Name | Description |
---|---|
PartialAbsoluteSensor | Partial component to model a sensor that measures a potential variable |
PartialFlowSensor | Partial component to model sensors that measure flow properties |
Partial component to model an absolute sensor. The component can be used for pressure sensor models. Use for other properties such as temperature or density is discouraged, because the enthalpy at the connector can have different meanings, depending on the connection topology. For these properties, use Buildings.Fluid.Sensors.BaseClasses.PartialFlowSensor.
Type | Name | Description |
---|---|---|
FluidPort_a | port |
partial model PartialAbsoluteSensor "Partial component to model a sensor that measures a potential variable" replaceable package Medium=Modelica.Media.Interfaces.PartialMedium "Medium in the sensor";Modelica.Fluid.Interfaces.FluidPort_a port(redeclare package Medium=Medium, m_flow(min=0)); equation port.m_flow = 0; port.h_outflow = 0; port.Xi_outflow = zeros(Medium.nXi); port.C_outflow = zeros(Medium.nC);end PartialAbsoluteSensor;
Partial component to model a sensor that measures any intensive properties of a flow, e.g., to get temperature or density in the flow between fluid connectors.
The model includes zero-volume balance equations. Sensor models inheriting from this partial class should add a medium instance to calculate the measured property.
Extends from Modelica.Fluid.Interfaces.PartialTwoPort (Partial component with two ports).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate, used for regularization near zero flow [kg/s] | |
Advanced | |||
MassFlowRate | m_flow_small | 1E-4*m_flow_nominal | For bi-directional flow, temperature is regularized in the region |m_flow| < m_flow_small (m_flow_small > 0 required) [kg/s] |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Type | Name | Description |
---|---|---|
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
partial model PartialFlowSensor "Partial component to model sensors that measure flow properties" extends Modelica.Fluid.Interfaces.PartialTwoPort; parameter Medium.MassFlowRate m_flow_nominal(min=0) "Nominal mass flow rate, used for regularization near zero flow"; parameter Medium.MassFlowRate m_flow_small(min=0) = 1E-4*m_flow_nominal "For bi-directional flow, temperature is regularized in the region |m_flow| < m_flow_small (m_flow_small > 0 required)"; equation // mass balance 0 = port_a.m_flow + port_b.m_flow; // momentum equation (no pressure loss) port_a.p = port_b.p; // isenthalpic state transformation (no storage and no loss of energy) port_a.h_outflow = inStream(port_b.h_outflow); port_b.h_outflow = inStream(port_a.h_outflow); port_a.Xi_outflow = inStream(port_b.Xi_outflow); port_b.Xi_outflow = inStream(port_a.Xi_outflow); port_a.C_outflow = inStream(port_b.C_outflow); port_b.C_outflow = inStream(port_a.C_outflow);end PartialFlowSensor;