPLR = {1.014593E-01,6.216537E-01,2.780213E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 1259kW/6.45COP/Vanes";
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes, !- Name
1266000, !- Reference Capacity {W}
4.39, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
35.00, !- Reference Entering Condenser Fluid Temperature {C}
0.03533, !- Reference Chilled Water Flow Rate {m3/s}
0.05773, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.11, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.11, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 35.00 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1266000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05773 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.285663E-01,-2.860032E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.284925E-02,4.206167E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.326942E-01,-7.962527E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1266kW_4_39COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1266000,
COP_nominal = 4.39,
PLRMin = 0.11,
PLRMinUnl = 0.11,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.03533,
mCon_flow_nominal = 1000 * 0.05773,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 35.00,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {1.285663E-01,-2.860032E-02,-1.369319E-03,6.676366E-02,-1.510647E-03,2.947167E-03},
EIRFunT = {8.284925E-02,4.206167E-02,-5.254555E-03,1.964407E-02,1.070646E-04,2.298241E-04},
EIRFunPLR = {7.326942E-01,-7.962527E-01,1.059148E+00},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1266kW/4.39COP/Vanes";
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes, !- Name
1283500, !- Reference Capacity {W}
6.20, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03684, !- Reference Chilled Water Flow Rate {m3/s}
0.05337, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1283500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.20 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.119245E+00,-1.524417E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.815645E-01,-2.448971E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.324812E-01,7.690691E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1284kW_6_20COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1283500,
COP_nominal = 6.20,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03684,
mCon_flow_nominal = 1000 * 0.05337,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.119245E+00,-1.524417E-02,-1.074186E-03,-1.260169E-03,-4.380237E-04,2.027779E-03},
EIRFunT = {7.815645E-01,-2.448971E-02,1.644370E-03,5.564580E-03,5.800428E-04,-1.086993E-03},
EIRFunPLR = {2.324812E-01,7.690691E-01,-6.532223E-04},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes";
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes, !- Name
1294100, !- Reference Capacity {W}
7.61, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03243, !- Reference Chilled Water Flow Rate {m3/s}
0.04732, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.16, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.16, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1294100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.274222E-01,1.278683E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.085249E+00,-9.441252E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.344563E-02,3.993002E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1294kW_7_61COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1294100,
COP_nominal = 7.61,
PLRMin = 0.16,
PLRMinUnl = 0.16,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03243,
mCon_flow_nominal = 1000 * 0.04732,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {9.274222E-01,1.278683E-02,-1.621880E-03,2.816339E-03,-7.658105E-04,1.881968E-03},
EIRFunT = {1.085249E+00,-9.441252E-04,-2.505100E-03,-8.724367E-03,4.164780E-04,8.473746E-04},
EIRFunPLR = {9.344563E-02,3.993002E-01,5.087169E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes";
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes, !- Name
1329300, !- Reference Capacity {W}
5.38, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.04732, !- Reference Chilled Water Flow Rate {m3/s}
0.07098, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.29, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.29, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.29 | Minimum part unload ratio |
Real | PLRMin | 0.29 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1329300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.38 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04732 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07098 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.339754E-01,1.016009E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.074052E-01,3.355495E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.079777E-02,1.174456E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1329300,
COP_nominal = 5.38,
PLRMin = 0.29,
PLRMinUnl = 0.29,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.04732,
mCon_flow_nominal = 1000 * 0.07098,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 21.11,
TConEntMax = 273.15 + 29.44,
capFunT = {5.339754E-01,1.016009E-01,-3.979592E-03,1.261254E-02,-4.666667E-04,-8.351648E-05},
EIRFunT = {8.074052E-01,3.355495E-02,-1.549617E-03,-7.142554E-03,5.056363E-04,-7.547786E-04},
EIRFunPLR = {4.079777E-02,1.174456E+00,-2.212711E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes";
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD, !- Name
1350400, !- Reference Capacity {W}
7.90, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03684, !- Reference Chilled Water Flow Rate {m3/s}
0.05337, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1350400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.063866E+00,-1.448990E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.953536E-01,-3.118863E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.336374E-01,-4.098166E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1350kW_7_90COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1350400,
COP_nominal = 7.90,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03684,
mCon_flow_nominal = 1000 * 0.05337,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.063866E+00,-1.448990E-02,-1.021036E-03,-1.197817E-03,-4.163507E-04,1.927446E-03},
EIRFunT = {9.953536E-01,-3.118863E-02,2.094171E-03,7.086716E-03,7.387078E-04,-1.384330E-03},
EIRFunPLR = {3.336374E-01,-4.098166E-01,1.077791E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD";
ElectricEIRChiller York YT 1368kW/7.35COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1368kW/7.35COP/VSD, !- Name
1367900, !- Reference Capacity {W}
7.35, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.07571, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1368kW/7.35COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1367900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.832184E-01,-3.265439E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.227543E-01,-1.415418E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.483562E-02,1.521114E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1368kW_7_35COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1367900,
COP_nominal = 7.35,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.07571,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {3.832184E-01,-3.265439E-02,-3.392654E-03,8.580180E-02,-3.513013E-03,6.528440E-03},
EIRFunT = {3.227543E-01,-1.415418E-02,-5.090650E-03,4.606511E-02,-8.769578E-04,2.600343E-03},
EIRFunPLR = {9.483562E-02,1.521114E-01,7.543027E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1368kW/7.35COP/VSD";
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes, !- Name
1371500, !- Reference Capacity {W}
7.49, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.07571, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.41, !- Minimum Part Load Ratio
1.07, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.41, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1371500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.993784E-01,6.523380E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.123765E-01,1.616509E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.154478E-02,9.635713E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1372kW_7_49COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1371500,
COP_nominal = 7.49,
PLRMin = 0.41,
PLRMinUnl = 0.41,
PLRMax = 1.07,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.07571,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {5.993784E-01,6.523380E-02,-7.714286E-03,3.114955E-02,-1.843989E-03,4.096552E-03},
EIRFunT = {9.123765E-01,1.616509E-02,1.906349E-03,-1.143164E-02,1.080775E-03,-2.873661E-03},
EIRFunPLR = {5.154478E-02,9.635713E-01,-1.896824E-02},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes";
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes, !- Name
1396100, !- Reference Capacity {W}
7.35, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.07571, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1396100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.167863E-01,-2.788454E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.207500E-01,-9.073869E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.043032E-01,3.720107E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1396kW_7_35COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1396100,
COP_nominal = 7.35,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.07571,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {5.167863E-01,-2.788454E-02,-9.497810E-04,6.693411E-02,-2.728430E-03,4.723123E-03},
EIRFunT = {5.207500E-01,-9.073869E-03,-1.812171E-04,2.568740E-02,4.255936E-05,-5.899242E-04},
EIRFunPLR = {3.043032E-01,3.720107E-02,6.590338E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1396kW/7.35COP/Vanes";
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD, !- Name
1403100, !- Reference Capacity {W}
7.09, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03426, !- Reference Chilled Water Flow Rate {m3/s}
0.04252, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.17, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.17, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.601814E-01,-3.596494E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.098641E+00,-2.485880E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.788698E-02,2.678891E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1403100,
COP_nominal = 7.09,
PLRMin = 0.17,
PLRMinUnl = 0.17,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03426,
mCon_flow_nominal = 1000 * 0.04252,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {9.601814E-01,-3.596494E-03,-1.706786E-03,6.272429E-03,-9.858212E-04,2.611673E-03},
EIRFunT = {1.098641E+00,-2.485880E-02,-6.240421E-05,-1.719488E-03,4.887321E-04,9.618075E-05},
EIRFunPLR = {8.788698E-02,2.678891E-01,6.445180E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD";
ElectricEIRChiller York YT 1403kW/6.94COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1403kW/6.94COP/VSD, !- Name
1403100, !- Reference Capacity {W}
6.94, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.05047, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1403kW/6.94COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.1, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.1 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-3.447077E-02,1.273138E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.983846E-01,2.396665E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.272242E-02,3.873540E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1403kW_6_94COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1403100,
COP_nominal = 6.94,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.1,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.05047,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {-3.447077E-02,1.273138E-01,-9.716868E-03,8.863546E-02,-3.165958E-03,2.521351E-03},
EIRFunT = {3.983846E-01,2.396665E-02,-6.601871E-03,2.944077E-02,-4.570885E-04,1.873209E-03},
EIRFunPLR = {3.272242E-02,3.873540E-01,5.789579E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1403kW/6.94COP/VSD";
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD, !- Name
1406600, !- Reference Capacity {W}
7.14, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.07571, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.521342E-01,5.248142E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.674858E-01,4.461513E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.963988E-02,3.503067E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1407kW_7_14COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1406600,
COP_nominal = 7.14,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.07571,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {4.521342E-01,5.248142E-03,-6.687636E-03,5.869437E-02,-2.390647E-03,5.040171E-03},
EIRFunT = {5.674858E-01,4.461513E-02,-6.341978E-03,4.674972E-03,4.387295E-04,2.778096E-04},
EIRFunPLR = {5.963988E-02,3.503067E-01,5.870000E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD";
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes, !- Name
1406600, !- Reference Capacity {W}
6.60, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04038, !- Reference Chilled Water Flow Rate {m3/s}
0.05804, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04038 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05804 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.191784E+00,2.070584E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.929709E-01,3.424884E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.700603E-02,5.414789E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_1407kW_6_60COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1406600,
COP_nominal = 6.60,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.04038,
mCon_flow_nominal = 1000 * 0.05804,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.191784E+00,2.070584E-02,-4.952378E-03,1.757508E-02,-2.487599E-03,5.934709E-03},
EIRFunT = {7.929709E-01,3.424884E-02,-5.567434E-03,-6.974667E-03,2.531138E-04,1.862577E-03},
EIRFunPLR = {7.700603E-02,5.414789E-01,3.826334E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes";
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD, !- Name
1406600, !- Reference Capacity {W}
6.04, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06057, !- Reference Chilled Water Flow Rate {m3/s}
0.07571, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.042261E+00,2.644821E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.026340E+00,-1.612819E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.188880E-01,6.723542E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 32.22 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1407kW_6_04COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1406600,
COP_nominal = 6.04,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.06057,
mCon_flow_nominal = 1000 * 0.07571,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 32.22,
capFunT = {1.042261E+00,2.644821E-03,-1.468026E-03,1.366256E-02,-8.302334E-04,1.573579E-03},
EIRFunT = {1.026340E+00,-1.612819E-02,-1.092591E-03,-1.784393E-02,7.961842E-04,-9.586049E-05},
EIRFunPLR = {1.188880E-01,6.723542E-01,2.068754E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD";
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD, !- Name
1410100, !- Reference Capacity {W}
8.54, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04, !- Reference Chilled Water Flow Rate {m3/s}
0.05861, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1410100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.597856E-01,-6.247187E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.131014E+00,-6.735406E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.662908E-02,7.475978E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1410kW_8_54COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1410100,
COP_nominal = 8.54,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.04,
mCon_flow_nominal = 1000 * 0.05861,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {9.597856E-01,-6.247187E-03,-1.117998E-03,6.991040E-03,-6.321252E-04,1.765068E-03},
EIRFunT = {1.131014E+00,-6.735406E-02,3.034309E-06,1.307361E-02,3.384625E-04,7.872113E-04},
EIRFunPLR = {9.662908E-02,7.475978E-01,1.566368E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD";
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD, !- Name
1441800, !- Reference Capacity {W}
6.61, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.05047, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.07, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1441800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.007341E-01,1.148568E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.287646E-01,-3.024605E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.299787E-02,3.244475E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1442kW_6_61COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1441800,
COP_nominal = 6.61,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.07,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.05047,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {4.007341E-01,1.148568E-03,1.049504E-04,5.574667E-02,-1.646131E-03,1.323200E-03},
EIRFunT = {6.287646E-01,-3.024605E-02,6.137016E-04,1.805826E-02,1.640653E-04,-1.113802E-04},
EIRFunPLR = {9.299787E-02,3.244475E-01,5.818753E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD";
ElectricEIRChiller York YT 1459kW/6.40COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1459kW/6.40COP/VSD, !- Name
1459400, !- Reference Capacity {W}
6.40, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05047, !- Reference Chilled Water Flow Rate {m3/s}
0.05047, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1459kW/6.40COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.13, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.13 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1459400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-1.665585E-01,2.211580E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.438935E-01,9.821191E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.999642E-02,2.509430E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1459kW_6_40COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1459400,
COP_nominal = 6.40,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.13,
mEva_flow_nominal = 1000 * 0.05047,
mCon_flow_nominal = 1000 * 0.05047,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {-1.665585E-01,2.211580E-01,-1.408361E-02,6.476151E-02,-2.009341E-03,-7.897630E-05},
EIRFunT = {1.438935E-01,9.821191E-02,-1.174270E-02,3.748666E-02,-5.700518E-04,1.053698E-03},
EIRFunPLR = {3.999642E-02,2.509430E-01,7.067059E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1459kW/6.40COP/VSD";
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD, !- Name
1484000, !- Reference Capacity {W}
9.96, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09085, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.24, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.24, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.24 | Minimum part unload ratio |
Real | PLRMin | 0.24 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1484000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-4.544480E-01,-3.615933E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-3.693940E-01,-6.387787E-02... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.353827E-01,1.385983E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1484kW_9_96COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1484000,
COP_nominal = 9.96,
PLRMin = 0.24,
PLRMinUnl = 0.24,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09085,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {-4.544480E-01,-3.615933E-02,-2.734006E-03,1.683863E-01,-4.557649E-03,5.362840E-03},
EIRFunT = {-3.693940E-01,-6.387787E-02,-2.760494E-04,1.661135E-01,-3.105485E-03,1.705909E-03},
EIRFunPLR = {1.353827E-01,1.385983E-02,8.522688E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD";
ElectricEIRChiller York YT 1495kW/7.51COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1495kW/7.51COP/VSD, !- Name
1494500, !- Reference Capacity {W}
7.51, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.0429, !- Reference Chilled Water Flow Rate {m3/s}
0.06719, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1495kW/7.51COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.11, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.11, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1494500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.51 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0429 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06719 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.051921E+00,-1.632255E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.106985E-01,-2.087623E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.517470E-01,-1.577252E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1495kW_7_51COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1494500,
COP_nominal = 7.51,
PLRMin = 0.11,
PLRMinUnl = 0.11,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.0429,
mCon_flow_nominal = 1000 * 0.06719,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {1.051921E+00,-1.632255E-01,1.149042E-02,5.463515E-02,-1.579985E-03,1.628246E-03},
EIRFunT = {7.106985E-01,-2.087623E-01,9.421379E-03,8.491925E-02,-1.260820E-03,1.125512E-03},
EIRFunPLR = {1.517470E-01,-1.577252E-01,1.005197E+00},
etaMotor = 1.0) "ElectricEIRChiller York YT 1495kW/7.51COP/VSD";
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes, !- Name
1519200, !- Reference Capacity {W}
7.10, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.03186, !- Reference Chilled Water Flow Rate {m3/s}
0.08139, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1519200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08139 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.265889E+00,3.401563E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.981236E-01,-1.060763E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.563837E-01,4.894381E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1519200,
COP_nominal = 7.10,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03186,
mCon_flow_nominal = 1000 * 0.08139,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {1.265889E+00,3.401563E-02,-6.532621E-03,-6.600960E-03,-2.172017E-03,7.121766E-03},
EIRFunT = {9.981236E-01,-1.060763E-02,-3.921458E-03,-1.206761E-02,-1.398595E-04,3.467199E-03},
EIRFunPLR = {1.563837E-01,4.894381E-01,3.541551E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes";
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD, !- Name
1557800, !- Reference Capacity {W}
5.81, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
21.11, !- Reference Entering Condenser Fluid Temperature {C}
0.03785, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1557800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.034307E+00,2.390635E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.099343E+00,-3.132676E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.620909E-01,-2.553890E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.94 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1558kW_5_81COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1557800,
COP_nominal = 5.81,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.03785,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 21.11,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 11.94,
TConEntMax = 273.15 + 23.89,
capFunT = {1.034307E+00,2.390635E-02,-1.222578E-03,-5.346220E-03,-2.183258E-04,6.282331E-04},
EIRFunT = {1.099343E+00,-3.132676E-02,4.108521E-04,-7.377845E-03,5.775048E-04,-3.528472E-04},
EIRFunPLR = {1.620909E-01,-2.553890E-01,1.092232E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD";
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD, !- Name
1586000, !- Reference Capacity {W}
5.53, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.03388, !- Reference Chilled Water Flow Rate {m3/s}
0.04669, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1586000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03388 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04669 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.119233E+00,1.130501E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.110611E+00,-3.795765E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.996379E-01,-1.612021E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1586kW_5_53COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1586000,
COP_nominal = 5.53,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.03388,
mCon_flow_nominal = 1000 * 0.04669,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {1.119233E+00,1.130501E-02,-6.423802E-04,-5.144512E-03,-3.085995E-04,7.813582E-04},
EIRFunT = {1.110611E+00,-3.795765E-02,2.851444E-04,-4.560404E-03,4.044229E-04,1.407332E-04},
EIRFunPLR = {1.996379E-01,-1.612021E-01,9.608483E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD";
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes, !- Name
1635200, !- Reference Capacity {W}
7.47, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04416, !- Reference Chilled Water Flow Rate {m3/s}
0.06624, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.08, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.08, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.47 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04416 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06624 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.894188E-01,2.983148E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.040733E+00,-7.118888E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.836695E-01,5.781685E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_1635kW_7_47COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1635200,
COP_nominal = 7.47,
PLRMin = 0.08,
PLRMinUnl = 0.08,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.04416,
mCon_flow_nominal = 1000 * 0.06624,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {9.894188E-01,2.983148E-03,-2.484601E-03,5.974984E-03,-1.063988E-03,2.601503E-03},
EIRFunT = {1.040733E+00,-7.118888E-02,2.262395E-03,1.221901E-02,2.152693E-04,7.409943E-04},
EIRFunPLR = {1.836695E-01,5.781685E-01,2.385719E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes";
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes, !- Name
1635200, !- Reference Capacity {W}
6.36, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.03432, !- Reference Chilled Water Flow Rate {m3/s}
0.05035, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.36 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03432 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05035 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.639212E-01,1.160405E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.355981E-01,-1.083354E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.581595E-01,2.707154E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1635kW_6_36COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1635200,
COP_nominal = 6.36,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.03432,
mCon_flow_nominal = 1000 * 0.05035,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {7.639212E-01,1.160405E-02,-5.344185E-03,3.306796E-02,-2.100827E-03,4.920586E-03},
EIRFunT = {7.355981E-01,-1.083354E-02,-9.244662E-04,1.458943E-02,8.494647E-06,1.279572E-04},
EIRFunPLR = {2.581595E-01,2.707154E-01,4.707425E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes";
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD, !- Name
1656300, !- Reference Capacity {W}
8.24, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04322, !- Reference Chilled Water Flow Rate {m3/s}
0.06296, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.17, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.17, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1656300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.611706E-01,-2.867067E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.730916E-01,-8.073559E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.982584E-01,4.414042E-02,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1656kW_8_24COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1656300,
COP_nominal = 8.24,
PLRMin = 0.17,
PLRMinUnl = 0.17,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.04322,
mCon_flow_nominal = 1000 * 0.06296,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {7.611706E-01,-2.867067E-02,-2.363358E-03,4.097113E-02,-2.343044E-03,4.547017E-03},
EIRFunT = {7.730916E-01,-8.073559E-02,-2.161313E-03,6.144398E-02,-1.953734E-03,4.056527E-03},
EIRFunPLR = {1.982584E-01,4.414042E-02,7.642946E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD";
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes, !- Name
1663300, !- Reference Capacity {W}
9.34, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04139, !- Reference Chilled Water Flow Rate {m3/s}
0.0776, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.17, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.17, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1663300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04139 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0776 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.112226E-01,-4.546497E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.028094E+00,-6.127553E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.127966E-01,3.131004E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1663kW_9_34COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1663300,
COP_nominal = 9.34,
PLRMin = 0.17,
PLRMinUnl = 0.17,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.04139,
mCon_flow_nominal = 1000 * 0.0776,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {9.112226E-01,-4.546497E-02,4.431126E-03,2.439160E-02,-1.415836E-03,1.877877E-03},
EIRFunT = {1.028094E+00,-6.127553E-02,3.236371E-03,1.656482E-02,2.976850E-04,-4.418361E-04},
EIRFunPLR = {2.127966E-01,3.131004E-01,4.726018E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1663kW/9.34COP/Vanes";
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes, !- Name
1673900, !- Reference Capacity {W}
7.89, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09085, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.32, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.32, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.32 | Minimum part unload ratio |
Real | PLRMin | 0.32 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1673900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.925408E-01,-4.406182E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.868510E-01,-6.325526E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.386410E-01,2.621224E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XL_1674kW_7_89COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1673900,
COP_nominal = 7.89,
PLRMin = 0.32,
PLRMinUnl = 0.32,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09085,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {2.925408E-01,-4.406182E-02,-1.292074E-03,9.008701E-02,-2.646719E-03,3.388396E-03},
EIRFunT = {9.868510E-01,-6.325526E-02,3.498632E-03,1.699731E-02,2.573490E-04,-4.233553E-04},
EIRFunPLR = {3.386410E-01,2.621224E-01,3.987109E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes";
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes, !- Name
1680900, !- Reference Capacity {W}
6.59, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.04366, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1680900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.59 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.792987E-01,-5.291217E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.344630E-01,-5.781149E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.619116E-01,2.362420E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1680900,
COP_nominal = 6.59,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.04366,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 18.33,
TConEntMax = 273.15 + 23.89,
capFunT = {6.792987E-01,-5.291217E-02,-5.280108E-03,5.252682E-02,-2.523689E-03,7.344940E-03},
EIRFunT = {4.344630E-01,-5.781149E-03,2.852311E-04,2.723246E-02,1.280801E-04,-8.964328E-04},
EIRFunPLR = {1.619116E-01,2.362420E-01,6.032459E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes";
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD, !- Name
1723100, !- Reference Capacity {W}
8.32, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04757, !- Reference Chilled Water Flow Rate {m3/s}
0.06934, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1723100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06934 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.742518E-01,-5.109937E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.950574E-01,-1.036684E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.374010E-01,-1.796745E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1723kW_8_32COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1723100,
COP_nominal = 8.32,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.04757,
mCon_flow_nominal = 1000 * 0.06934,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {4.742518E-01,-5.109937E-02,-2.845323E-03,8.257997E-02,-3.404799E-03,5.625321E-03},
EIRFunT = {2.950574E-01,-1.036684E-01,-4.169567E-03,1.256790E-01,-4.004203E-03,6.718687E-03},
EIRFunPLR = {2.374010E-01,-1.796745E-01,9.441507E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD";
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes, !- Name
1726600, !- Reference Capacity {W}
9.04, !- Reference COP {W/W}
7.78, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.03912, !- Reference Chilled Water Flow Rate {m3/s}
0.07192, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.17, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.17, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1726600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03912 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07192 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.509915E-01,2.567642E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.072553E+00,-8.058631E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.465824E-01,4.494453E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1727kW_9_04COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1726600,
COP_nominal = 9.04,
PLRMin = 0.17,
PLRMinUnl = 0.17,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03912,
mCon_flow_nominal = 1000 * 0.07192,
TEvaLvg_nominal = 273.15 + 7.78,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {6.509915E-01,2.567642E-02,-5.417815E-03,3.406103E-02,-1.703640E-03,3.336164E-03},
EIRFunT = {1.072553E+00,-8.058631E-03,-2.109608E-03,-1.262910E-03,6.155442E-04,4.796754E-04},
EIRFunPLR = {2.465824E-01,4.494453E-01,3.037680E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes";
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes, !- Name
1751300, !- Reference Capacity {W}
6.73, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.04145, !- Reference Chilled Water Flow Rate {m3/s}
0.09337, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1751300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.923045E-01,1.003672E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.089395E-01,2.628482E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.250725E-01,2.648297E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_WSC_1751kW_6_73COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1751300,
COP_nominal = 6.73,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.04145,
mCon_flow_nominal = 1000 * 0.09337,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {7.923045E-01,1.003672E-01,-4.348900E-03,3.755572E-03,-7.675491E-04,6.788600E-04},
EIRFunT = {8.089395E-01,2.628482E-02,-1.773497E-03,-8.118430E-03,7.146809E-04,-6.481705E-04},
EIRFunPLR = {2.250725E-01,2.648297E-01,5.095786E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes";
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
5.96, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.074211E+00,7.710761E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.910329E-01,-9.895115E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.694797E-01,9.551656E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_1758kW_5_96COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 5.96,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06309,
mCon_flow_nominal = 1000 * 0.06309,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {1.074211E+00,7.710761E-03,-3.166770E-03,-1.868765E-02,1.273866E-04,2.744586E-03},
EIRFunT = {4.910329E-01,-9.895115E-02,4.257871E-03,5.433817E-02,-8.184909E-04,6.178810E-04},
EIRFunPLR = {3.694797E-01,9.551656E-02,5.347291E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes";
ElectricEIRChiller York YT 1758kW/5.76COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1758kW/5.76COP/VSD, !- Name
1758300, !- Reference Capacity {W}
5.76, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1758kW/5.76COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.76 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.575085E-01,1.313508E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.794525E-01,6.694756E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.859908E-02,1.950291E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.51 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1758kW_5_76COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 5.76,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06309,
mCon_flow_nominal = 1000 * 0.06309,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.51,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {4.575085E-01,1.313508E-01,-4.408831E-03,1.930354E-02,-5.479641E-04,-1.376580E-03},
EIRFunT = {6.794525E-01,6.694756E-02,-3.625396E-03,-1.018762E-02,1.066394E-03,-2.113402E-03},
EIRFunPLR = {7.859908E-02,1.950291E-01,7.241581E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1758kW/5.76COP/VSD";
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
6.26, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.14, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.14 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.975936E-01,-1.459740E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.311197E-01,9.581517E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.720545E-01,5.598164E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1758kW_6_26COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 6.26,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.14,
mEva_flow_nominal = 1000 * 0.06309,
mCon_flow_nominal = 1000 * 0.06309,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {8.975936E-01,-1.459740E-02,3.647187E-03,3.202545E-02,-1.190379E-03,3.297810E-04},
EIRFunT = {2.311197E-01,9.581517E-02,-5.672726E-03,2.766035E-02,-1.411214E-04,-1.011216E-03},
EIRFunPLR = {1.720545E-01,5.598164E-01,2.626117E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1758kW/6.26COP/Vanes";
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
5.96, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.492365E-01,5.551947E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.949320E-01,9.099785E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.236154E-01,2.590053E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1758kW_5_96COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 5.96,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.06309,
mCon_flow_nominal = 1000 * 0.06309,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {8.492365E-01,5.551947E-02,-2.973138E-04,1.164389E-03,-2.955716E-04,8.464931E-05},
EIRFunT = {4.949320E-01,9.099785E-03,-6.935841E-04,3.277452E-02,-3.895481E-04,-5.524011E-04},
EIRFunPLR = {2.236154E-01,2.590053E-01,5.169137E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1758kW/5.96COP/Vanes";
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
5.96, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09464, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.566057E-02,-2.457943E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.243313E+00,-3.031784E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.871377E-01,5.849639E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 5.96,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09464,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 23.89,
TConEntMax = 273.15 + 35.00,
capFunT = {9.566057E-02,-2.457943E-02,-6.827143E-03,7.119360E-02,-2.047680E-03,5.248800E-03},
EIRFunT = {1.243313E+00,-3.031784E-02,3.452464E-03,-2.739941E-02,9.141695E-04,-1.000080E-03},
EIRFunPLR = {1.871377E-01,5.849639E-01,2.291447E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes";
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
6.28, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09464, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.079149E-01,-2.006276E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.605391E-01,-1.377994E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.861223E-01,5.482049E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1758kW_6_28COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 6.28,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09464,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 35.00,
capFunT = {7.079149E-01,-2.006276E-03,-2.596043E-03,3.005922E-02,-1.056423E-03,2.045705E-03},
EIRFunT = {5.605391E-01,-1.377994E-02,6.569542E-05,1.321951E-02,2.686074E-04,-5.011451E-04},
EIRFunPLR = {1.861223E-01,5.482049E-01,2.647377E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1758kW/6.28COP/Vanes";
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD, !- Name
1758300, !- Reference Capacity {W}
5.86, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06303, !- Reference Chilled Water Flow Rate {m3/s}
0.07337, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.86 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.677279E-01,-3.175504E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.743365E-01,-5.054806E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.784580E-01,-5.498632E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1758kW_5_86COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 5.86,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06303,
mCon_flow_nominal = 1000 * 0.07337,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {3.677279E-01,-3.175504E-02,-4.096383E-03,7.527566E-02,-2.757540E-03,5.359020E-03},
EIRFunT = {1.743365E-01,-5.054806E-02,-5.424748E-03,8.244673E-02,-2.400392E-03,5.078720E-03},
EIRFunPLR = {2.784580E-01,-5.498632E-01,1.269693E+00},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD";
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD, !- Name
1758300, !- Reference Capacity {W}
6.46, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.46 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.066671E+00,5.889240E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.989434E-02,2.062907E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.268954E-01,3.297771E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_1758kW_6_46COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 6.46,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06309,
mCon_flow_nominal = 1000 * 0.06309,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {1.066671E+00,5.889240E-03,-3.155053E-03,-1.591039E-02,1.042897E-04,2.576256E-03},
EIRFunT = {7.989434E-02,2.062907E-02,-4.050827E-04,4.570552E-02,-1.469163E-04,-1.563259E-03},
EIRFunPLR = {3.268954E-01,3.297771E-01,3.423342E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD";
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
6.87, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.44, !- Reference Entering Condenser Fluid Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.87 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.085529E-01,3.412026E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.329473E-01,5.521802E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.401900E-01,5.090345E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 6.87,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.06309,
mCon_flow_nominal = 1000 * 0.06309,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 24.44,
capFunT = {8.085529E-01,3.412026E-02,-4.184591E-04,4.111323E-03,-1.764627E-04,4.184748E-04},
EIRFunT = {6.329473E-01,5.521802E-03,1.487172E-04,2.433576E-03,7.100129E-04,-1.108627E-03},
EIRFunPLR = {2.401900E-01,5.090345E-01,2.500532E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes";
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes, !- Name
1775900, !- Reference Capacity {W}
8.00, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04757, !- Reference Chilled Water Flow Rate {m3/s}
0.07003, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.17, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.17, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1775900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07003 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.841535E-01,-3.584260E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.006719E-01,-3.137026E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.276235E-01,2.787167E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1776kW_8_00COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1775900,
COP_nominal = 8.00,
PLRMin = 0.17,
PLRMinUnl = 0.17,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.04757,
mCon_flow_nominal = 1000 * 0.07003,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {4.841535E-01,-3.584260E-02,-1.467417E-03,7.773868E-02,-3.125809E-03,3.729631E-03},
EIRFunT = {8.006719E-01,-3.137026E-02,4.098888E-04,3.176921E-02,-2.104567E-04,-7.660277E-05},
EIRFunPLR = {3.276235E-01,2.787167E-01,3.952405E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes";
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes, !- Name
1779400, !- Reference Capacity {W}
6.18, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.06303, !- Reference Chilled Water Flow Rate {m3/s}
0.08858, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08858 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.703515E-01,-4.051337E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.872331E-01,-3.907248E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.090532E-01,2.641442E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XL_1779kW_6_18COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1779400,
COP_nominal = 6.18,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.06303,
mCon_flow_nominal = 1000 * 0.08858,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 26.11,
capFunT = {2.703515E-01,-4.051337E-02,-5.968813E-03,8.261488E-02,-3.019425E-03,6.718040E-03},
EIRFunT = {5.872331E-01,-3.907248E-02,3.474913E-04,2.950392E-02,-2.510016E-04,2.481610E-04},
EIRFunPLR = {3.090532E-01,2.641442E-01,4.269265E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes";
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes, !- Name
1779400, !- Reference Capacity {W}
6.18, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.04454, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04454 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.331346E-01,-5.678656E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.137523E-01,-1.879556E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.699409E-01,1.874304E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_1779kW_6_18COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1779400,
COP_nominal = 6.18,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.04454,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 18.33,
TConEntMax = 273.15 + 23.89,
capFunT = {3.331346E-01,-5.678656E-02,-1.257764E-03,8.198893E-02,-2.612490E-03,4.226087E-03},
EIRFunT = {3.137523E-01,-1.879556E-02,-1.860907E-03,3.469711E-02,-1.503480E-04,7.641242E-04},
EIRFunPLR = {1.699409E-01,1.874304E-01,6.410385E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes";
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes, !- Name
1793500, !- Reference Capacity {W}
8.11, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05148, !- Reference Chilled Water Flow Rate {m3/s}
0.09653, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.08, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.536140E+00,-1.630760E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.546274E-01,2.456473E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.187543E-02,8.272483E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1794kW_8_11COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1793500,
COP_nominal = 8.11,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.08,
mEva_flow_nominal = 1000 * 0.05148,
mCon_flow_nominal = 1000 * 0.09653,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {1.536140E+00,-1.630760E-01,1.225832E-02,2.148166E-02,-1.654700E-03,2.660568E-03},
EIRFunT = {8.546274E-01,2.456473E-01,-9.770595E-03,-7.386557E-02,2.843499E-03,-5.292981E-03},
EIRFunPLR = {3.187543E-02,8.272483E-01,1.279099E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1794kW/8.11COP/Vanes";
ElectricEIRChiller York YT 1794kW/7.90COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1794kW/7.90COP/VSD, !- Name
1793500, !- Reference Capacity {W}
7.90, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05148, !- Reference Chilled Water Flow Rate {m3/s}
0.09653, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1794kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.552268E-01,-1.553435E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.984829E-01,-1.552700E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.445880E-01,1.059293E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1794kW_7_90COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1793500,
COP_nominal = 7.90,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.05148,
mCon_flow_nominal = 1000 * 0.09653,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {9.552268E-01,-1.553435E-01,7.958834E-03,6.132388E-02,-1.899594E-03,3.323245E-03},
EIRFunT = {5.984829E-01,-1.552700E-01,6.909012E-03,6.801572E-02,-7.450754E-04,5.764600E-04},
EIRFunPLR = {1.445880E-01,1.059293E-01,7.489704E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1794kW/7.90COP/VSD";
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes, !- Name
1797000, !- Reference Capacity {W}
5.69, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.07737, !- Reference Chilled Water Flow Rate {m3/s}
0.09672, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.39, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.39, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.39 | Minimum part unload ratio |
Real | PLRMin | 0.39 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1797000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07737 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09672 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.084596E-01,4.671596E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.084290E+00,-4.318103E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.926251E-01,-2.657314E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1797000,
COP_nominal = 5.69,
PLRMin = 0.39,
PLRMinUnl = 0.39,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.07737,
mCon_flow_nominal = 1000 * 0.09672,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 21.11,
TConEntMax = 273.15 + 29.44,
capFunT = {9.084596E-01,4.671596E-02,-1.188845E-03,-2.284596E-03,-3.170254E-05,-3.577858E-04},
EIRFunT = {1.084290E+00,-4.318103E-02,1.586113E-03,1.664015E-03,8.043383E-05,5.681056E-05},
EIRFunPLR = {5.926251E-01,-2.657314E-01,6.731751E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes";
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD, !- Name
1800500, !- Reference Capacity {W}
6.34, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05161, !- Reference Chilled Water Flow Rate {m3/s}
0.06385, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1800500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05161 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06385 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.174861E-01,-7.299051E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.931082E-01,-1.885558E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.040764E-01,2.818752E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1800500,
COP_nominal = 6.34,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.05161,
mCon_flow_nominal = 1000 * 0.06385,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {6.174861E-01,-7.299051E-02,-1.897105E-03,7.003662E-02,-2.852439E-03,5.751931E-03},
EIRFunT = {6.931082E-01,-1.885558E-02,8.345461E-04,1.263879E-02,4.588028E-04,-8.221467E-04},
EIRFunPLR = {1.040764E-01,2.818752E-01,6.144036E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD";
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes, !- Name
1867300, !- Reference Capacity {W}
10.09, !- Reference COP {W/W}
7.78, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09085, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1867300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.451516E-01,-1.252382E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.668391E-01,1.506485E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.157002E-01,2.251016E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1867kW_10_09COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1867300,
COP_nominal = 10.09,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09085,
TEvaLvg_nominal = 273.15 + 7.78,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {4.451516E-01,-1.252382E-02,-2.878042E-03,6.132233E-02,-2.365055E-03,4.514258E-03},
EIRFunT = {6.668391E-01,1.506485E-02,-4.249134E-03,3.588996E-02,-1.681591E-04,7.028459E-04},
EIRFunPLR = {2.157002E-01,2.251016E-01,5.584287E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1867kW/10.09COP/Vanes";
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes, !- Name
1870800, !- Reference Capacity {W}
6.49, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.06303, !- Reference Chilled Water Flow Rate {m3/s}
0.0877, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1870800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0877 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.658630E-03,-3.836575E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.029608E+00,-7.149045E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.984908E-01,2.906868E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XL_1871kW_6_49COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1870800,
COP_nominal = 6.49,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06303,
mCon_flow_nominal = 1000 * 0.0877,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {5.658630E-03,-3.836575E-02,-5.122195E-03,1.068063E-01,-3.377824E-03,5.650118E-03},
EIRFunT = {1.029608E+00,-7.149045E-02,2.043279E-03,-6.116474E-04,3.908334E-04,6.870233E-04},
EIRFunPLR = {2.984908E-01,2.906868E-01,4.089411E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes";
ElectricEIRChiller York YT 1881kW/6.77COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1881kW/6.77COP/VSD, !- Name
1881400, !- Reference Capacity {W}
6.77, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09464, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1881kW/6.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.065247E-01,-4.158206E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.175311E-01,-3.913241E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.087656E-02,4.842164E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1881kW_6_77COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1881400,
COP_nominal = 6.77,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09464,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {5.065247E-01,-4.158206E-03,-2.681976E-03,4.763436E-02,-1.951270E-03,3.994399E-03},
EIRFunT = {6.175311E-01,-3.913241E-02,6.177961E-04,2.775640E-02,-2.151466E-04,5.514895E-04},
EIRFunPLR = {6.087656E-02,4.842164E-01,4.571519E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 1881kW/6.77COP/VSD";
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes, !- Name
1881400, !- Reference Capacity {W}
6.53, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.04397, !- Reference Chilled Water Flow Rate {m3/s}
0.1041, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.561286E-01,4.130164E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.434989E-01,4.361264E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.272116E-02,4.176382E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 9.44 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_1881kW_6_53COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1881400,
COP_nominal = 6.53,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.04397,
mCon_flow_nominal = 1000 * 0.1041,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 9.44,
TConEntMax = 273.15 + 26.67,
capFunT = {8.561286E-01,4.130164E-02,-7.109335E-04,4.306273E-03,-6.336613E-04,7.211635E-04},
EIRFunT = {4.434989E-01,4.361264E-02,-1.733337E-03,9.915503E-03,4.312717E-04,-1.122346E-03},
EIRFunPLR = {5.272116E-02,4.176382E-01,5.310870E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 1881kW/6.53COP/Vanes";
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes, !- Name
1895400, !- Reference Capacity {W}
6.42, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09085, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.09, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.09 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1895400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.573195E-01,-1.131937E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.915073E-01,-4.399727E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.592598E-01,1.425462E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_1895kW_6_42COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1895400,
COP_nominal = 6.42,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.09,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09085,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {8.573195E-01,-1.131937E-01,3.444205E-03,4.865045E-02,-2.103805E-03,4.986639E-03},
EIRFunT = {3.915073E-01,-4.399727E-02,-3.868294E-06,4.623771E-02,-7.092319E-04,1.372133E-03},
EIRFunPLR = {2.592598E-01,1.425462E-01,5.966041E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes";
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes, !- Name
1934100, !- Reference Capacity {W}
7.55, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
13.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05552, !- Reference Chilled Water Flow Rate {m3/s}
0.08675, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 13.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08675 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.420318E-02,1.103599E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.173674E+00,-1.301647E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.706237E-01,6.063362E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_1934kW_7_55COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1934100,
COP_nominal = 7.55,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.05552,
mCon_flow_nominal = 1000 * 0.08675,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 13.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {4.420318E-02,1.103599E-01,-2.597752E-03,7.043754E-02,-2.138316E-03,-4.696924E-04},
EIRFunT = {1.173674E+00,-1.301647E-01,5.588446E-03,8.605153E-03,7.234201E-05,1.314581E-03},
EIRFunPLR = {1.706237E-01,6.063362E-01,2.170672E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 1934kW/7.55COP/Vanes";
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes, !- Name
1934100, !- Reference Capacity {W}
6.01, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.05552, !- Reference Chilled Water Flow Rate {m3/s}
0.07981, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.08, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.01 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.893111E-01,-3.834949E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.885371E-01,-5.877829E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.849256E-01,-2.369152E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PEH_1934kW_6_01COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1934100,
COP_nominal = 6.01,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.08,
mEva_flow_nominal = 1000 * 0.05552,
mCon_flow_nominal = 1000 * 0.07981,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {2.893111E-01,-3.834949E-02,1.757934E-03,8.665805E-02,-2.597243E-03,2.413315E-03},
EIRFunT = {2.885371E-01,-5.877829E-03,-1.807763E-03,5.193076E-02,-7.936373E-04,1.108590E-03},
EIRFunPLR = {3.849256E-01,-2.369152E-01,8.496351E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes";
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes, !- Name
1972800, !- Reference Capacity {W}
6.28, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.04145, !- Reference Chilled Water Flow Rate {m3/s}
0.09337, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1972800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.110884E+00,7.376077E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.097378E+00,-3.018324E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.282891E-01,2.722981E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_WDC_1973kW_6_28COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1972800,
COP_nominal = 6.28,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.04145,
mCon_flow_nominal = 1000 * 0.09337,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {1.110884E+00,7.376077E-02,-5.957719E-03,-2.861037E-02,-2.129104E-04,2.547028E-03},
EIRFunT = {1.097378E+00,-3.018324E-02,-2.792200E-03,-1.252428E-02,2.095232E-04,2.409252E-03},
EIRFunPLR = {1.282891E-01,2.722981E-01,6.012232E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes";
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes, !- Name
1997400, !- Reference Capacity {W}
7.24, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.04397, !- Reference Chilled Water Flow Rate {m3/s}
0.1041, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1997400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.058272E-01,1.309175E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.188194E-01,8.769791E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.359332E-02,5.873752E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_1997kW_7_24COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1997400,
COP_nominal = 7.24,
PLRMin = 0.18,
PLRMinUnl = 0.18,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.04397,
mCon_flow_nominal = 1000 * 0.1041,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 7.22,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {9.058272E-01,1.309175E-01,-3.446620E-03,-3.166792E-02,2.325200E-04,-4.892256E-04},
EIRFunT = {1.188194E-01,8.769791E-02,-1.692086E-03,2.209962E-03,1.327958E-03,-3.249833E-03},
EIRFunPLR = {9.359332E-02,5.873752E-01,3.208990E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 1997kW/7.24COP/Vanes";
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes, !- Name
2043100, !- Reference Capacity {W}
8.44, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.04757, !- Reference Chilled Water Flow Rate {m3/s}
0.06814, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.08, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.08, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06814 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.383569E-01,4.716323E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.891693E-01,1.168677E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.225600E-01,3.070007E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_2043kW_8_44COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2043100,
COP_nominal = 8.44,
PLRMin = 0.08,
PLRMinUnl = 0.08,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.04757,
mCon_flow_nominal = 1000 * 0.06814,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {8.383569E-01,4.716323E-02,-2.515385E-03,-3.773603E-03,-9.186324E-04,2.177057E-03},
EIRFunT = {7.891693E-01,1.168677E-02,-1.825470E-03,1.278749E-02,1.521317E-04,2.156746E-04},
EIRFunPLR = {1.225600E-01,3.070007E-01,5.712759E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes";
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes, !- Name
2043100, !- Reference Capacity {W}
9.08, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
18.33, !- Reference Entering Condenser Fluid Temperature {C}
0.09085, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.28, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.28, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.08 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-1.340241E+00,7.634284E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.065177E-01,1.178669E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.173752E-01,4.394720E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_2043kW_9_08COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2043100,
COP_nominal = 9.08,
PLRMin = 0.28,
PLRMinUnl = 0.28,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.09085,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 18.33,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 18.33,
TConEntMax = 273.15 + 29.44,
capFunT = {-1.340241E+00,7.634284E-03,-3.044184E-03,1.991327E-01,-4.530240E-03,2.700765E-03},
EIRFunT = {6.065177E-01,1.178669E-02,2.098586E-03,1.532536E-02,6.756887E-04,-2.629852E-03},
EIRFunPLR = {2.173752E-01,4.394720E-01,3.431813E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes";
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes, !- Name
2057200, !- Reference Capacity {W}
6.05, !- Reference COP {W/W}
7.78, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.08322, !- Reference Chilled Water Flow Rate {m3/s}
0.09722, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.28, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.28, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2057200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09722 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.737452E-01,-1.249478E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.623086E-01,-5.844490E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.041274E-01,-3.861525E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XL_2057kW_6_05COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2057200,
COP_nominal = 6.05,
PLRMin = 0.28,
PLRMinUnl = 0.28,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.08322,
mCon_flow_nominal = 1000 * 0.09722,
TEvaLvg_nominal = 273.15 + 7.78,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.737452E-01,-1.249478E-02,-3.193419E-03,2.110302E-02,-1.188413E-03,3.820335E-03},
EIRFunT = {8.623086E-01,-5.844490E-02,-2.284745E-03,2.469188E-02,-1.022604E-03,3.996523E-03},
EIRFunPLR = {4.041274E-01,-3.861525E-01,9.804493E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes";
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes, !- Name
2110000, !- Reference Capacity {W}
7.15, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06057, !- Reference Chilled Water Flow Rate {m3/s}
0.09464, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2110000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.359238E-01,1.785857E-02,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.270855E-01,-4.119654E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.469187E-01,1.862690E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_2110kW_7_15COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2110000,
COP_nominal = 7.15,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.06057,
mCon_flow_nominal = 1000 * 0.09464,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {5.359238E-01,1.785857E-02,1.579272E-03,4.522868E-02,-1.632172E-03,6.008061E-04},
EIRFunT = {6.270855E-01,-4.119654E-02,1.327107E-03,2.661446E-02,-1.856827E-04,5.094942E-04},
EIRFunPLR = {2.469187E-01,1.862690E-01,5.660904E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 2110kW/7.15COP/Vanes";
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes, !- Name
2124000, !- Reference Capacity {W}
6.03, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.05552, !- Reference Chilled Water Flow Rate {m3/s}
0.07981, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2124000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.040134E+00,-1.745650E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.157799E+00,-3.621524E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.051419E-01,2.033679E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_2124kW_6_03COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2124000,
COP_nominal = 6.03,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.05552,
mCon_flow_nominal = 1000 * 0.07981,
TEvaLvg_nominal = 273.15 + 8.89,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {1.040134E+00,-1.745650E-02,1.084856E-03,6.629328E-03,-8.008991E-04,1.567769E-03},
EIRFunT = {1.157799E+00,-3.621524E-02,-3.684818E-03,-1.202959E-02,-7.378548E-05,3.787365E-03},
EIRFunPLR = {1.051419E-01,2.033679E-01,6.902026E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes";
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes, !- Name
2159200, !- Reference Capacity {W}
6.85, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.14, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.14, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2159200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.85 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.322235E-01,1.553954E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.106730E-01,-3.786410E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.595694E-01,1.889684E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_2159kW_6_85COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2159200,
COP_nominal = 6.85,
PLRMin = 0.14,
PLRMinUnl = 0.14,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {6.322235E-01,1.553954E-02,-9.149770E-03,5.284289E-02,-2.818835E-03,7.074096E-03},
EIRFunT = {9.106730E-01,-3.786410E-03,-1.084261E-03,-7.148246E-03,5.178799E-04,1.818623E-05},
EIRFunPLR = {2.595694E-01,1.889684E-01,5.518450E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 2159kW/6.85COP/Vanes";
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes, !- Name
2183800, !- Reference Capacity {W}
6.78, !- Reference COP {W/W}
7.78, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.04883, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2183800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04883 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.235680E+00,2.213527E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.877947E-01,-1.334886E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.942647E-02,5.249540E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_2184kW_6_78COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2183800,
COP_nominal = 6.78,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.04883,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 7.78,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 18.33,
TConEntMax = 273.15 + 23.89,
capFunT = {1.235680E+00,2.213527E-02,-1.770186E-03,-1.131594E-02,-5.008696E-04,1.356522E-03},
EIRFunT = {8.877947E-01,-1.334886E-02,1.689581E-03,-1.599710E-03,7.884945E-04,-1.584900E-03},
EIRFunPLR = {8.942647E-02,5.249540E-01,3.850801E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes";
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes, !- Name
2201400, !- Reference Capacity {W}
6.69, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.14, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.14, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2201400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.474968E-01,-4.800356E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.234137E-01,1.308264E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.653493E-01,1.444620E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_2201kW_6_69COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2201400,
COP_nominal = 6.69,
PLRMin = 0.14,
PLRMinUnl = 0.14,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {5.474968E-01,-4.800356E-03,-6.845886E-03,6.302552E-02,-2.911528E-03,6.598690E-03},
EIRFunT = {8.234137E-01,1.308264E-02,-1.147806E-03,-4.071161E-03,5.220869E-04,-6.312495E-04},
EIRFunPLR = {2.653493E-01,1.444620E-01,5.911158E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 2201kW/6.69COP/Vanes";
ElectricEIRChiller York YT 2233kW/9.54COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 2233kW/9.54COP/VSD, !- Name
2233000, !- Reference Capacity {W}
9.54, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.06107, !- Reference Chilled Water Flow Rate {m3/s}
0.11451, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 2233kW/9.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2233000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06107 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11451 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.585741E-01,-5.127829E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.563409E-01,-1.966623E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.917141E-02,1.743339E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_2233kW_9_54COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2233000,
COP_nominal = 9.54,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.06107,
mCon_flow_nominal = 1000 * 0.11451,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.585741E-01,-5.127829E-02,5.848602E-03,4.235544E-02,-1.606561E-03,9.364594E-04},
EIRFunT = {7.563409E-01,-1.966623E-02,-3.927494E-04,2.973607E-02,1.299230E-04,-4.325357E-04},
EIRFunPLR = {6.917141E-02,1.743339E-01,7.524059E-01},
etaMotor = 1.0) "ElectricEIRChiller York YT 2233kW/9.54COP/VSD";
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes, !- Name
2236600, !- Reference Capacity {W}
6.41, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.13, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.13, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2236600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.899710E-01,-1.413334E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.567950E-01,3.354557E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.605354E-01,2.125571E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_2237kW_6_41COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2236600,
COP_nominal = 6.41,
PLRMin = 0.13,
PLRMinUnl = 0.13,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {6.899710E-01,-1.413334E-03,-1.109323E-03,4.078120E-02,-1.785625E-03,2.977821E-03},
EIRFunT = {8.567950E-01,3.354557E-03,1.047901E-03,-5.217250E-03,6.565310E-04,-1.361740E-03},
EIRFunPLR = {2.605354E-01,2.125571E-01,5.269144E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 2237kW/6.41COP/Vanes";
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes, !- Name
2275200, !- Reference Capacity {W}
6.32, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.13, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.13, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2275200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.034673E+00,-1.091064E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.326094E-01,-6.056615E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.735485E-01,2.163041E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_2275kW_6_32COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2275200,
COP_nominal = 6.32,
PLRMin = 0.13,
PLRMinUnl = 0.13,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {1.034673E+00,-1.091064E-02,9.019479E-04,9.686229E-03,-9.160783E-04,2.045641E-03},
EIRFunT = {8.326094E-01,-6.056615E-03,-3.016626E-04,-2.498578E-03,4.933363E-04,-3.125632E-04},
EIRFunPLR = {2.735485E-01,2.163041E-01,5.099054E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 2275kW/6.32COP/Vanes";
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes, !- Name
2299900, !- Reference Capacity {W}
8.10, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09085, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.23, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.23, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.23 | Minimum part unload ratio |
Real | PLRMin | 0.23 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2299900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.268137E-01,3.920902E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.178121E-01,6.561784E-03,8... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.161399E-01,4.347344E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_2300kW_8_10COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2299900,
COP_nominal = 8.10,
PLRMin = 0.23,
PLRMinUnl = 0.23,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09085,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {6.268137E-01,3.920902E-02,-5.475881E-04,3.072669E-02,-1.474615E-03,8.577783E-04},
EIRFunT = {7.178121E-01,6.561784E-03,8.193740E-06,2.319141E-02,-1.755983E-06,-8.834410E-04},
EIRFunPLR = {1.161399E-01,4.347344E-01,4.486380E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes";
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD, !- Name
2317400, !- Reference Capacity {W}
6.33, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.09085, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2317400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.33 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.277716E-01,1.018101E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.502330E-01,-2.301510E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.861441E-02,5.297727E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2317400,
COP_nominal = 6.33,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.09085,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.277716E-01,1.018101E-02,-6.282438E-04,1.337701E-02,-5.050352E-04,1.527259E-03},
EIRFunT = {3.502330E-01,-2.301510E-02,5.749596E-04,1.902421E-02,3.109974E-04,-4.714517E-04},
EIRFunPLR = {9.861441E-02,5.297727E-01,3.707229E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD";
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes, !- Name
2391300, !- Reference Capacity {W}
6.77, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06858, !- Reference Chilled Water Flow Rate {m3/s}
0.0846, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.266646E-01,-2.367443E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.036386E-01,2.524850E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_2391kW_6_77COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2391300,
COP_nominal = 6.77,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06858,
mCon_flow_nominal = 1000 * 0.0846,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {3.676388E-01,-5.087680E-02,-1.772675E-03,9.518123E-02,-3.403878E-03,4.526983E-03},
EIRFunT = {6.266646E-01,-2.367443E-02,4.031296E-04,2.827714E-02,-1.985242E-04,-1.470260E-04},
EIRFunPLR = {3.036386E-01,2.524850E-01,4.429285E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes";
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD, !- Name
2391300, !- Reference Capacity {W}
6.44, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06858, !- Reference Chilled Water Flow Rate {m3/s}
0.0846, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.230142E-01,-2.371649E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.774812E-02,2.490111E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19XR_2391kW_6_44COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2391300,
COP_nominal = 6.44,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.06858,
mCon_flow_nominal = 1000 * 0.0846,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {3.676388E-01,-5.087680E-02,-1.772675E-03,9.518123E-02,-3.403878E-03,4.526983E-03},
EIRFunT = {6.230142E-01,-2.371649E-02,3.996265E-04,2.874515E-02,-2.115103E-04,-1.526191E-04},
EIRFunPLR = {9.774812E-02,2.490111E-01,6.539378E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD";
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes, !- Name
2412400, !- Reference Capacity {W}
5.58, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.09085, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.12, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.12, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2412400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.473817E-01,8.069214E-03,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.626807E-01,-2.305674E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.472427E-01,7.531481E-01,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_2412kW_5_58COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2412400,
COP_nominal = 5.58,
PLRMin = 0.12,
PLRMinUnl = 0.12,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.09085,
mCon_flow_nominal = 1000 * 0.11356,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {7.473817E-01,8.069214E-03,8.433986E-05,1.925706E-02,-7.505775E-04,1.174526E-03},
EIRFunT = {4.626807E-01,-2.305674E-02,1.169126E-03,3.431185E-02,-3.396938E-04,-7.381352E-05},
EIRFunPLR = {2.472427E-01,7.531481E-01,8.643617E-04},
etaMotor = 1.0)
"ElectricEIRChiller York YK 2412kW/5.58COP/Vanes";
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes, !- Name
2461600, !- Reference Capacity {W}
6.67, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.07066, !- Reference Chilled Water Flow Rate {m3/s}
0.10157, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2461600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07066 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.10157 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.561527E-01,5.742999E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.462893E-01,2.854651E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.222135E-02,5.830980E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_2462kW_6_67COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2461600,
COP_nominal = 6.67,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.07066,
mCon_flow_nominal = 1000 * 0.10157,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {9.561527E-01,5.742999E-02,-4.868087E-03,1.799507E-02,-1.793848E-03,3.194186E-03},
EIRFunT = {5.462893E-01,2.854651E-02,-5.770782E-03,1.634571E-02,-2.645314E-04,2.138325E-03},
EIRFunPLR = {9.222135E-02,5.830980E-01,3.250019E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes";
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD, !- Name
2567100, !- Reference Capacity {W}
11.77, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.12113, !- Reference Chilled Water Flow Rate {m3/s}
0.15142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.11, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.11, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2567100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 11.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.12113 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.549428E-01,2.748161E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.561990E-01,-3.333063E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.039419E-01,4.184975E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_2567kW_11_77COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2567100,
COP_nominal = 11.77,
PLRMin = 0.11,
PLRMinUnl = 0.11,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.12113,
mCon_flow_nominal = 1000 * 0.15142,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {4.549428E-01,2.748161E-02,-4.298342E-03,4.363928E-02,-1.352509E-03,2.964225E-03},
EIRFunT = {4.561990E-01,-3.333063E-02,-1.763576E-03,5.624520E-02,-8.535085E-05,3.567604E-04},
EIRFunPLR = {1.039419E-01,4.184975E-01,4.774210E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD";
ElectricEIRChiller York YK 2771kW/6.84COP/VSD
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 2771kW/6.84COP/VSD, !- Name
2771100, !- Reference Capacity {W}
6.84, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.10094, !- Reference Chilled Water Flow Rate {m3/s}
0.15142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 2771kW/6.84COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2771100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.10094 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.734286E-01,4.848829E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.203736E-01,1.030460E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.653354E-02,1.737382E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_2771kW_6_84COP_VSD =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2771100,
COP_nominal = 6.84,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.10094,
mCon_flow_nominal = 1000 * 0.15142,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.734286E-01,4.848829E-02,-1.859209E-03,2.611971E-02,-1.243562E-03,7.210181E-04},
EIRFunT = {7.203736E-01,1.030460E-02,-7.854237E-04,-1.206349E-03,8.210060E-04,-1.455414E-03},
EIRFunPLR = {8.653354E-02,1.737382E-01,7.403679E-01},
etaMotor = 1.0) "ElectricEIRChiller York YK 2771kW/6.84COP/VSD";
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes, !- Name
2799200, !- Reference Capacity {W}
6.40, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.09893, !- Reference Chilled Water Flow Rate {m3/s}
0.13761, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -2799200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13761 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.210324E-01,-2.752320E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.267558E-01,-7.615857E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.023576E-01,-2.893592E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_2799kW_6_40COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -2799200,
COP_nominal = 6.40,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.09893,
mCon_flow_nominal = 1000 * 0.13761,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {2.210324E-01,-2.752320E-02,4.903763E-04,7.337449E-02,-1.919426E-03,1.935659E-03},
EIRFunT = {2.267558E-01,-7.615857E-02,2.140583E-03,7.088812E-02,-1.124968E-03,6.089843E-04},
EIRFunPLR = {3.023576E-01,-2.893592E-02,7.262269E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes";
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes, !- Name
3133300, !- Reference Capacity {W}
9.16, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.08076, !- Reference Chilled Water Flow Rate {m3/s}
0.12618, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.07, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.07, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.07 | Minimum part unload ratio |
Real | PLRMin | 0.07 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -3133300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08076 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.12618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.607419E-01,1.323998E-02,6... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.150153E-01,-3.956395E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.387579E-01,6.435208E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YT_3133kW_9_16COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -3133300,
COP_nominal = 9.16,
PLRMin = 0.07,
PLRMinUnl = 0.07,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.08076,
mCon_flow_nominal = 1000 * 0.12618,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.607419E-01,1.323998E-02,6.902287E-04,1.510969E-02,-9.443341E-04,1.484396E-03},
EIRFunT = {9.150153E-01,-3.956395E-02,1.865473E-03,1.810633E-02,2.900613E-04,-4.199110E-04},
EIRFunPLR = {1.387579E-01,6.435208E-01,2.155990E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YT 3133kW/9.16COP/Vanes";
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes, !- Name
3165000, !- Reference Capacity {W}
6.48, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
22.78, !- Reference Entering Condenser Fluid Temperature {C}
0.09085, !- Reference Chilled Water Flow Rate {m3/s}
0.13627, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -3165000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.48 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13627 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.342558E+00,7.520735E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.347904E-01,6.551597E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.054110E-01,4.090646E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -3165000,
COP_nominal = 6.48,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.09085,
mCon_flow_nominal = 1000 * 0.13627,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 22.78,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {1.342558E+00,7.520735E-02,-8.988936E-03,-3.340001E-02,-6.065934E-04,4.684791E-03},
EIRFunT = {9.347904E-01,6.551597E-02,-1.242676E-02,-2.799974E-02,3.323287E-04,4.803491E-03},
EIRFunPLR = {1.054110E-01,4.090646E-01,4.838839E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes";
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes, !- Name
4019500, !- Reference Capacity {W}
7.35, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
12.78, !- Reference Entering Condenser Fluid Temperature {C}
0.07874, !- Reference Chilled Water Flow Rate {m3/s}
0.09842, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.14, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.14, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4019500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07874 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09842 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.958422E-01,3.762768E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.322623E-01,-2.157964E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.763566E-02,5.964012E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4019500,
COP_nominal = 7.35,
PLRMin = 0.14,
PLRMinUnl = 0.14,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.07874,
mCon_flow_nominal = 1000 * 0.09842,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 12.78,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {8.958422E-01,3.762768E-02,-3.550080E-03,-4.322645E-03,-1.194933E-03,3.006034E-03},
EIRFunT = {9.322623E-01,-2.157964E-02,-1.435883E-03,1.379036E-02,-1.491048E-04,1.302075E-03},
EIRFunPLR = {5.763566E-02,5.964012E-01,3.473613E-01},
etaMotor = 1.0)
"ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes";
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes, !- Name
4395800, !- Reference Capacity {W}
6.63, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.19558, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.41, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.41, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4395800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.63 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.693621E-01,-7.284715E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.913358E-01,-5.974145E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.021070E-01,3.103971E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4396kW_6_63COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4395800,
COP_nominal = 6.63,
PLRMin = 0.41,
PLRMinUnl = 0.41,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.19558,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {3.693621E-01,-7.284715E-02,-4.871930E-03,1.223355E-01,-5.368259E-03,1.035036E-02},
EIRFunT = {5.913358E-01,-5.974145E-02,8.176561E-04,3.987353E-02,-8.176694E-04,1.457994E-03},
EIRFunPLR = {3.021070E-01,3.103971E-02,6.669726E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4396kW/6.63COP/Vanes";
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes, !- Name
4476700, !- Reference Capacity {W}
6.64, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.19558, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.41, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.41, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4476700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.844230E-01,-9.879643E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.264570E-01,-3.391606E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.767206E-01,1.074393E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4477kW_6_64COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4476700,
COP_nominal = 6.64,
PLRMin = 0.41,
PLRMinUnl = 0.41,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.19558,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {4.844230E-01,-9.879643E-02,-2.516527E-03,1.144722E-01,-5.101526E-03,1.022861E-02},
EIRFunT = {4.264570E-01,-3.391606E-02,-1.991396E-03,5.032090E-02,-1.140771E-03,1.814692E-03},
EIRFunPLR = {2.767206E-01,1.074393E-01,6.145706E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4477kW/6.64COP/Vanes";
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes, !- Name
4515400, !- Reference Capacity {W}
6.22, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.19558, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.40, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.40, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4515400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.22 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.732405E-01,-7.176618E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.908290E-01,1.028668E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.870815E-01,3.951784E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4515kW_6_22COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4515400,
COP_nominal = 6.22,
PLRMin = 0.40,
PLRMinUnl = 0.40,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.19558,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {3.732405E-01,-7.176618E-03,-2.588788E-03,5.381225E-02,-1.773937E-03,3.509721E-03},
EIRFunT = {5.908290E-01,1.028668E-02,-4.718838E-04,1.220347E-02,4.166971E-04,-1.484327E-03},
EIRFunPLR = {2.870815E-01,3.951784E-01,3.177735E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4515kW/6.22COP/Vanes";
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes, !- Name
4536500, !- Reference Capacity {W}
6.28, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.19558, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.40, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.40, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4536500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.418253E-01,8.142292E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.709829E-01,-2.257680E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.528426E-01,2.920280E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4537kW_6_28COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4536500,
COP_nominal = 6.28,
PLRMin = 0.40,
PLRMinUnl = 0.40,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.19558,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {9.418253E-01,8.142292E-02,-9.532713E-03,3.185018E-02,-2.583116E-03,5.294716E-03},
EIRFunT = {7.709829E-01,-2.257680E-02,2.492708E-04,7.635418E-03,3.376522E-04,-3.614203E-04},
EIRFunPLR = {2.528426E-01,2.920280E-01,4.533447E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4537kW/6.28COP/Vanes";
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes, !- Name
4610300, !- Reference Capacity {W}
6.34, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.19129, !- Reference Chilled Water Flow Rate {m3/s}
0.24757, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4610300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19129 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24757 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.614836E-01,-3.988130E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.415078E-01,-4.779029E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.026691E-01,2.922585E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_4610kW_6_34COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4610300,
COP_nominal = 6.34,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.19129,
mCon_flow_nominal = 1000 * 0.24757,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 18.33,
TConEntMax = 273.15 + 29.44,
capFunT = {8.614836E-01,-3.988130E-03,-1.643579E-03,8.882312E-03,-3.930474E-04,1.593969E-03},
EIRFunT = {7.415078E-01,-4.779029E-02,-1.028085E-03,1.423650E-02,1.304315E-04,9.170177E-04},
EIRFunPLR = {2.026691E-01,2.922585E-01,5.044422E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes";
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes, !- Name
4666600, !- Reference Capacity {W}
6.16, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.19558, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.40, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.40, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4666600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {4.084496E-01,-4.396326E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.214788E-01,-8.218594E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.771252E-01,2.854188E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19EX_4667kW_6_16COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4666600,
COP_nominal = 6.16,
PLRMin = 0.40,
PLRMinUnl = 0.40,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.19558,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {4.084496E-01,-4.396326E-02,-2.112120E-03,8.225310E-02,-3.066058E-03,5.257550E-03},
EIRFunT = {5.214788E-01,-8.218594E-03,-3.068358E-05,2.152332E-02,1.203908E-04,-7.167755E-04},
EIRFunPLR = {3.771252E-01,2.854188E-02,5.928670E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes";
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes, !- Name
4677100, !- Reference Capacity {W}
6.27, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.20138, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.41, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.41, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4677100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.20138 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.449416E-01,-2.116553E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.283132E-01,-3.030491E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.531562E-01,-2.126229E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CVHF_4677kW_6_27COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4677100,
COP_nominal = 6.27,
PLRMin = 0.41,
PLRMinUnl = 0.41,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.20138,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {8.449416E-01,-2.116553E-02,6.121458E-03,7.120879E-03,-1.798959E-04,-1.349219E-04},
EIRFunT = {8.283132E-01,-3.030491E-02,4.164965E-03,-3.278448E-03,6.762508E-04,-1.107762E-03},
EIRFunPLR = {3.531562E-01,-2.126229E-01,8.597400E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes";
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes, !- Name
4965500, !- Reference Capacity {W}
6.05, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.21198, !- Reference Chilled Water Flow Rate {m3/s}
0.26498, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.12, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.12, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4965500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.21198 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.746486E-01,-3.051134E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.229769E-01,-8.128614E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.416463E-01,1.947185E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4966kW_6_05COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4965500,
COP_nominal = 6.05,
PLRMin = 0.12,
PLRMinUnl = 0.12,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.21198,
mCon_flow_nominal = 1000 * 0.26498,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {5.746486E-01,-3.051134E-02,-1.964984E-04,3.309783E-02,-9.174714E-04,2.287276E-03},
EIRFunT = {8.229769E-01,-8.128614E-03,1.110212E-03,-3.521351E-03,6.129803E-04,-9.170063E-04},
EIRFunPLR = {3.416463E-01,1.947185E-01,4.640804E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4966kW/6.05COP/Vanes";
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes, !- Name
4969000, !- Reference Capacity {W}
7.14, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.17665, !- Reference Chilled Water Flow Rate {m3/s}
0.26498, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.16, !- Minimum Part Load Ratio
1.07, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.16, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.817577E-01,-1.012013E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.382162E-01,-5.847442E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.259512E-01,2.320151E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4969kW_7_14COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4969000,
COP_nominal = 7.14,
PLRMin = 0.16,
PLRMinUnl = 0.16,
PLRMax = 1.07,
mEva_flow_nominal = 1000 * 0.17665,
mCon_flow_nominal = 1000 * 0.26498,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {7.817577E-01,-1.012013E-01,-1.584389E-03,7.928475E-02,-3.674093E-03,7.999392E-03},
EIRFunT = {7.382162E-01,-5.847442E-02,1.117191E-03,2.168089E-02,-2.189722E-04,1.036877E-03},
EIRFunPLR = {2.259512E-01,2.320151E-01,5.423771E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4969kW/7.14COP/Vanes";
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes, !- Name
4969000, !- Reference Capacity {W}
7.07, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.17665, !- Reference Chilled Water Flow Rate {m3/s}
0.26498, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.16, !- Minimum Part Load Ratio
1.06, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.16, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.07 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.803605E-01,-9.685535E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.220087E-01,-4.480691E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.308102E-01,1.802734E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_4969kW_7_07COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4969000,
COP_nominal = 7.07,
PLRMin = 0.16,
PLRMinUnl = 0.16,
PLRMax = 1.06,
mEva_flow_nominal = 1000 * 0.17665,
mCon_flow_nominal = 1000 * 0.26498,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {1.803605E-01,-9.685535E-02,-5.831135E-03,1.341596E-01,-5.279908E-03,1.045372E-02},
EIRFunT = {7.220087E-01,-4.480691E-02,9.621038E-06,2.084835E-02,-2.615973E-04,1.188407E-03},
EIRFunPLR = {2.308102E-01,1.802734E-01,5.894894E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 4969kW/7.07COP/Vanes";
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes, !- Name
4997200, !- Reference Capacity {W}
6.40, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.19558, !- Reference Chilled Water Flow Rate {m3/s}
0.24605, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.40, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.40, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -4997200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {7.122762E-02,2.550937E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.685097E-01,-2.541433E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.364887E-01,2.122607E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -4997200,
COP_nominal = 6.40,
PLRMin = 0.40,
PLRMinUnl = 0.40,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.19558,
mCon_flow_nominal = 1000 * 0.24605,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.67,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.67,
capFunT = {7.122762E-02,2.550937E-03,-9.679482E-03,9.391204E-02,-3.505261E-03,7.309943E-03},
EIRFunT = {6.685097E-01,-2.541433E-02,3.334144E-03,1.002578E-02,5.753780E-04,-1.801340E-03},
EIRFunPLR = {3.364887E-01,2.122607E-01,4.486522E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes";
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes, !- Name
5148400, !- Reference Capacity {W}
6.34, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.18283, !- Reference Chilled Water Flow Rate {m3/s}
0.25526, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -5148400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25526 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {3.564454E-01,2.020689E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.426449E-01,3.961314E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.883602E-01,5.018646E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19EX_5148kW_6_34COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -5148400,
COP_nominal = 6.34,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.18283,
mCon_flow_nominal = 1000 * 0.25526,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {3.564454E-01,2.020689E-02,-6.286899E-03,5.760425E-02,-2.102376E-03,4.126650E-03},
EIRFunT = {5.426449E-01,3.961314E-03,-1.195821E-04,1.609421E-02,3.089258E-04,-1.129525E-03},
EIRFunPLR = {1.883602E-01,5.018646E-01,3.089569E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes";
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes, !- Name
5169500, !- Reference Capacity {W}
7.15, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.17665, !- Reference Chilled Water Flow Rate {m3/s}
0.26498, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.15, !- Minimum Part Load Ratio
1.08, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.15, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -5169500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.675697E-01,-1.191228E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.894383E-01,-2.926530E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.497273E-01,1.011288E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_5170kW_7_15COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -5169500,
COP_nominal = 7.15,
PLRMin = 0.15,
PLRMinUnl = 0.15,
PLRMax = 1.08,
mEva_flow_nominal = 1000 * 0.17665,
mCon_flow_nominal = 1000 * 0.26498,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {1.675697E-01,-1.191228E-01,-4.328384E-03,1.355905E-01,-5.171251E-03,1.039840E-02},
EIRFunT = {5.894383E-01,-2.926530E-02,-1.900238E-03,2.849479E-02,-5.105015E-04,1.702334E-03},
EIRFunPLR = {2.497273E-01,1.011288E-01,6.499847E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 5170kW/7.15COP/Vanes";
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes, !- Name
5208200, !- Reference Capacity {W}
6.88, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.18283, !- Reference Chilled Water Flow Rate {m3/s}
0.25293, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -5208200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.88 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25293 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.563516E-01,-4.106264E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.198204E-01,-1.523340E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.334262E-01,3.926783E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19EX_5208kW_6_88COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -5208200,
COP_nominal = 6.88,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.18283,
mCon_flow_nominal = 1000 * 0.25293,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {5.563516E-01,-4.106264E-02,-3.164992E-03,5.722234E-02,-2.313857E-03,5.377616E-03},
EIRFunT = {5.198204E-01,-1.523340E-02,-6.391523E-04,2.170049E-02,2.423693E-05,1.432604E-04},
EIRFunPLR = {2.334262E-01,3.926783E-01,3.731320E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes";
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes, !- Name
5464900, !- Reference Capacity {W}
6.94, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.18296, !- Reference Chilled Water Flow Rate {m3/s}
0.27444, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.14, !- Minimum Part Load Ratio
1.07, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.14, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -5464900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.092441E-01,-1.225892E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.396022E-01,-5.954060E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.795792E-01,7.872758E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_5465kW_6_94COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -5464900,
COP_nominal = 6.94,
PLRMin = 0.14,
PLRMinUnl = 0.14,
PLRMax = 1.07,
mEva_flow_nominal = 1000 * 0.18296,
mCon_flow_nominal = 1000 * 0.27444,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {1.092441E-01,-1.225892E-01,-2.802873E-03,1.324138E-01,-4.714937E-03,9.205744E-03},
EIRFunT = {6.396022E-01,-5.954060E-02,5.884523E-04,3.170651E-02,-5.088216E-04,1.460759E-03},
EIRFunPLR = {2.795792E-01,7.872758E-02,6.424321E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 5465kW/6.94COP/Vanes";
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes, !- Name
5549300, !- Reference Capacity {W}
6.50, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.18296, !- Reference Chilled Water Flow Rate {m3/s}
0.27444, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.14, !- Minimum Part Load Ratio
1.05, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.14, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -5549300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-1.402079E-01,1.836029E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.989980E-01,-8.246157E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.336623E-01,1.901320E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YK_5549kW_6_50COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -5549300,
COP_nominal = 6.50,
PLRMin = 0.14,
PLRMinUnl = 0.14,
PLRMax = 1.05,
mEva_flow_nominal = 1000 * 0.18296,
mCon_flow_nominal = 1000 * 0.27444,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 26.11,
capFunT = {-1.402079E-01,1.836029E-02,-2.390588E-03,1.207956E-01,-3.563147E-03,2.024532E-03},
EIRFunT = {4.989980E-01,-8.246157E-02,6.047523E-03,5.168793E-02,-8.552445E-04,6.275326E-05},
EIRFunPLR = {2.336623E-01,1.901320E-01,5.749473E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YK 5549kW/6.50COP/Vanes";
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes, !- Name
5651300, !- Reference Capacity {W}
5.50, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.18927, !- Reference Chilled Water Flow Rate {m3/s}
0.18927, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.19, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.19, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -5651300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18927 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.18927 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.299676E+00,1.790645E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.853207E-01,-1.652255E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.629327E-01,5.709336E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -5651300,
COP_nominal = 5.50,
PLRMin = 0.19,
PLRMinUnl = 0.19,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.18927,
mCon_flow_nominal = 1000 * 0.18927,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 29.44,
capFunT = {1.299676E+00,1.790645E-02,-2.522300E-03,2.536423E-03,-1.128041E-03,3.003265E-03},
EIRFunT = {7.853207E-01,-1.652255E-02,-3.294526E-04,4.569179E-03,1.964013E-04,1.761497E-04},
EIRFunPLR = {1.629327E-01,5.709336E-01,2.659304E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes";
DOE-2 Centrifugal/5.50COP
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
DOE-2 Centrifugal/5.50COP, !- Name
Autosize, !- Reference Capacity {W}
5.5, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.4, !- Reference Entering Condenser Fluid Temperature {C}
Autosize, !- Reference Chilled Water Flow Rate {m3/s}
Autosize, !- Reference Condenser Water Flow Rate {m3/s}
DOE-2 Centrifugal/5.50COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name
DOE-2 Centrifugal/5.50COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
DOE-2 Centrifugal/5.50COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.1, !- Minimum Part Load Ratio
1.0, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.2, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow; !- Chiller Flow Mode
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.0 | Maximum part load ratio |
Real | PLRMinUnl | 0.2 | Minimum part unload ratio |
Real | PLRMin | 0.1 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.5 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {0.257896E+00,0.389016E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.933884E+00,-0.582120E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.222903,0.313387,0.463710} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] |
Modelica definition
record DOE_2_Centrifugal_5_50COP =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -100000.0,
COP_nominal = 5.5,
PLRMin = 0.1,
PLRMinUnl = 0.2,
PLRMax = 1.0,
mEva_flow_nominal = 1000 * 0.0022,
mCon_flow_nominal = 1000 * 0.0041,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.4,
TEvaLvgMin = 273.15 + 5.0,
TEvaLvgMax = 273.15 + 10.0,
TConEntMin = 273.15 + 24.0,
TConEntMax = 273.15 + 35.0,
capFunT = {0.257896E+00,0.389016E-01,-0.217080E-03,0.468684E-01,-0.942840E-03,-0.343440E-03},
EIRFunT = {0.933884E+00,-0.582120E-01,0.450036E-02,0.243000E-02,0.486000E-03,-0.121500E-02},
EIRFunPLR = {0.222903,0.313387,0.463710},
etaMotor = 1.0) "DOE-2 Centrifugal/5.50COP";
ElectricEIRChiller Multistack MS 172kW/3.67COP/None
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Multistack MS 172kW/3.67COP/None, !- Name
172300, !- Reference Capacity {W}
3.67, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
18.33, !- Reference Entering Condenser Fluid Temperature {C}
0.00738, !- Reference Chilled Water Flow Rate {m3/s}
0.00959, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Multistack MS 172kW/3.67COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.40, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.40, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -172300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00738 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.00959 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.839419E-01,1.094957E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.396181E-01,-5.754225E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.747786E-03,1.072374E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Multistack_MS_172kW_3_67COP_None =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -172300,
COP_nominal = 3.67,
PLRMin = 0.40,
PLRMinUnl = 0.40,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.00738,
mCon_flow_nominal = 1000 * 0.00959,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 18.33,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 18.33,
TConEntMax = 273.15 + 35.00,
capFunT = {9.839419E-01,1.094957E-01,-4.547595E-03,-2.311886E-02,2.595943E-04,-5.093307E-04},
EIRFunT = {9.396181E-01,-5.754225E-02,2.561677E-03,1.081450E-02,1.839935E-04,5.269319E-05},
EIRFunPLR = {4.747786E-03,1.072374E+00,-7.758317E-02},
etaMotor = 1.0)
"ElectricEIRChiller Multistack MS 172kW/3.67COP/None";
DOE-2 Reciprocating/3.67COP
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
DOE-2 Reciprocating/3.67COP, !- Name
Autosize, !- Reference Capacity {W}
3.67, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.4, !- Reference Entering Condenser Fluid Temperature {C}
Autosize, !- Reference Chilled Water Flow Rate {m3/s}
Autosize, !- Reference Condenser Water Flow Rate {m3/s}
DOE-2 Reciprocating/3.67COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name
DOE-2 Reciprocating/3.67COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
DOE-2 Reciprocating/3.67COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.1, !- Minimum Part Load Ratio
1.0, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.2, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow; !- Chiller Flow Mode
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.0 | Maximum part load ratio |
Real | PLRMinUnl | 0.2 | Minimum part unload ratio |
Real | PLRMin | 0.1 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0044 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {0.507883E+00,0.145228E+00,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.103076E+01,-0.103536E+00,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.088065,1.137742,-0.225806} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] |
Modelica definition
record DOE_2_Reciprocating_3_67COP =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -100000.0,
COP_nominal = 3.67,
PLRMin = 0.1,
PLRMinUnl = 0.2,
PLRMax = 1.0,
mEva_flow_nominal = 1000 * 0.0022,
mCon_flow_nominal = 1000 * 0.0044,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.4,
TEvaLvgMin = 273.15 + 5.0,
TEvaLvgMax = 273.15 + 10.0,
TConEntMin = 273.15 + 24.0,
TConEntMax = 273.15 + 35.0,
capFunT = {0.507883E+00,0.145228E+00,-0.625644E-02,-0.111780E-02,-0.129600E-03,-0.281880E-03},
EIRFunT = {0.103076E+01,-0.103536E+00,0.710208E-02,0.931860E-02,0.317520E-03,-0.104328E-02},
EIRFunPLR = {0.088065,1.137742,-0.225806},
etaMotor = 1.0) "DOE-2 Reciprocating/3.67COP";
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve, !- Name
383300, !- Reference Capacity {W}
4.17, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.0165, !- Reference Chilled Water Flow Rate {m3/s}
0.02063, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.25, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.25, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -383300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.17 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0165 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02063 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.830684E-01,3.676199E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.228513E-01,-8.700783E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.295553E-02,9.114398E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTWA_383kW_4_17COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -383300,
COP_nominal = 4.17,
PLRMin = 0.25,
PLRMinUnl = 0.25,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.0165,
mCon_flow_nominal = 1000 * 0.02063,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 23.89,
TConEntMax = 273.15 + 35.00,
capFunT = {9.830684E-01,3.676199E-02,5.307995E-05,-4.828624E-03,-4.755963E-05,-2.377982E-04},
EIRFunT = {6.228513E-01,-8.700783E-03,9.719796E-04,5.184584E-03,4.951699E-04,-9.632370E-04},
EIRFunPLR = {3.295553E-02,9.114398E-01,5.565265E-02},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve";
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve, !- Name
531000, !- Reference Capacity {W}
4.83, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.0135, !- Reference Chilled Water Flow Rate {m3/s}
0.01577, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -531000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.83 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0135 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.434012E-01,1.630729E-02,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.524778E-01,1.045156E-04,6... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.980020E-01,2.733157E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHB_531kW_4_83COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -531000,
COP_nominal = 4.83,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.0135,
mCon_flow_nominal = 1000 * 0.01577,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.434012E-01,1.630729E-02,8.621098E-04,3.242384E-03,-3.003973E-04,1.931126E-04},
EIRFunT = {4.524778E-01,1.045156E-04,6.932509E-05,2.044980E-02,3.672953E-04,-1.099051E-03},
EIRFunPLR = {1.980020E-01,2.733157E-01,5.277318E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve";
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve, !- Name
538000, !- Reference Capacity {W}
5.12, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.01375, !- Reference Chilled Water Flow Rate {m3/s}
0.01956, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -538000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.12 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01375 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.344780E-01,2.760000E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.455087E-01,-9.301201E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.816950E-01,3.731838E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHB_538kW_5_12COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -538000,
COP_nominal = 5.12,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.01375,
mCon_flow_nominal = 1000 * 0.01956,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.344780E-01,2.760000E-02,3.781512E-04,-9.176470E-04,-1.270588E-04,-4.235294E-05},
EIRFunT = {5.455087E-01,-9.301201E-03,5.012361E-04,1.432870E-02,4.719381E-04,-8.937669E-04},
EIRFunPLR = {1.816950E-01,3.731838E-01,4.448009E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve";
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve, !- Name
541500, !- Reference Capacity {W}
5.26, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
21.11, !- Reference Entering Condenser Fluid Temperature {C}
0.01363, !- Reference Chilled Water Flow Rate {m3/s}
0.01577, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -541500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01363 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.226438E-01,2.878831E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.953775E-01,-1.359340E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.057645E-01,-1.548084E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHB_542kW_5_26COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -541500,
COP_nominal = 5.26,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.01363,
mCon_flow_nominal = 1000 * 0.01577,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 21.11,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.226438E-01,2.878831E-02,3.756957E-04,-1.963636E-03,-8.415584E-05,-1.262338E-04},
EIRFunT = {4.953775E-01,-1.359340E-02,5.784637E-04,2.778142E-02,1.747259E-04,-8.590768E-04},
EIRFunPLR = {3.057645E-01,-1.548084E-01,8.484536E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve";
ElectricEIRChiller York YS 672kW/7.90COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 672kW/7.90COP/Valve, !- Name
671600, !- Reference Capacity {W}
7.90, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
15.56, !- Reference Entering Condenser Fluid Temperature {C}
0.01514, !- Reference Chilled Water Flow Rate {m3/s}
0.0241, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 672kW/7.90COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -671600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.274375E-01,2.846559E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.069331E-01,-6.420922E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.936152E-01,3.375574E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_672kW_7_90COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -671600,
COP_nominal = 7.90,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.01514,
mCon_flow_nominal = 1000 * 0.0241,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 15.56,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.274375E-01,2.846559E-02,4.024428E-04,-5.932730E-03,-1.067418E-05,-2.199015E-04},
EIRFunT = {4.069331E-01,-6.420922E-03,2.689257E-04,4.500373E-02,1.583981E-04,-1.284532E-03},
EIRFunPLR = {1.936152E-01,3.375574E-01,4.704892E-01},
etaMotor = 1.0) "ElectricEIRChiller York YS 672kW/7.90COP/Valve";
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve, !- Name
685700, !- Reference Capacity {W}
5.91, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
23.74, !- Reference Entering Condenser Fluid Temperature {C}
0.0571, !- Reference Chilled Water Flow Rate {m3/s}
0.03255, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -685700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.91 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03255 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {2.903523E-01,-2.676742E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.014060E-01,1.561000E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.113934E-01,4.190226E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_686kW_5_91COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -685700,
COP_nominal = 5.91,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.0571,
mCon_flow_nominal = 1000 * 0.03255,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 23.74,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {2.903523E-01,-2.676742E-02,-4.771695E-03,8.162394E-02,-3.028217E-03,5.712524E-03},
EIRFunT = {5.014060E-01,1.561000E-03,-1.347980E-04,1.525028E-02,5.701374E-04,-1.221374E-03},
EIRFunPLR = {2.113934E-01,4.190226E-01,3.686143E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve";
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve, !- Name
706800, !- Reference Capacity {W}
7.77, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
15.56, !- Reference Entering Condenser Fluid Temperature {C}
0.04921, !- Reference Chilled Water Flow Rate {m3/s}
0.03268, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.28, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.28, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -706800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03268 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.362925E-01,2.940722E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.497944E-01,6.883157E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.997099E-01,6.754676E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 11.11 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -706800,
COP_nominal = 7.77,
PLRMin = 0.28,
PLRMinUnl = 0.28,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.04921,
mCon_flow_nominal = 1000 * 0.03268,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 15.56,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 11.11,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.362925E-01,2.940722E-02,5.726999E-04,-5.696483E-03,-5.569609E-05,-1.708132E-04},
EIRFunT = {6.497944E-01,6.883157E-03,-5.277681E-04,1.725788E-02,6.779317E-04,-1.244055E-03},
EIRFunPLR = {1.997099E-01,6.754676E-01,1.243767E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve";
ElectricEIRChiller York YS 756kW/7.41COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 756kW/7.41COP/Valve, !- Name
756000, !- Reference Capacity {W}
7.41, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
16.06, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 756kW/7.41COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.11, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.11, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 16.06 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -756000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.432455E-01,2.794778E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.917947E-01,-1.929936E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.929778E-01,1.673799E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 16.06 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_756kW_7_41COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -756000,
COP_nominal = 7.41,
PLRMin = 0.11,
PLRMinUnl = 0.11,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 16.06,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 16.06,
TConEntMax = 273.15 + 23.89,
capFunT = {9.432455E-01,2.794778E-02,2.937753E-04,-5.818549E-03,-3.764392E-05,-5.777607E-05},
EIRFunT = {6.917947E-01,-1.929936E-02,1.450011E-03,1.795987E-02,9.301685E-04,-1.755165E-03},
EIRFunPLR = {2.929778E-01,1.673799E-02,6.881229E-01},
etaMotor = 1.0) "ElectricEIRChiller York YS 756kW/7.41COP/Valve";
ElectricEIRChiller York YS 781kW/5.42COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 781kW/5.42COP/Valve, !- Name
780700, !- Reference Capacity {W}
5.42, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.01893, !- Reference Chilled Water Flow Rate {m3/s}
0.03785, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 781kW/5.42COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -780700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.002148E+00,3.300191E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.475957E-01,-1.054652E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.519108E-01,2.756914E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_781kW_5_42COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -780700,
COP_nominal = 5.42,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.01893,
mCon_flow_nominal = 1000 * 0.03785,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 35.00,
capFunT = {1.002148E+00,3.300191E-02,3.741670E-04,-5.925358E-03,-2.599267E-05,-2.172126E-04},
EIRFunT = {4.475957E-01,-1.054652E-02,7.126870E-04,1.158632E-02,5.151510E-04,-9.831355E-04},
EIRFunPLR = {2.519108E-01,2.756914E-01,4.725826E-01},
etaMotor = 1.0) "ElectricEIRChiller York YS 781kW/5.42COP/Valve";
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve, !- Name
829900, !- Reference Capacity {W}
6.97, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.03186, !- Reference Chilled Water Flow Rate {m3/s}
0.04744, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -829900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.97 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.198506E-01,4.299516E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.610959E-01,-1.560459E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.307464E-01,7.784162E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 14.17 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_830kW_6_97COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -829900,
COP_nominal = 6.97,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.03186,
mCon_flow_nominal = 1000 * 0.04744,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 14.17,
TConEntMax = 273.15 + 23.89,
capFunT = {8.198506E-01,4.299516E-03,-2.451574E-04,1.431034E-02,-3.586302E-04,2.510412E-04},
EIRFunT = {4.610959E-01,-1.560459E-02,-2.737454E-04,2.650593E-02,-7.789498E-05,1.855843E-04},
EIRFunPLR = {2.307464E-01,7.784162E-01,-7.516503E-03},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve";
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve, !- Name
861500, !- Reference Capacity {W}
6.11, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.04296, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-3.646458E-02,-6.061334E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.420642E-01,-2.110032E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.292819E-01,3.662723E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_862kW_6_11COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -861500,
COP_nominal = 6.11,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.04296,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {-3.646458E-02,-6.061334E-02,-3.708583E-03,1.197997E-01,-3.723397E-03,5.368766E-03},
EIRFunT = {5.420642E-01,-2.110032E-02,1.513908E-03,2.067897E-02,5.287518E-04,-1.630330E-03},
EIRFunPLR = {2.292819E-01,3.662723E-01,4.032019E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve";
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve, !- Name
861500, !- Reference Capacity {W}
6.84, !- Reference COP {W/W}
9.69, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.06782, !- Reference Chilled Water Flow Rate {m3/s}
0.04296, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.69 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {-4.535842E-02,-6.253871E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.930611E-01,-2.082914E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.145826E-01,7.340475E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_862kW_6_84COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -861500,
COP_nominal = 6.84,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.06782,
mCon_flow_nominal = 1000 * 0.04296,
TEvaLvg_nominal = 273.15 + 9.69,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {-4.535842E-02,-6.253871E-02,-3.623064E-03,1.218299E-01,-3.793440E-03,5.404739E-03},
EIRFunT = {5.930611E-01,-2.082914E-02,1.600282E-03,2.352564E-02,5.992247E-04,-1.907335E-03},
EIRFunPLR = {1.145826E-01,7.340475E-01,1.507744E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve";
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve, !- Name
865100, !- Reference Capacity {W}
6.05, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.03716, !- Reference Chilled Water Flow Rate {m3/s}
0.04366, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -865100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03716 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04366 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.079758E-01,-2.344768E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.437328E-01,7.625344E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.545235E-01,3.104981E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_865kW_6_05COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -865100,
COP_nominal = 6.05,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03716,
mCon_flow_nominal = 1000 * 0.04366,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 3.33,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {5.079758E-01,-2.344768E-02,-3.296630E-03,3.508384E-02,-8.359630E-04,2.585294E-03},
EIRFunT = {5.437328E-01,7.625344E-03,-9.201579E-05,1.339616E-03,8.286757E-04,-1.543530E-03},
EIRFunPLR = {2.545235E-01,3.104981E-01,4.347781E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve";
ElectricEIRChiller York YS 879kW/5.82COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 879kW/5.82COP/Valve, !- Name
879100, !- Reference Capacity {W}
5.82, !- Reference COP {W/W}
4.44, !- Reference Leaving Chilled Water Temperature {C}
26.11, !- Reference Entering Condenser Fluid Temperature {C}
0.03785, !- Reference Chilled Water Flow Rate {m3/s}
0.04732, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 879kW/5.82COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -879100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.82 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.031429E+00,3.364723E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.595308E-01,-1.087985E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.029493E-01,3.223124E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_879kW_5_82COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -879100,
COP_nominal = 5.82,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.03785,
mCon_flow_nominal = 1000 * 0.04732,
TEvaLvg_nominal = 273.15 + 4.44,
TConEnt_nominal = 273.15 + 26.11,
TEvaLvgMin = 273.15 + 3.33,
TEvaLvgMax = 273.15 + 7.78,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 29.44,
capFunT = {1.031429E+00,3.364723E-02,-2.735093E-04,-3.789167E-03,-1.553912E-04,2.782117E-04},
EIRFunT = {5.595308E-01,-1.087985E-02,8.721022E-04,1.010347E-02,5.087454E-04,-1.211319E-03},
EIRFunPLR = {3.029493E-01,3.223124E-01,3.751948E-01},
etaMotor = 1.0) "ElectricEIRChiller York YS 879kW/5.82COP/Valve";
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve, !- Name
1009200, !- Reference Capacity {W}
5.37, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
24.86, !- Reference Entering Condenser Fluid Temperature {C}
0.03186, !- Reference Chilled Water Flow Rate {m3/s}
0.04618, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.86 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1009200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.37 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.134633E+00,3.267210E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.383883E-01,7.754235E-03,6... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.316727E-01,1.013111E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 19.97 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.86 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHC_1009kW_5_37COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1009200,
COP_nominal = 5.37,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.03186,
mCon_flow_nominal = 1000 * 0.04618,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 24.86,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 19.97,
TConEntMax = 273.15 + 24.86,
capFunT = {1.134633E+00,3.267210E-02,5.266344E-04,-1.076173E-02,-4.853769E-05,-2.569325E-04},
EIRFunT = {4.383883E-01,7.754235E-03,6.353809E-04,-2.951880E-03,1.270756E-03,-1.541831E-03},
EIRFunPLR = {1.316727E-01,1.013111E+00,-1.413213E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve";
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve, !- Name
1051400, !- Reference Capacity {W}
5.05, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.04527, !- Reference Chilled Water Flow Rate {m3/s}
0.05659, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1051400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04527 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05659 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.482157E-01,3.306737E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.904181E-01,-5.530317E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.590465E-01,2.148987E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1051400,
COP_nominal = 5.05,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.04527,
mCon_flow_nominal = 1000 * 0.05659,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 23.89,
TConEntMax = 273.15 + 35.00,
capFunT = {9.482157E-01,3.306737E-02,-6.450072E-05,-3.756522E-03,-6.501672E-05,2.517986E-15},
EIRFunT = {4.904181E-01,-5.530317E-03,1.209907E-03,9.122333E-03,5.923591E-04,-1.469958E-03},
EIRFunPLR = {2.590465E-01,2.148987E-01,5.265039E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve";
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve, !- Name
1062000, !- Reference Capacity {W}
5.50, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.04573, !- Reference Chilled Water Flow Rate {m3/s}
0.05716, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1062000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04573 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05716 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.025695E+00,2.327484E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.634070E-01,-7.025220E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.576261E-01,3.416910E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1062000,
COP_nominal = 5.50,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.04573,
mCon_flow_nominal = 1000 * 0.05716,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 21.11,
TConEntMax = 273.15 + 29.44,
capFunT = {1.025695E+00,2.327484E-02,-4.693708E-03,-7.092715E-03,-3.754967E-04,2.843046E-03},
EIRFunT = {2.634070E-01,-7.025220E-03,-4.942613E-04,2.516931E-02,1.712769E-04,-4.309735E-04},
EIRFunPLR = {2.576261E-01,3.416910E-01,4.007672E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve";
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve, !- Name
1065500, !- Reference Capacity {W}
5.73, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
25.28, !- Reference Entering Condenser Fluid Temperature {C}
0.05142, !- Reference Chilled Water Flow Rate {m3/s}
0.04416, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.30, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.30, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 25.28 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1065500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05142 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.062396E+00,4.575299E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.003080E-01,3.783201E-03,9... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.007344E-01,1.119205E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 20.07 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 25.28 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1065500,
COP_nominal = 5.73,
PLRMin = 0.30,
PLRMinUnl = 0.30,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.05142,
mCon_flow_nominal = 1000 * 0.04416,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 25.28,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 20.07,
TConEntMax = 273.15 + 25.28,
capFunT = {1.062396E+00,4.575299E-02,2.802795E-04,-8.802343E-03,-3.127891E-05,-5.937227E-04},
EIRFunT = {9.003080E-01,3.783201E-03,9.815780E-04,-4.051727E-02,2.037095E-03,-1.619326E-03},
EIRFunPLR = {1.007344E-01,1.119205E+00,-2.173230E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve";
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve, !- Name
1093600, !- Reference Capacity {W}
6.55, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
23.33, !- Reference Entering Condenser Fluid Temperature {C}
0.04921, !- Reference Chilled Water Flow Rate {m3/s}
0.04524, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.25, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.25, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.33 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1093600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04524 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.643756E-01,3.820069E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.579136E-01,-1.133448E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.626466E-01,7.903550E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_RTHC_1094kW_6_55COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1093600,
COP_nominal = 6.55,
PLRMin = 0.25,
PLRMinUnl = 0.25,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.04921,
mCon_flow_nominal = 1000 * 0.04524,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 23.33,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.643756E-01,3.820069E-02,4.611891E-04,-5.174840E-03,-5.784404E-05,-2.944185E-04},
EIRFunT = {6.579136E-01,-1.133448E-02,6.497057E-04,7.318160E-03,6.167738E-04,-9.553369E-04},
EIRFunPLR = {1.626466E-01,7.903550E-01,4.770888E-02},
etaMotor = 1.0)
"ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve";
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve, !- Name
1107700, !- Reference Capacity {W}
6.92, !- Reference COP {W/W}
8.97, !- Reference Leaving Chilled Water Temperature {C}
23.74, !- Reference Entering Condenser Fluid Temperature {C}
0.0571, !- Reference Chilled Water Flow Rate {m3/s}
0.05142, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1107700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.97 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {6.631328E-01,-1.027433E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.668296E-01,-2.800906E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.370745E-01,8.374817E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_1108kW_6_92COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1107700,
COP_nominal = 6.92,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.0571,
mCon_flow_nominal = 1000 * 0.05142,
TEvaLvg_nominal = 273.15 + 8.97,
TConEnt_nominal = 273.15 + 23.74,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {6.631328E-01,-1.027433E-02,-5.388040E-04,3.320295E-02,-1.304714E-03,2.169498E-03},
EIRFunT = {5.668296E-01,-2.800906E-02,9.362408E-04,2.210818E-02,4.660373E-04,-7.989601E-04},
EIRFunPLR = {1.370745E-01,8.374817E-01,2.534280E-02},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve";
ElectricEIRChiller York YS 1171kW/9.15COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 1171kW/9.15COP/Valve, !- Name
1171000, !- Reference Capacity {W}
9.15, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
15.56, !- Reference Entering Condenser Fluid Temperature {C}
0.03249, !- Reference Chilled Water Flow Rate {m3/s}
0.05173, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 1171kW/9.15COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.09, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.09, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1171000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03249 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.299045E-01,2.350383E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.325834E-01,-2.611733E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.889392E-01,4.684305E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_1171kW_9_15COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1171000,
COP_nominal = 9.15,
PLRMin = 0.09,
PLRMinUnl = 0.09,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.03249,
mCon_flow_nominal = 1000 * 0.05173,
TEvaLvg_nominal = 273.15 + 6.11,
TConEnt_nominal = 273.15 + 15.56,
TEvaLvgMin = 273.15 + 6.11,
TEvaLvgMax = 273.15 + 12.78,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 23.89,
capFunT = {9.299045E-01,2.350383E-02,-4.649409E-04,-4.367237E-03,-2.040112E-04,6.430038E-04},
EIRFunT = {5.325834E-01,-2.611733E-02,1.365012E-03,4.099324E-02,3.401995E-04,-1.514251E-03},
EIRFunPLR = {1.889392E-01,4.684305E-01,3.451545E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YS 1171kW/9.15COP/Valve";
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve, !- Name
1195600, !- Reference Capacity {W}
6.39, !- Reference COP {W/W}
7.22, !- Reference Leaving Chilled Water Temperature {C}
23.89, !- Reference Entering Condenser Fluid Temperature {C}
0.03653, !- Reference Chilled Water Flow Rate {m3/s}
0.04271, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03653 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04271 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {5.775948E-01,2.206074E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.077824E-01,-1.608447E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.061065E-01,7.305514E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Carrier_23XL_1196kW_6_39COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1195600,
COP_nominal = 6.39,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.03,
mEva_flow_nominal = 1000 * 0.03653,
mCon_flow_nominal = 1000 * 0.04271,
TEvaLvg_nominal = 273.15 + 7.22,
TConEnt_nominal = 273.15 + 23.89,
TEvaLvgMin = 273.15 + 6.67,
TEvaLvgMax = 273.15 + 12.22,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 23.89,
capFunT = {5.775948E-01,2.206074E-02,-3.342365E-03,3.970188E-02,-1.669877E-03,2.762827E-03},
EIRFunT = {5.077824E-01,-1.608447E-02,1.742121E-04,2.093857E-02,4.160938E-04,-7.169668E-04},
EIRFunPLR = {1.061065E-01,7.305514E-01,1.632883E-01},
etaMotor = 1.0)
"ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve";
ElectricEIRChiller York YS 1554kW/9.31COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 1554kW/9.31COP/Valve, !- Name
1554300, !- Reference Capacity {W}
9.31, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
15.56, !- Reference Entering Condenser Fluid Temperature {C}
0.0424, !- Reference Chilled Water Flow Rate {m3/s}
0.07949, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 1554kW/9.31COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1554300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.31 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0424 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07949 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {1.083027E+00,9.278069E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.099117E-01,1.379553E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.720219E-01,5.084848E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_1554kW_9_31COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1554300,
COP_nominal = 9.31,
PLRMin = 0.10,
PLRMinUnl = 0.10,
PLRMax = 1.02,
mEva_flow_nominal = 1000 * 0.0424,
mCon_flow_nominal = 1000 * 0.07949,
TEvaLvg_nominal = 273.15 + 5.56,
TConEnt_nominal = 273.15 + 15.56,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 15.56,
TConEntMax = 273.15 + 35.00,
capFunT = {1.083027E+00,9.278069E-03,1.175024E-03,-1.395851E-02,9.301303E-05,6.968115E-05},
EIRFunT = {5.099117E-01,1.379553E-02,-2.069529E-04,2.846021E-02,7.189977E-04,-2.027317E-03},
EIRFunPLR = {1.720219E-01,5.084848E-01,3.212462E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YS 1554kW/9.31COP/Valve";
ElectricEIRChiller York YS 1758kW/5.84COP/Valve
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller York YS 1758kW/5.84COP/Valve, !- Name
1758300, !- Reference Capacity {W}
5.84, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.07571, !- Reference Chilled Water Flow Rate {m3/s}
0.09464, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller York YS 1758kW/5.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {8.130185E-01,-1.425368E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.381264E-01,6.304193E-03,9... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.149879E-01,3.171267E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_York_YS_1758kW_5_84COP_Valve =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -1758300,
COP_nominal = 5.84,
PLRMin = 0.20,
PLRMinUnl = 0.20,
PLRMax = 1.04,
mEva_flow_nominal = 1000 * 0.07571,
mCon_flow_nominal = 1000 * 0.09464,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 4.44,
TEvaLvgMax = 273.15 + 8.89,
TConEntMin = 273.15 + 12.78,
TConEntMax = 273.15 + 35.00,
capFunT = {8.130185E-01,-1.425368E-02,-1.618007E-03,2.638417E-02,-9.154379E-04,1.696015E-03},
EIRFunT = {6.381264E-01,6.304193E-03,9.233511E-04,-4.552881E-03,8.256904E-04,-1.561533E-03},
EIRFunPLR = {3.149879E-01,3.171267E-01,3.709077E-01},
etaMotor = 1.0)
"ElectricEIRChiller York YS 1758kW/5.84COP/Valve";
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None
Information
Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None, !- Name
207400, !- Reference Capacity {W}
3.99, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.00898, !- Reference Chilled Water Flow Rate {m3/s}
0.01122, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.25, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.25, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition |
HeatFlowRate | QEva_flow_nominal | -207400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.99 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00898 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01122 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves |
Real | capFunT[nCapFunT] | {9.441897E-01,3.371079E-02,9... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.273870E-01,-1.189276E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.146742E-02,6.543795E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
record ElectricEIRChiller_Trane_CGWD_207kW_3_99COP_None =
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (
QEva_flow_nominal = -207400,
COP_nominal = 3.99,
PLRMin = 0.25,
PLRMinUnl = 0.25,
PLRMax = 1.01,
mEva_flow_nominal = 1000 * 0.00898,
mCon_flow_nominal = 1000 * 0.01122,
TEvaLvg_nominal = 273.15 + 6.67,
TConEnt_nominal = 273.15 + 29.44,
TEvaLvgMin = 273.15 + 5.56,
TEvaLvgMax = 273.15 + 10.00,
TConEntMin = 273.15 + 23.89,
TConEntMax = 273.15 + 35.00,
capFunT = {9.441897E-01,3.371079E-02,9.756685E-05,-3.220573E-03,-4.917369E-05,-1.775717E-04},
EIRFunT = {7.273870E-01,-1.189276E-02,5.411677E-04,1.879294E-03,4.734664E-04,-7.114850E-04},
EIRFunPLR = {4.146742E-02,6.543795E-01,3.044125E-01},
etaMotor = 1.0)
"ElectricEIRChiller Trane CGWD 207kW/3.99COP/None";
Automatically generated Wed Feb 12 08:15:18 2014.