Buildings.Fluid.HeatExchangers.CoolingTowers.Data.DryCooler.BaseClasses
Package with base classes for dry cooling tower data records
Information
This package contains base classes that are used to construct the data records in Buildings.Fluid.HeatExchangers.CoolingTowers.Data.Merkel.
Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).
Package Content
| Name | Description |
|---|---|
| UA correction factors for Merkel cooling towers |
Buildings.Fluid.HeatExchangers.CoolingTowers.Data.DryCooler.BaseClasses.UACorrection
UA correction factors for Merkel cooling towers
Information
This data record specifies parameters for the flow and temperature correction of the convective heat transfer coefficients used in the model Buildings.Fluid.HeatExchangers.CoolingTowers.DryCooler.
Extends from Modelica.Icons.Record (Icon for records).
Contents
| Type | Name | Default | Description |
|---|---|---|---|
| Real | n_w | 0.85 | Water-side exponent for convective heat transfer coefficient, h~m_flow^n |
| Real | n_a | 0.8 | Air-side exponent for convective heat transfer coefficient, h~m_flow^n |
| Nominal condition | |||
| Real | r_nominal | 0.5 | Ratio between air-side and water-side convective heat transfer coefficient |
| Advanced | |||
| Modeling detail | |||
| Boolean | waterSideFlowDependent | true | Set to false to make water-side hA independent of mass flow rate |
| Boolean | airSideFlowDependent | true | Set to false to make air-side hA independent of mass flow rate |
| Boolean | waterSideTemperatureDependent | true | Set to false to make water-side hA independent of temperature |
| Boolean | airSideTemperatureDependent | true | Set to false to make air-side hA independent of temperature |
Modelica definition
record UACorrection "UA correction factors for Merkel cooling towers"
extends Modelica.Icons.Record;
parameter Real r_nominal(min=0)=0.5
"Ratio between air-side and water-side convective heat transfer coefficient";
parameter Real n_w(min=0, max=1)=0.85
"Water-side exponent for convective heat transfer coefficient, h~m_flow^n";
parameter Real n_a(min=0, max=1)=0.8
"Air-side exponent for convective heat transfer coefficient, h~m_flow^n";
parameter Boolean waterSideFlowDependent=true
"Set to false to make water-side hA independent of mass flow rate";
parameter Boolean airSideFlowDependent = true
"Set to false to make air-side hA independent of mass flow rate";
parameter Boolean waterSideTemperatureDependent = true
"Set to false to make water-side hA independent of temperature";
parameter Boolean airSideTemperatureDependent = true
"Set to false to make air-side hA independent of temperature";
end UACorrection;