This package contains examples for the use of models that can be found in Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).| Name | Description | 
|---|---|
|  YorkCalc | Example for yorkCalc correlation | 
 Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.Examples.YorkCalc
Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.Examples.YorkCalc
| Type | Name | Default | Description | 
|---|---|---|---|
| TemperatureDifference | TRan | 5.56 | Range temperature (water in - water out) [K] | 
| Temperature | TAirInWB | 25.55 + 273.15 | Inlet air wet bulb temperature [K] | 
model YorkCalc "Example for yorkCalc correlation"
  extends Modelica.Icons.Example;
  parameter Modelica.SIunits.TemperatureDifference TRan = 5.56 
    "Range temperature (water in - water out)";
  parameter Modelica.SIunits.Temperature TAirInWB = 25.55 + 273.15 
    "Inlet air wet bulb temperature";
  Modelica.SIunits.MassFraction x "Independent variable";
  Modelica.SIunits.TemperatureDifference TApp_Wat 
    "Approach temperature as a function of FRWat";
  Modelica.SIunits.TemperatureDifference TApp_Air 
    "Approach temperature as a function of FRAir";
equation 
  x = 0.25+time;
  TApp_Wat=Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.yorkCalc(TRan=TRan,
                                                                    TWetBul=TAirInWB,
                                                                    FRWat=x,
                                                                    FRAir=1);
  TApp_Air=Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.yorkCalc(TRan=TRan,
                                                                    TWetBul=TAirInWB,
                                                                    FRWat=1,
                                                                    FRAir=x);
end YorkCalc;