Buildings.DHC.Networks.Pipes.Validation
Validation models for Pipes
Information
This package contains validation cases for the BaseClasses found in Buildings.DHC.Networks.Pipes.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
| Name | Description | 
|---|---|
|  Pipe | Validates the PipeAutosize model initialization | 
 Buildings.DHC.Networks.Pipes.Validation.Pipe
Buildings.DHC.Networks.Pipes.Validation.Pipe
Validates the PipeAutosize model initialization
 
Information
Validation model for Buildings.DHC.Networks.Combined.BaseClasses.PipeAutosize for range of flow rates and pressure drops per unit length.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
| Type | Name | Default | Description | 
|---|---|---|---|
| Real | dp1_length_nominal | 1000 | Pressure drop per unit length 1 [Pa/m] | 
| Real | dp2_length_nominal | 0.1 | Pressure drop per unit length 2 [Pa/m] | 
| MassFlowRate | m1_flow_nominal | 0.01 | Nominal mass flow rate 1 [kg/s] | 
| MassFlowRate | m2_flow_nominal | 1000 | Nominal mass flow rate 2 [kg/s] | 
Modelica definition
model Pipe "Validates the PipeAutosize model initialization"
  extends Modelica.Icons.Example;
  package Medium = Buildings.Media.Water "Medium model";
  parameter Real dp1_length_nominal(final unit="Pa/m") = 1000 "Pressure drop per unit length 1";
  parameter Real dp2_length_nominal(final unit="Pa/m") = 0.1 "Pressure drop per unit length 2";
  parameter Modelica.Units.SI.MassFlowRate m1_flow_nominal = 0.01 "Nominal mass flow rate 1";
  parameter Modelica.Units.SI.MassFlowRate m2_flow_nominal = 1000 "Nominal mass flow rate 2";
  Buildings.Fluid.Sources.Boundary_pT sin(redeclare final package Medium = Medium,
   nPorts=4) "Sink for water flow";
  Buildings.DHC.Networks.Pipes.PipeStandard pipSta1(
    redeclare final package Medium = Medium,
    m_flow_nominal=m1_flow_nominal,
    dh=0.00548,
    length=100) "Pipe 1 with standard hydraulic diameter";
  Buildings.Fluid.Sources.MassFlowSource_T souSta1(
    redeclare final package Medium = Medium,
    m_flow=m1_flow_nominal,
    nPorts=1) "Source of water flow for standard pipe 1";
  Buildings.Fluid.Sources.MassFlowSource_T souAut2(
    redeclare final package Medium = Medium,
    m_flow=m2_flow_nominal,
    nPorts=1) "Source of water flow for autosized pipe 2";
  Buildings.DHC.Networks.Pipes.PipeAutosize pipAut2(
    redeclare final package Medium = Medium,
    m_flow_nominal=m2_flow_nominal,
    dp_length_nominal=dp2_length_nominal,
    length=100) "Pipe 2 with autosized hydraulic diameter";
  Fluid.Sources.MassFlowSource_T souAut1(
    redeclare final package Medium = Medium,
    m_flow=m1_flow_nominal,
    nPorts=1) "Source of water flow for autosized pipe 1";
  Pipes.PipeAutosize pipAut1(
    redeclare final package Medium = Medium,
    m_flow_nominal=m1_flow_nominal,
    dp_length_nominal=dp1_length_nominal,
    length=100) "Pipe 1 with autosized hydraulic diameter";
  Pipes.PipeStandard pipSta2(
    redeclare final package Medium = Medium,
    m_flow_nominal=m2_flow_nominal,
    dh=2.943,
    length=100) "Pipe 2 with standard hydraulic diameter";
  Fluid.Sources.MassFlowSource_T souSta2(
    redeclare final package Medium = Medium,
    m_flow=m2_flow_nominal,
    nPorts=1) "Source of water flow for standard pipe 2";
equation 
  connect(souSta1.ports[1], pipSta1.port_a);
  connect(souAut2.ports[1], pipAut2.port_a);
  connect(souAut1.ports[1], pipAut1.port_a);
  connect(souSta2.ports[1], pipSta2.port_a);
  connect(pipAut1.port_b, sin.ports[1]);
  connect(pipAut2.port_b, sin.ports[2]);
  connect(pipSta1.port_b, sin.ports[3]);
  connect(pipSta2.port_b, sin.ports[4]);
end Pipe;