Buildings.Fluid.Sensors.UsersGuide Buildings.Fluid.Sensors.UsersGuide


This package contains models of sensors. There are models with one and with two fluid ports.

Note that sensors with two ports should be used if the measured quantity depends on the direction of the flow, such as temperature, relative humidity or density. The use of sensors with one fluid port is discouraged for such quantities, unless the sensor is directly connected to the port of a volume in the package Buildings.Fluid.MixingVolumes. For an explanation, see Modelica.Fluid.Examples.Explanatory.MeasuringTemperature.

For quantities that do not depend on the flow direction, such as static pressure, sensors with one or with two ports can be used for all connection topologies.

Extends from Modelica.Icons.Info (Icon for general information packages).