Buildings.Fluid.HeatExchangers.CoolingTowers.Data.YorkCalc
Performance data records for wet cooling towers using the York calculation method
Information
This package contains performance data records for wet cooling towers that use the York calculation method. The data records can be used with the model Buildings.Fluid.HeatExchangers.CoolingTowers.YorkCalc.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
| Name | Description |
|---|---|
| Performance data record for a wet cooling cooler using the York calculation method |
Buildings.Fluid.HeatExchangers.CoolingTowers.Data.YorkCalc.Generic
Performance data record for a wet cooling cooler using the York calculation method
Information
Performance data record for a wet cooling cooler using the York calculation methods.
The default settings are for a cooler with a design approach temperature (cooling out - air wet bulb in) of 3.89 K and a design range temperature (cooling in - cooling out) of 5.56 K. This corresponds to a nominal water inlet temperature of 35 °C and a nominal water outlet temperature of 29.44 °C.
Extends from Buildings.Fluid.HeatExchangers.CoolingTowers.Data.BaseClasses.BaseCoolingTower (Performance data record for dry and wet cooling towers).
Contents
| Type | Name | Default | Description |
|---|---|---|---|
| Real | PFan_Q_flow_nominal | -0.05 | Ratio of fan power to provided cooling at full load (negative as Q_flow_nominal<0) [1] |
| Nominal thermal performance | |||
| HeatFlowRate | Q_flow_nominal | Nominal heat flow rate (negative, as heat is removed from the fluid) [W] | |
| Temperature | TCooIn_nominal | 308.15 | Nominal cooling loop inlet temperature [K] |
| Temperature | TCooOut_nominal | 302.59 | Nominal cooling loop outlet temperature [K] |
| Temperature | TAirInWB_nominal | 298.7 | Nominal outdoor (air inlet) wetbulb temperature [K] |
| Nominal condition | |||
| PressureDifference | dp_nominal | Pressure difference at design mass flow rate [Pa] | |
| Advanced | |||
| Real | ratCooAir_nominal | Buildings.Fluid.HeatExchange... | Coolant-to-air mass flow rate ratio at design condition, used to compute air flow rate for UA_value [1] |
| fan | fanRelPow | Fan relative power consumption as a function of control signal, fanRelPow=P(y)/P(y=1) | |
| Real | fraFreCon | 0.125 | Fraction of tower capacity in free convection regime [1] |