Release notes
This section summarizes the changes that have been performed
on the Buildings library
Package Content
Version 0.5.0
Version 0.4.0
Version 0.3.0
-
Added package Buildings.Fluids.Sources.
The package contains models for modeling species that
do not affect the medium balance of volumes. This can be used to track
for example carbon dioxide or other species that have a small concentration.
-
The package Buildings.Fluids.Actuators.Motors has been added.
The package contains a motor model for valves and dampers.
-
The package Buildings.Media has been reorganized and
the new medium model
Buildings.Media.GasesPTDecoupled.MoistAir
has been added.
In addition, this package now contains a bug fix that is needed for Modelica 2.2.1 and 2.2.2.
The bugs are fixed by using a new
base class
Buildings.Media.Interfaces.PartialSimpleIdealGasMedium
(that fixes the bugs) instead of
Modelica.Media.Interfaces.PartialSimpleIdealGasMedium.
In the original implementation, initial states of fluid volumes can be far away from
the steady-state value because of an inconsistent implementation of the the enthalpy
and internal energy.
When the Buildings library is upgraded to
to Modelica 3.0.0, it should be safe to remove this bug fix.
-
The package Buildings.Fluids.HeatExchangers
has been revised and several models have been renamed.
The heat exchanger models have been revised to allow computing the fluid volumes either
dynamically, or in steady-state.
-
The damper with exponential opening characteristic has been revised to allow control signals
over the whole range between 0 and 1. This was in earlier versions restricted.
In the same model, a bug was fixed that caused the flow to be largest for y=0, i.e., when the damper is closed.
-
Additional models for psychrometric equations have been added. The new models contain equations
that convert dew point temperature and water vapor pressure, as well
as water vapor concentration and water vapor pressure.
-
A new mixing volume has been added that allows latent heat exchange with the volume.
This model can be used to model a volume of moist air with water vapor condensation
inside the volume. The condensate is removed from the volume in its liquid phase.
Version 0.2.0
New in this version are models for two and three way valves.
In addition, the Fluids package has been slightly revised.
The package Fluids.BaseClasses has been added because in
the previous version, partial models for fixed resistances
where part of the Actuator package.
Version 0.1.0
First release of the library.
This version contains basic models for modeling building HVAC systems.
It also contains new medium models in the package
Buildings.Media. These medium models
have simpler property functions than the ones from
Modelica.Media. For example,
there is medium model with constant heat capacity which is often sufficiently
accurate for building HVAC simulation, in contrast to the more detailed models
from Modelica.Media that are valid in
a larger temperature range, at the expense of introducing non-linearities due
to the medium properties.
HTML-documentation generated by Dymola Thu Feb 19 16:50:41 2009.