Buildings.Media.Conversions.Validation
Package with validation models
Information
This package contains validation models for the models in Buildings.Media.Conversions.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
| Name | Description |
|---|---|
| Validation model for Buildings.Media.Conversions.FlowResistance.pressureDrop_massFlowRate |
Buildings.Media.Conversions.Validation.PressureDrop_massFlowRate
Validation model for Buildings.Media.Conversions.FlowResistance.pressureDrop_massFlowRate
Information
Validation model for Buildings.Media.Conversions.FlowResistanceFlowWork.pressureDrop_massFlowRate.
The model computes the ratio of pressure drops dpRat_m_flow
when the working fluid is changed from water to a 25% volume fraction
propylene glycol-water mixture, both evaluated at 20°C.
The mass flow rate ratio ratio_m_flow varies linearly from
0.5 to 1.5 over the simulation period of 1 second.
The pressure drop ratio is computed for turbulent flow, i.e., n=2.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | n | 1.688 | Flow coefficient n, n=1 for laminar, n=1.688 for turbulent flow |
| Real | dpRat_equalHeatFlowRate | FloRes.pressureDrop_equalHea... | Pressure drop ratio for equal heat flow rate at turbulent flow [1] |