Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Modulations
Package of sequences to modulate economizer dampers
Information
The package contains the sequences to modulate the economizer dampers. The damper control depends on the type of building pressure control system.
Package Content
Name | Description |
---|---|
![]() |
Modulates dampers of economizer in buildings using relief damper or fan to control the pressure |
![]() |
Modulates dampers of economizer in buildings using return fan to control the pressure |
![]() |
Collection of validation models |
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Modulations.Reliefs
Modulates dampers of economizer in buildings using relief damper or fan to control the pressure
Information
This is a multi zone VAV AHU economizer modulation block. It calculates the outdoor and return air damper positions based on the supply air temperature control loop signal. It is implemented according to Section 5.16.2.3.d, Figure 5.16.2.3-1 of ASHRAE Guideline 36, May 2020. Damper positions are linearly mapped to the supply air control loop signal.
When the economizer is enabled, the PI controller modulates the damper positions. Return and outdoor damper are not interlocked. When the economizer is disabled, the damper positions are set to the minimum outdoor air damper position limits.
The control charts below show the input-output structure and an economizer damper modulation sequence assuming a well configured controller. Control diagram:
Multi zone AHU economizer modulation control chart:
Parameters
Type | Name | Default | Description |
---|---|---|---|
Commissioning | |||
Controller | |||
Real | uMin | -0.25 | Lower limit of controller input when outdoor damper opens (see diagram) [1] |
Real | uMax | +0.25 | Upper limit of controller input when return damper is closed (see diagram) [1] |
Real | uOutDamMax | (uMin + uMax)/2 | Maximum loop signal for the OA damper to be fully open [1] |
Real | uRetDamMin | (uMin + uMax)/2 | Minimum loop signal for the RA damper to be fully open [1] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | uTSup | Signal for supply air temperature control (T Sup Control Loop Signal in diagram) [1] |
input RealInput | uOutDam_min | Minimum economizer damper position limit as returned by the damper position limits sequence [1] |
input RealInput | uOutDam_max | Maximum economizer damper position limit as returned by the economizer enable-disable sequence. If the economizer is disabled, this value equals uOutDam_min [1] |
input RealInput | uRetDam_min | Minimum return air damper position limit as returned by the economizer enable-disable sequence [1] |
input RealInput | uRetDam_max | Maximum return air damper position limit as returned by the economizer enable-disable sequence [1] |
output RealOutput | yOutDam | Economizer damper commanded position [1] |
output RealOutput | yRetDam | Return air damper commanded position [1] |
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Modulations.ReturnFan
Modulates dampers of economizer in buildings using return fan to control the pressure
Information
Block modulates the damper of economizers of buildings with pressure controlled by return fan and airflow tracking. It is implemented according to Section 5.16.2.3.d, Figure 5.16.2.3-2 and Figure 5.16.2.3-3 of ASHRAE Guideline 36, May 2020.
Return air damper position limits, which are the inputs to the sequence, are the outputs of
sequences in package
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.
It also requires input uTSup
from
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.SupplySignals
sequences.
The time rate of change of the damper signals is limited by a first order hold,
using the sample time samplePeriod
.
This prevents a quick opening of the outdoor air damper, for example when the
outdoor airflow setpoint has a step change.
Slowing down the opening of the outdoor air damper allows the freeze protection
to componensate with its dynamics that is faster than the opening of the outdoor air damper.
To avoid that all dampers are closed, the return air damper has the same
time rate of change limitation.
The modulation is shown as the control chart:
Note in the above chart, if the building has direct pressure control
(have_dirCon
), the profile for relief air damper control should
be ignored.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | have_dirCon | true | True: the building have direct pressure control |
Commissioning | |||
Controller | |||
Real | uMin | -0.25 | Lower limit of controller input when outdoor damper opens (see diagram) [1] |
Real | uMax | +0.25 | Upper limit of controller input when return damper is closed (see diagram) [1] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | uTSup | Supply air temperature control loop signal [1] |
input RealInput | uRetDam_max | Maximum return air damper position limit as returned by the economizer enable-disable sequence [1] |
input RealInput | uRetDam_min | Minimum return air damper position limit as returned by the economizer enable-disable sequence [1] |
output RealOutput | yRetDam | Return air damper position [1] |
output RealOutput | yRelDam | Relief air damper position [1] |
output RealOutput | yOutDam | Outdoor air damper position [1] |