Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Validation
Collection of validation models
Information
This package contains validation models for the classes in Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.
Note that most validation models contain simple input data which may not be realistic, but for which the correct output can be obtained through an analytic solution. The examples plot various outputs, which have been verified against these solutions. These model outputs are stored as reference data and used for continuous validation whenever models in the library change.
Package Content
| Name | Description |
|---|---|
| Validate the control of inline valve | |
| Validate the control of heat exchanger pump | |
| Validate water side economizer outlet temperature prediction | |
| Validate water side economizer tuning parameter sequence |
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Validation.BypassValve
Validate the control of inline valve
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.BypassValve.
The validation shows that when the plant is enabled in waterside mode
(uPla=true and uWSE=true):
-
The condenser water isolation valve to the heat exchanger will be fully
open (
yConIsoVal=1). -
The economizer in-line chilled water return line valve will be enabled,
with the initial position as fully open (
yRetVal=1). -
The return line valve will be modulated to maintain the static pressure
difference (
dpChiWat) across the chilled water side of the heat exchanger at the design value (dpDes).
If the economizer is disabled (uWSE=false), the condenser water
isolation valve to the heat exchanger should be fully closed, and the return
line valve should be disabled in the fully open position.
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Validation.HeatExchangerPump
Validate the control of heat exchanger pump
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.HeatExchangerPump. It demonstrates the process of controlling the heat exchanger pump in the following scenarios:
-
At 720 seconds, the plant is enabled in waterside economizer mode. The heat exchange pump becomes enabled
(
yPumOn=true) and the condenser water isolation valve becomes fully open (yConWatIsoVal=1). - From 720 seconds to 2880 seconds, the pump speed is adjusted by the Trim and Respond sequence based on the speed reset requests that are generated based on the temperature difference between the chilled water return temperature upstream of the economizer and the chilled water temperature entering the heat exchanger.
- At 2880 seconds, the economizer becomes disabled. Thus, the pump is disabled, and the pump speed setpoint becomes 0.
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Validation.PredictedOutletTemperature
Validate water side economizer outlet temperature prediction
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.PredictedOutletTemperature.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | aveTWetBul | 288.15 | Chilled water supply set temperature [K] |
| Real | aveVChiWat_flow | 0.01 | Average measured chilled water return temperature [m3/s] |
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Validation.Tuning_uEcoSta_uTowFanSpeMax
Validate water side economizer tuning parameter sequence
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning.