Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24
Complying California Title 24
Information
This package contains sequences to set the minimum outdoor airflow setpoint for compliance with the ventilation rate procedure of California Title 24. It is implemented according to Section 5.16.3.2 of ASHRAE Guideline G36, May 2020.
- Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.AHU conducts AHU level calculations for specifying minimum outdoor airflow rate,
- and Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone finds the sums of outputs from zone level calculations. They become inputs of AHU level calculation.
Package Content
Name | Description |
---|---|
![]() |
AHU level setpoint calculation |
![]() |
Sum of the zone level setpoints calculation |
![]() |
Collection of validation models |
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.AHU
AHU level setpoint calculation
Information
This sequence outputs AHU level effective outdoor air absolute minimum and design
minimum setpoints VEffAbsOutAir_flow
, VEffDesOutAir_flow
and
the nomalized minimum setpoint effOutAir_normalized
when complying with California Title 24 ventilation requirements.
It is implemented according to Section 5.16.3.2 of ASHRAE
Guideline G36, May 2020.
It calculates as below:
-
See the sum of zone absolute and design minimum outdoor airflow setpoint
VSumZonAbsMin_flow
andVSumZonDesMin_flow
from Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone for the detailed description. -
Effective outdoor air absolute minimum and design minimum setpoints
(
VEffAbsOutAir_flow
andVEffDesOutAir_flow
) are recalculated continuously based on the mode of the zones being served.-
Effective outdoor air absolute minimum setpoint
VEffAbsOutAir_flow
is the sum ofVZonAbsMin_flow
for all zones in all zone groups that are in occupied mode but shall be no larger than the absolute minimum outdoor airflowVAbsOutAir_flow
. -
Effective outdoor air design minimum setpoint
VEffDesOutAir_flow
is the sum ofVZonDesMin_flow
for all zones in all zone groups that are in occupied mode but shall be no larger than the absolute minimum outdoor airflowVDesOutAir_flow
.
-
Effective outdoor air absolute minimum setpoint
-
According to section 5.16.4, 5.16.5 and 5.16.6, the effective minimum outdoor airflow
setpoint should be reset based on the highest zone CO2 control- loop signal from
VEffAbsOutAir_flow
at 50% signal toVEffDesOutAir_flow
at 100% signal. When there is no CO2 sensor in any zone, the effective minimum outdoor airflow setpoint should be equal to theVEffDesOutAir_flow
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | have_CO2Sen | True: there are zones have CO2 sensor | |
Economizer design | |||
OutdoorAirSection | minOADes | Type of outdoor air section | |
Nominal condition | |||
Real | VAbsOutAir_flow | Design outdoor airflow rate when all zones with CO2 sensors or occupancy sensors are unpopulated [m3/s] | |
Real | VDesOutAir_flow | Design minimum outdoor airflow rate with the areas served by the system are occupied at their design population, including diversity where applicable [m3/s] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | VSumZonAbsMin_flow | Sum of the zone absolute minimum outdoor airflow setpoint [m3/s] |
input RealInput | VSumZonDesMin_flow | Sum of the zone design minimum outdoor airflow setpoint [m3/s] |
input RealInput | uCO2Loo_max | Maximum Zone CO2 control loop [1] |
input RealInput | VAirOut_flow | Measured outdoor air volumetric flow rate [m3/s] |
output RealOutput | VEffAbsOutAir_flow | Effective outdoor air absolute minimum setpoint [m3/s] |
output RealOutput | effAbsOutAir_normalized | Effective minimum outdoor airflow setpoint, normalized by the absolute outdoor airflow rate [1] |
output RealOutput | VEffDesOutAir_flow | Effective outdoor air design minimum setpoint [m3/s] |
output RealOutput | effDesOutAir_normalized | Effective minimum outdoor airflow setpoint, normalized by the design outdoor airflow rate [1] |
output RealOutput | effOutAir_normalized | Effective minimum outdoor airflow setpoint, normalized by the design total outdoor airflow rate [1] |
output RealOutput | outAir_normalized | Normalized outdoor airflow rate [1] |
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone
Sum of the zone level setpoints calculation
Information
This sequence sums up zone level minimum outdoor airflow setpoints when complying with California Title 24 ventilation requirements. It is implemented according to Section 5.16.3.2 of ASHRAE Guideline G36, May 2020.
It calculates following values:
-
Sum of the zone absolute minimum outdoor airflow setpoint
VZonAbsMin_flow
for all zones in all zone groups that are in occupied mode. -
Sum of the zone design minimum outdoor airflow setpoint
VZonDesMin_flow
for all zones in all zone groups that are in occupied mode. -
Maximum zone level CO2 control loop signal
yMaxCO2
.
See the zone absolute and design minimum outdoor airflow setpoint
VZonAbsMin_flow
and VZonDesMin_flow
from
Buildings.Controls.OBC.ASHRAE.G36.VentilationZones.Title24.Setpoints for the detailed
description.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nZon | Total number of serving zones | |
Integer | nGro | Total number of groups | |
Integer | zonGroMat[nGro, nZon] | Zone matrix with zone group as row index and zone as column index. It flags which zone is grouped in which zone group | |
Boolean | have_CO2Sen | True: some zones have CO2 sensor |
Connectors
Type | Name | Description |
---|---|---|
input IntegerInput | uOpeMod[nGro] | Groups operation mode |
input RealInput | VZonAbsMin_flow[nZon] | Zone absolute minimum outdoor airflow setpoint [m3/s] |
input RealInput | VZonDesMin_flow[nZon] | Zone design minimum outdoor airflow setpoint [m3/s] |
input RealInput | uCO2[nZon] | Zone CO2 control loop [1] |
output RealOutput | VSumZonAbsMin_flow | Sum of the zone absolute minimum outdoor airflow setpoint [m3/s] |
output RealOutput | VSumZonDesMin_flow | Sum of the zone design minimum outdoor airflow setpoint [m3/s] |
output RealOutput | yMaxCO2 | Maximum CO2 control loop signal [1] |