LBL logo

Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves

Package with sevral performance curves

Information

This package contains performance curves for the cooling capacity and the EIR of DX cooling coils that are used in the examples.

For performance data of specific DX cooling coils, see the packages Buildings.Fluid.HeatExchangers.DXCoils.Data.SingleSpeed and Buildings.Fluid.HeatExchangers.DXCoils.Data.DoubleSpeed.

The data are described in Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.DXCoil.

Package Content

NameDescription
Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_I Curve_I Curve_I
Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_II Curve_II Curve_II
Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_III Curve_III Curve_III

Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_I Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_I

Curve_I

Information

This record declares performance curves for the cooling capacity and the EIR. It has been obtained from the EnergyPlus 7.1 example file >AirflowNetwork_MultiZone_House.idf>.

Extends from Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.942587793,0.009543347,0.0...Biquadratic coefficients for cooling capacity function of temperature
RealcapFunFF[:]{0.8,0.2,0,0}Polynomial coefficients for cooling capacity function of flow fration
RealEIRFunT[6]{0.342414409,0.034885008,-0....Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.1552,-0.1808,0.0256,0}Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin291.15Minimum condenser inlet temperature for cooling capacity function [K]
TemperatureTConInMax319.26111Maximum condenser inlet temperature for cooling capacity function [K]
TemperatureTEvaInMin285.92778Minimum evaporator inlet temperature for cooling capacity function [K]
TemperatureTEvaInMax297.03889Maximum evaporator inlet temperature for cooling capacity function [K]
RealffMin0.6Minimum flow fraction for which performance data are valid
RealffMax1.8Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_I "Curve_I"
  extends Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.BaseClasses.PerformanceCurve
    (
    each capFunT={0.942587793,0.009543347,0.000683770,-0.011042676,0.000005249,
        -0.000009720},
    each capFunFF={0.8,0.2,0,0},
    each EIRFunT={0.342414409,0.034885008,-0.000623700,0.004977216,0.000437951,
        -0.000728028},
    each EIRFunFF={1.1552,-0.1808,0.0256,0},
    TConInMin=291.15,
    TConInMax = 319.26111,
    TEvaInMin= 285.92778,
    TEvaInMax= 297.03889,
    ffMin=0.6,
    ffMax=1.8);
end Curve_I;

Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_II Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_II

Curve_II

Information

This record declares performance curves for the cooling capacity and the EIR. It has been obtained from the EnergyPlus 7.1 example file >DXCoilSystemAuto.idf>.

Extends from Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.766956,0.0107756,-0.00004...Biquadratic coefficients for cooling capacity function of temperature
RealcapFunFF[:]{0.8,0.2,0,0}Polynomial coefficients for cooling capacity function of flow fration
RealEIRFunT[6]{0.297145,0.0430933,-0.00074...Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.1552,-0.1808,0.0256,0}Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin291.15Minimum condenser inlet temperature for cooling capacity function [K]
TemperatureTConInMax319.26111Maximum condenser inlet temperature for cooling capacity function [K]
TemperatureTEvaInMin285.92778Minimum evaporator inlet temperature for cooling capacity function [K]
TemperatureTEvaInMax297.03889Maximum evaporator inlet temperature for cooling capacity function [K]
RealffMin0.5Minimum flow fraction for which performance data are valid
RealffMax1.5Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_II "Curve_II"
  extends Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.BaseClasses.PerformanceCurve
    (
    each capFunT={0.766956,0.0107756,-0.0000414703,0.00134961,-0.000261144,
        0.000457488},
    each capFunFF={0.8,0.2,0,0},
    each EIRFunT={0.297145,0.0430933,-0.000748766,0.00597727,0.000482112,-0.000956448},
    each EIRFunFF={1.1552,-0.1808,0.0256,0},
    TConInMin=291.15,
    TConInMax = 319.26111,
    TEvaInMin= 285.92778,
    TEvaInMax= 297.03889,
    ffMin=0.5,
    ffMax=1.5);

end Curve_II;

Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_III Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.Examples.PerformanceCurves.Curve_III

Curve_III

Information

This record declares performance curves for the cooling capacity and the EIR. It has been obtained from the EnergyPlus 7.1 example file >5ZoneAutoDXVAV.idf>.

Extends from Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.476428,0.0401147000,0.000...Biquadratic coefficients for cooling capacity function of temperature
RealcapFunFF[:]{0.47278589,1.2433415,-1.038...Polynomial coefficients for cooling capacity function of flow fration
RealEIRFunT[6]{0.632475,-0.0121321000,0.00...Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.0079484,0.34544129,-0.692...Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin297.03889Minimum condenser inlet temperature for cooling capacity function [K]
TemperatureTConInMax319.26111Maximum condenser inlet temperature for cooling capacity function [K]
TemperatureTEvaInMin285.92778Minimum evaporator inlet temperature for cooling capacity function [K]
TemperatureTEvaInMax297.03889Maximum evaporator inlet temperature for cooling capacity function [K]
RealffMin0.5Minimum flow fraction for which performance data are valid
RealffMax1.5Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_III "Curve_III"
  extends Buildings.Fluid.HeatExchangers.DXCoils.Data.Generic.BaseClasses.PerformanceCurve
    (
    each capFunT={0.476428,0.0401147000,0.0002264110,-0.0008271360,-0.0000073224,
        -0.0004462780},
    each capFunFF={0.47278589,1.2433415,-1.0387055,0.32257813},
    each EIRFunT={0.632475,-0.0121321000,0.0005077730,0.0155377000,0.0002728400,
        -0.0006792010},
    each EIRFunFF={1.0079484,0.34544129,-0.6922891, 0.33889943},
    TConInMin = 297.03889,
    TConInMax = 319.26111,
    TEvaInMin = 285.92778,
    TEvaInMax = 297.03889,
    ffMin = 0.5,
    ffMax = 1.5);
end Curve_III;

Automatically generated Thu Oct 24 15:09:16 2013.